To connect the 19FA chiller to the network, proceed as follows (
Figure 23
):
1. Cut power to the Product Integrated Control (PIC) center.
2. Remove the COMM1 plug from the processor module.
3. Cut a CCN wire and strip the ends of the RED, WHITE, and BLACK conductors.
4. Using a wirenut, connect the drain wires together.
5. Insert and secure the RED wire to Terminal 1 of the COMM1 plug.
6. Insert and secure the WHITE wire to Terminal 2 of the COMM1 plug.
7. Insert and secure the BLACK wire to Terminal 3 of the COMM1 plug.
8. Mount a terminal strip in a convenient location.
9. Connect the opposite ends of each conductor to separate terminals on the terminal strip.
10. Cut another CCN wire and strip the ends of the conductors.
11. Connect the RED wire to the matching location on the terminal strip.
12. Connect the WHITE wire to the matching location on the terminal strip.
13. Connect the BLACK wire to the matching location on the terminal strip.
Click here for Figure 22 — Carrier Comfort Network Communication Bus Wiring
Summary of Contents for HFC-134a
Page 40: ...Figure 1 Model Number Identification ...
Page 41: ...Figure 2 Typical 19FA Installation 1400 2200 Tons 4922 7735 kW ...
Page 42: ...Figure 3 Machine Rigging Guide 3 Indicates center of gravity ...
Page 44: ...Figure 5 Machine Footprint ...
Page 45: ...Figure 6 Machine Contact Surfaces with Anchor Bolts ...
Page 51: ...Figure 12 Water Piping Oil Cooler to Chilled Water Circuit Typical ...
Page 52: ...Figure 13 Pumpout Unit ...
Page 53: ...Figure 14 Typical 19FA Relief Valve Tree for Storage Vessel ...
Page 54: ...Figure 15 Compressor Terminal Arrangement 18 Lead Rear Inlet ...
Page 55: ...Figure 16 Compressor Terminal Arrangement 18 Lead Top Inlet ...
Page 56: ...Figure 17 Compressor Terminal Arrangement 18 Lead Side Inlet ...
Page 57: ...Figure 18 Oil Pump Wiring ...
Page 58: ...Figure 19 Oil Heater and Control Power Wiring ...
Page 59: ...Figure 20 Pumpout Unit Controls ...
Page 60: ...Figure 21 Pumpout Unit Wiring Schematic ...
Page 61: ...Figure 22 Carrier Comfort Network Communication Bus Wiring ...
Page 62: ...Figure 23 COMM1 CCN Communication Wiring For Multiple Chillers Typical ...
Page 63: ...Figure 24 Typical 19FA With Free Standing Starter ...
Page 65: ...Figure 26 19FA Insulation ...