background image

11

heater operation. The factory selection is the largest heater range
approved. (See Fig. 17, A as indicated.)

B. AC/HP SIZE -- Select system size installed

The factory setting for air conditioner or heat pump size is the

largest unit meant for application with the model of fan coil
purchased. Installer needs to select air conditioner or heat pump

size to ensure that airflow delivered falls within proper range for

the size unit installed. This applies to all operational modes with
the exception of electric heat modes. (See Fig. 17, B as indicated.)

C. SYSTEM TYPE -- Select system type installed AC or HP

The type of system must be selected:

1. AC -- Air conditioner
2. HP--COMFORT -- Heat Pump Comfort provides approxim-

ately 315 CFM per ton for higher normal heating air deliv-
ery temperature. Provides approximately 350 CFM per ton
cooling airflow for good humidity removal.

3. HP--EFF -- Heat Pump Efficiency provides same airflow for

heating and cooling modes to increase overall HP effi-

ciency; approximately 350 CFM per ton. The factory setting
is AC. (See Fig. 17, C as indicated.)

D. AC/HP CFM ADJUST -- Select Medium, Low, or High

Airflow

To provide airflow at rates described above, the AC/HP ADJUST

select is factory set to the nominal (nom) tap. The adjust selections

HI/LO will regulate airflow supplied for all operational modes,
except non--heat pump heating modes. HI provides 15% airflow

over nominal unit size selected and LO provides 10% airflow
below nominal unit size selected. Adjust selection options are

provided to adjust airflow supplied to meet individual installation
needs for such things as noise, comfort, and humidity removal.

(See Fig. 17, D as indicated.)

E. ON/OFF DELAY -- Select desired time delay profile

NOTE

: Delay selections are active in cooling and heat pump

heating modes only. Auxiliary heating modes have a 1 minute off
delay and zero on delay programmed into the ECM motor that
cannot be overridden.
Four motor operation delay profiles are provided to customize and

enhance system operation. (See Fig. 17, E as indicated)

Selection options are:

1. The standard 90 sec off delay (Factory setting) at 100% air-

flow.

2. No delay option used for servicing unit or when a thermo-

stat is utilized to perform delay functions.

3. A 30 sec on delay with no airflow/90 sec off delay at 100%

airflow profile is used when it is desirable to allow system

coils time to heat--up/cool--down in conjunction with the
airflow.

4. ENH, enhanced selection, provides a 30 sec on delay with

no airflow/ plus 150 sec at 70% airflow/ no off delay for
added comfort. This profile will minimize cold blow in heat

pump operation and could enhance system efficiency.

F. CONTINUOUS FAN -- Select desired fan speed when ther-

mostat is set on continuous fan

NOTE

: If installed with a 2--speed outdoor unit, do not select HI

speed continuous fan. If HI is selected, low speed compression will
also

run

HI

speed

possibly

resulting

in

insufficient

dehumidification.

1. LO speed -- factory setting, 50% cooling mode airflow.
2. MED speed -- move connector to MED, 80% cooling mode

airflow.

3. HI speed -- move connector of HI, 100% cooling mode air-

flow. (See Fig. 17, F as indicated.)

G. Low--Voltage Circuit Fusing and Reference

The low--voltage circuit is fused by a board--mounted 5--amp
automotive fuse placed in series with the transformer SEC2 and the

R circuit. The C circuit of the transformer is referenced to chassis
ground through a printed circuit run at SEC1 connected to metal

standoff marked with ground symbol.

H. Basic Fan Coil Configuration

The following basic configuration of the fan coil will provide ARI

rated performance of the heat pump:

1. AUX HEAT KW/CFM -- Select the heater range for the

size electric heater installed.

2. AC/HP SIZE -- Select system size installed.
3. SYSTEM TYPE -- Select system type HP--EFF.
4. AC/HP CFM ADJUST -- Select NOM.
5. ON/OFF DELAY -- Select 0/90 profile.
6. CONTINUOUS FAN -- Select desired fan speed when ther-

mostat is set to continuous fan.

I. COMFORT OPTIONS -- WARMER HEATING AND

SUPER DEHUMIDIFY (See Fig. 21 for Quick Reference

Guide)

The FV4C Fan Coil provides better than average humidity control
and heated air temperature. This configuration will improve the

comfort provided by the heat pump system if more humidity

removal or if warmer heating air is desired. While providing this
improved comfort, the heat pump system will operate efficiently,

but not at the published HSPF or ARI SEER efficiency.
The following fan coil configuration is recommended for

maximum heating and cooling/dehumidifying comfort: (See Fig.
17.)

1. AUX HEAT KW/CFM -- Select narrowest heater range to

match size of electric heater installed (skip this step if no

heater is installed).

2. AC/HP SIZE -- Select system size installed.
3. SYSTEM TYPE -- Select system type HP--COMFORT (for

heat pump system) or AC (for air conditioner system).

4. AC/HP CFM ADJUST -- Select LO.
5. ON/OFF DELAY -- Select ENH profile.
6. CONTINUOUS FAN -- Select desired fan speed when ther-

mostat is set to continuous fan.

7. If the fan coil is installed with Intelligent Heat Staging cap-

able electric heaters, remove jumper J2. (See Fig. 17.)

NOTE

: If configuring to run warmer heating, do not remove

jumper J2 when using 5--, 8--, or 10--kW heaters.

8. Remove jumper J1 to activate dehumidify modes.
9. Wire low voltage connections as shown in Fig. 9, 10, 11, or

12.

10. Configure Thermidistat (or capable zoning system) follow-

ing

its

installation

instructions

for

enhanced

dehumidification and SuperComfort/Perfect Heat operation.

This configuration provides the following comfort enhancements:

a. A 30 second blower on delay with 150 seconds at 70% air-

flow to allow the indoor coil to warm up or cool down be-

fore the blower is asked to deliver 100% airflow reducing
the cold blow sensation at start up in heating and allowing
the indoor coil to more quickly reach wet coil operating

conditions in cooling.

b. No blower off delay eliminates cold blow which may be as-

sociated with running the blower after shut down of the
compressor and avoids re--evaporation of condensed mois-
ture after cooling/dehumidifying operation.

c. Lower airflow while the compressor is running to reduce

draft effects and increase heating air temperature and im-

proved humidity control during cooling operation.

FV4

C

 

 

 

Summary of Contents for FV4C

Page 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Page 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Page 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Page 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Page 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Page 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Page 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Page 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Page 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Page 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Page 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Page 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Page 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Page 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Page 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Page 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Page 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Page 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: