City water should be piped to an open sight drain.
If water from the machine chilled water circuit is used for oil cooling, it should enter the oil
cooler inlet from the entering water line of the machine cooler. See
Figure 12
. Water leaving the
oil cooler should connect to the leaving water line of the machine cooler to a point downstream
from the chilled water sensor, so that oil cooler leaving water temperature does not affect the
sensor readings. See
Figure 12
.
Locate the oil cooler leaving water connection at some distance from any chilled water
temperature indicator. On single-pass machines, water leaving the oil cooler should be
connected into the suction side of the chilled water pump so that adequate pressure drop is
assured for oil cooling.
The nominal conditions for oil cooler water flow are:
Flow rate . . . . . . . . . . . . . . . . . . . 30 gpm (114 L/s)
Leaving temperature (max) . . . . . 85 F to 100 F (29 to 39 C)
Pressure drop at oil cooler . . . . . . 10.5 ft (3.2 m)
Max differential pressure across
closed solenoid valve . . . . . . . . . 150 psid (1029 kPa)
The oil cooler water connections at the plug valve are 1-in. FPT.
Click here for Figure 12 — Water Piping, Oil Cooler to Chilled Water Circuit
(Typical)
Summary of Contents for HFC-134a
Page 40: ...Figure 1 Model Number Identification ...
Page 41: ...Figure 2 Typical 19FA Installation 1400 2200 Tons 4922 7735 kW ...
Page 42: ...Figure 3 Machine Rigging Guide 3 Indicates center of gravity ...
Page 44: ...Figure 5 Machine Footprint ...
Page 45: ...Figure 6 Machine Contact Surfaces with Anchor Bolts ...
Page 51: ...Figure 12 Water Piping Oil Cooler to Chilled Water Circuit Typical ...
Page 52: ...Figure 13 Pumpout Unit ...
Page 53: ...Figure 14 Typical 19FA Relief Valve Tree for Storage Vessel ...
Page 54: ...Figure 15 Compressor Terminal Arrangement 18 Lead Rear Inlet ...
Page 55: ...Figure 16 Compressor Terminal Arrangement 18 Lead Top Inlet ...
Page 56: ...Figure 17 Compressor Terminal Arrangement 18 Lead Side Inlet ...
Page 57: ...Figure 18 Oil Pump Wiring ...
Page 58: ...Figure 19 Oil Heater and Control Power Wiring ...
Page 59: ...Figure 20 Pumpout Unit Controls ...
Page 60: ...Figure 21 Pumpout Unit Wiring Schematic ...
Page 61: ...Figure 22 Carrier Comfort Network Communication Bus Wiring ...
Page 62: ...Figure 23 COMM1 CCN Communication Wiring For Multiple Chillers Typical ...
Page 63: ...Figure 24 Typical 19FA With Free Standing Starter ...
Page 65: ...Figure 26 19FA Insulation ...