15
Table 3 – FV4C Fan Coil Airflow Delivery (CFM) in Cooling Mode
OPERATING MODE
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
SINGLE—SPEED
APPLICATION
TWO—SPEED APPLICATION
FAN ONLY
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
High Speed
Low Speed
Lo
Med
High
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
002
018
525
420
—
—
—
—
350
420
525
024
700
560
700
560
560
450
350
560
700
030
875
700
—
—
—
—
440
700
875
036
1050
840
1050
840
840
670
525
840
1050
003
024
700
560
700
560
560
450
415
560
700
030
875
700
—
—
—
—
440
700
875
036
1050
840
1050
840
840
670
525
840
1050
042
1225
980
—
—
—
—
610
980
1225
005
030
875
700
—
—
—
—
440
700
875
036
1050
840
1050
840
840
670
525
840
1050
042
1225
980
—
—
—
—
610
980
1225
048
1400
1120
1400
1120
1120
895
700
1120
1400
006
036
1050
840
1050
840
840
670
540
840
1050
042
1225
980
—
—
—
—
610
980
1225
048
1400
1120
1400
1120
1120
895
700
1120
1400
060
1750
1400
1750
1400
1400
1120
875
1400
1750
NOTES
:
1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM.
2. Air flow can be ad15% or ---10% by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10KW heater and filter installed.
4. Airflows shown are at standard air conditions.
Table 4 – FV4C Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode
OPERATING MODE
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
SINGLE—SPEED
APPLICATION
TWO—SPEED APPLICATION
FAN ONLY
Heat Pump
Comfort
Heat Pump
Efficiency
High Speed
Low Speed
Lo
Med
High
Heat Pump
Comfort
Heat Pump
Efficiency
Heat Pump
Comfort
Heat Pump
Efficiency
002
018
470
525
—
—
—
—
350
380
470
024
630
700
630
700
505
560
350
505
630
030
785
875
—
—
—
—
390
630
785
036
945
1050
945
1050
755
840
470
755
945
003
024
630
700
630
700
415
560
415
505
630
030
785
875
—
—
—
—
415
630
785
036
945
1050
945
1050
755
840
470
755
945
042
1100
1225
—
—
—
—
550
880
1100
005
030
785
875
—
—
—
—
425
630
785
036
945
1050
945
1050
755
840
470
755
945
042
1100
1225
—
—
—
—
550
880
1100
048
1260
1400
1260
1400
1010
1120
630
1010
1260
006
036
945
1050
945
1050
755
840
540
755
945
042
1100
1225
—
—
—
—
550
880
1100
048
1260
1400
1260
1400
1010
1120
630
1010
1260
060
1575
1750
1575
1750
1260
1400
785
1260
1575
NOTES
:
1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM.
2. Air flow can be ad15% or ---10% by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10KW heater and filter installed.
4. Airflows shown are at standard air conditions.
FV4
C