background image

5

COIL

SUPPORT

RAIL

COIL

BRACKET

DRAIN PAN

SUPPORT

BRACKET

COIL

SUPPORT

RAIL

COIL

BRACKET

HORIZONTAL

DRAIN PAN

PRIMARY DRAIN

HORIZONTAL RIGHT

SECONDARY DRAIN

HORIZONTAL RIGHT

REFRIGERANT

CONNECTIONS

AIR SEAL
ASSEMBLY

A

B

C

HORIZONTAL

RIGHT

APPLICATION

A00071

Fig. 7 -- A--Coil in Horizontal--Right Application

E. Horizontal Right Conversion of Units With A--Coil

To convert units for horizontal right installations:

1. Remove blower and coil access panels. (See Fig. 6.)
2. Remove metal clip securing fitting panel to condensate pan.

Remove fitting panel.

3. Remove 2 snap--in clips securing A--coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil sup-

port rail on left side of unit and reinstall on coil support rail

on right side of unit.

6. Convert air--seal assembly for horizontal right.

a. Remove air--seal assembly from coil by removing 4

screws. (See Fig. 6.)

b. Remove air splitter (B) from coil seal assembly by re-

moving 3 screws. (See Fig. 6--factory--shipped inset.)

c. Remove filler plate (A) and install air splitter (B) in

place of filler plate.

d. Install filler plate (A) as shown in horizontal right ap-

plication.

e. Remove condensate troughs (C) and install on opposite

tube sheets.

f. Install hose onto plastic spout.

7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each

corner of vertical pan engages coil support rails.

9. Reinstall 2 snap--in clips to correctly position and secure

coil assembly in unit. Be sure clip with large offset is used
on right side of unit to secure horizontal pan.

10. Remove two oval fitting caps from left side of the coil, ac-

cess panel, and fitting panel.

11. Remove insulation knockouts on right side of coil access

panel

12. Remove 2 oval coil access panel plugs and reinstall into

holes on left side of coil access panel and fitting panel.

13. Install condensate pan fitting caps (from Step 10) in the

right side of the coil door making sure that the cap snaps

and seats cleanly on the back side of the coil door. Make
sure no insulation interferes with seating of the cap.

14. Reinstall access and fitting panels, aligning holes with

tubing connections and condensate pan connections. Be
sure to reinstall metal clip between fitting panel and vertical

condensate pan.

Make sure liquid and suction tube grommets are in place to prevent

air leaks and cabinet sweating.

F. Downflow Installations

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or property

damage.
The conversion of the fan coil to downflow requires special

procedures for the condensate drains on both A--coil and slope

units. The vertical drains have an overflow hole between the

primary and secondary drain holes. This hole is plugged for all

applications except downflow, but must be used for downflow.

During the conversion process, remove the plastic cap

covering the vertical drains only and discard. Remove the plug

from the overflow hole and discard. At completion of the

downflow installation, caulk around the vertical pan fitting to

door joint to retain the low air leak performance of the unit.

CAUTION

!

In this application, field conversion of the evaporator is required

using accessory downflow kit along with an accessory base kit.
Use fireproof resilient gasket, 1/8-- to 1/4--in. (3.2 to 6.4mm) thick,

between duct, unit, and floor.

NOTE

: To convert units for downflow applications, refer to

Installation Instructions supplied with kit for proper installation.
For slope fan coils, use kit Part No. KFADC0201SLP. For A fan
coils use kit Part No. KFADC0401ACL. Use fireproof resilient

FV4

C

 

 

 

Summary of Contents for FV4C

Page 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Page 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Page 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Page 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Page 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Page 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Page 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Page 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Page 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Page 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Page 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Page 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Page 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Page 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Page 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Page 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Page 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Page 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: