13

the full cooling or cooling plus dehumidify mode requested value.
If circuit R to G is open (0 vac) for super dehumidify mode, the

motor delivers reduced airflow to maximize the humidity removal
of the system while minimizing over--cooling.

E. Electric Heat Heating Mode

S

Thermostat closes circuit R to W/W1, or W2.

S

The fan coil delivers the selected electric heat airflow.

F. Heat Pump Heating Mode -- Single speed

S

Thermostat closes circuits R to G and R to Y/Y2.

S

The fan coil delivers single speed heat pump heating airflow.

G. Heat Pump Heating with Auxiliary Electric Heat

Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with

R to W/W1 or W2 (and R to O in the case of defrost).
In the event that electric heating is called for by the thermostat
while the heat pump is also operating in either heating or defrost

modes, the motor will modify its airflow output, if necessary, to
provide an airflow which is defined as safe for the operation of the

electric heater during heat pump operation. That airflow is the

greater of the heat pump heating airflow and the electric heater
only airflow.

Procedure 11 — TROUBLESHOOTING ECM

MOTOR AND CONTROLS

ELECTRICAL SHOCK HAZARD

Failure to follow this caution may result in personal injury.
High voltage is always present at motor. Disconnect power to

unit before removing or replacing connectors or servicing

motor. Wait at least 5 min after disconnecting power before

opening motor.

CAUTION

!

The ECM motor used with this product contains two parts: the
control module and motor winding section. Do not assume the

motor or module is defective if it will not start. Go through the
steps described below before replacing control module, Easy Select

Board or entire motor. The control module is available as a
replacement part.

A. If motor turns slowly:

1. Replace panel. Motor may appear to run slowly if access

panel is removed.

2. It is normal operation to run noticeably slower if G terminal

is not energized in cooling or heat--pump modes.

B. If motor does not run:

Turn off power and check the following:

1. Check 5 amp fuse on Easy Select Board.
2. Check for 24vac on SEC1 and SEC2. If no voltage is

present, check transformer.

3. Check all plugs and receptacles for any deformation which

could cause loose connections. Be sure plugs are fully
seated.

4. Verify that approximately 230vac is present at motor.
5. Verify low--voltage control signals to motor. The motor re-

ceives its control signals through the 12--pin plug (PL--1) on

Easy Select Board and 16--pin plug on wiring harness. (See
Troubleshooting Example.) The combinations of pins ener-

gized will determine motor speed. (See Fig. 20.) See Table 7
for circuit board, low--voltage screw terminals energized
and for voltage present at each pin on 12--pin plug (PL--1).

See Table 7 for pin number on 16--pin plug which should
have voltage when Easy Select Board screw terminals have

24vac.

C. Use following procedure to check control signals:

THERMOSTAT

1. Remove all thermostat wires from Easy Select Board.
2. Jumper screw terminals (1 at a time): R--G, R--Y/Y2, R--Y1,

R--W1. If motor runs in all cases, thermostat is mis--wired,

configured incorrectly or defective. If motor runs in some
cases, but not others, continue to check wiring harness and

circuit board.

WIRING HARNESS

1. Shut off power to unit; wait 5 min.
2. Remove 5--pin plug from motor.
3. Remove 16--pin from motor.
4. Replace 5--pin plug and turn power on.
5. Check for appropriate voltages on 16--pin connector with

screw terminals jumpered. (See Table 7 for values and see

examples below.)

If signals check correctly and motor does not run, inspect wiring

harness for loose pins or damaged plastic that could cause poor
connections. If connections are good, either control module or

motor is defective. If proper signals are not present, check circuit

board using procedure below:

12--PIN PLUG (PL--1) ON EASY SELECT BOARD

1. Unplug harness from board.
2. Check for appropriate voltages on pins with Easy Select

Board screw terminals jumpered. (See Table 7 for values

and see example below.)

If proper signals are not present, replace Easy Select Board. If

present at board and not at 16--pin connector, wiring harness is
defective.

TROUBLESHOOTING EXAMPLE:

Motor is not running on a call for heat--pump heating. System is a

single--speed heat pump.

1. After performing checks in Thermostat section, follow steps

1 thru 5 in Wiring Harness section. Then proceed with ex-
ample.

2. With all thermostat wires removed from Easy Select Board,

place a jumper wire between R and Y/Y2 low--voltage
screw terminals on the Easy Select board.

3. Check Table 7 for pin number on 16--pin connector associ-

ated with the Y/Y2 signal. The correct pin is #14. The far

right column shows that (--) 12vdc should be present
between pin #14 and pin #1 (common) on the 16--pin con-
nector.

4. Set meter to read DC voltage. Place meter between pins #1

and #14 and check for (--) 12vdc (common side of meter on

pin #1). If signal is present, the problem is in the module or
motor. If signal is not, problem is either in wiring harness or

Easy Select Board.

These steps can be repeated for other modes of operation.
To check Easy Select Board:

1. Leave jumper wire in place between R and Y/Y2.
2. Check Table 7 under “Wiring Harness Connection to Easy

Select Board” column and row for pin #14 to see pin# on
Easy Select Board that should have voltage. The correct pin

is #2. The column on far right will show voltage that should
be present between pin #2 and #9 (or #10 common).

3. Place meter between pins #2 and #9 on Easy Select Board

and check for (--) 12vdc.

4. If voltage is present, the wiring harness is bad; if not, the

Easy Select Board is bad.

D. Verify Motor Winding Section:

FV4

C

 

 

 

Summary of Contents for FV4C

Page 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Page 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Page 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Page 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Page 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Page 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Page 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Page 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Page 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Page 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Page 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Page 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Page 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Page 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Page 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Page 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Page 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Page 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: