background image

14

Before proceeding with module replacement, check the following
to ensure motor winding section is functional. With control module

removed and unplugged from winding section:

1. The resistance between any 2 motor leads should be similar.
2. The resistance between any motor lead and the unpainted

motor end plate should be greater than 100K ohms.

If motor winding section fails one of these tests, it is defective and
must be replaced.

START--UP PROCEDURES

Refer to outdoor unit Installation Instructions for system start--up
instructions and refrigerant charging method details.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible
equipment failure, it is essential that periodic maintenance be

performed on this equipment. The only required maintenance that

may be performed by the consumer is filter maintenance.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect all power to unit before servicing field wires or

removing control package. The disconnect (when used) on

access panel does not disconnect power to the line side of

disconnect, but does allow safe service to all other parts of

unit. If unit does not have a disconnect, disregard the

foregoing. Instead, make sure that a disconnecting means is

within sight from, and is readily accessible from, the unit.

Disconnect all electrical power to unit before performing any

maintenance or service on it.

!

WARNING

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect and clean or replace air filter each month or as re-

quired.

2. Inspect cooling coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean as necessary. An in-

spection port is provided on all A--coil delta plates. Remove
plastic plug to inspect.

3. Inspect blower motor and wheel for cleanliness each heating

and cooling season. Clean as necessary.

4. Inspect electrical connections for tightness and controls for

proper operation each heating and cooling season. Service
as necessary.

Consult Fan Coil Service Manual available from equipment

distributor for maintenance procedures.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

Using the Owner’s/User Manual furnished in outdoor unit, the

installing technician should explain system operation to the
consumer with particular emphasis on indoor fan coil operation

sounds and filter maintenance.

Table 2 – CFM Range for FV4C Units

FAN COIL SIZE

SYSTEM SIZES

CFM RANGE

FV4CNF002

024, 030, 036

350-1275

FV4CN(B,F)003

024, 030, 036, 042

415-1475

FV4CN(B,F)005

036, 042, 048

425-1700

FV4CNB006

042, 048, 060

540-2150

FV4

C

 

 

 

Summary of Contents for FV4C

Page 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Page 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Page 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Page 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Page 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Page 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Page 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Page 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Page 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Page 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Page 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Page 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Page 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Page 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Page 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Page 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Page 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Page 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: