
14
Before proceeding with module replacement, check the following
to ensure motor winding section is functional. With control module
removed and unplugged from winding section:
1. The resistance between any 2 motor leads should be similar.
2. The resistance between any motor lead and the unpainted
motor end plate should be greater than 100K ohms.
If motor winding section fails one of these tests, it is defective and
must be replaced.
START--UP PROCEDURES
Refer to outdoor unit Installation Instructions for system start--up
instructions and refrigerant charging method details.
CARE AND MAINTENANCE
For continuing high performance, and to minimize possible
equipment failure, it is essential that periodic maintenance be
performed on this equipment. The only required maintenance that
may be performed by the consumer is filter maintenance.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect all power to unit before servicing field wires or
removing control package. The disconnect (when used) on
access panel does not disconnect power to the line side of
disconnect, but does allow safe service to all other parts of
unit. If unit does not have a disconnect, disregard the
foregoing. Instead, make sure that a disconnecting means is
within sight from, and is readily accessible from, the unit.
Disconnect all electrical power to unit before performing any
maintenance or service on it.
!
WARNING
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect and clean or replace air filter each month or as re-
quired.
2. Inspect cooling coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean as necessary. An in-
spection port is provided on all A--coil delta plates. Remove
plastic plug to inspect.
3. Inspect blower motor and wheel for cleanliness each heating
and cooling season. Clean as necessary.
4. Inspect electrical connections for tightness and controls for
proper operation each heating and cooling season. Service
as necessary.
Consult Fan Coil Service Manual available from equipment
distributor for maintenance procedures.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.
CAUTION
!
Using the Owner’s/User Manual furnished in outdoor unit, the
installing technician should explain system operation to the
consumer with particular emphasis on indoor fan coil operation
sounds and filter maintenance.
Table 2 – CFM Range for FV4C Units
FAN COIL SIZE
SYSTEM SIZES
CFM RANGE
FV4CNF002
024, 030, 036
350-1275
FV4CN(B,F)003
024, 030, 036, 042
415-1475
FV4CN(B,F)005
036, 042, 048
425-1700
FV4CNB006
042, 048, 060
540-2150
FV4
C