background image

12

d. Intelligent Staging of the electric heater elements to more

closely match heating load requirements and provide more

consistent heating air temperatures.

Procedure 9 — ACCESSORY INSTALLATION

A. Accessory Electric Heaters

Electric heaters may be installed with the FV4C Fan Coil per

instructions supplied with electric heater package. See unit rating

plate for factory--approved electric heater kits.

NOTE

: Units installed without electric heat should have a sheet

metal block--off plate covering the heater opening. This reduces air
leakage and formation of exterior condensation.

B. Auxiliary Terminals

The AUX and HUM terminals on the Easy Select Board are tied
directly to the G terminal, and provide a 24--vac signal whenever

the G terminal is energized. (See Fig. 17 and 18.) During Super
Dehumidify and SuperComfort / Perfect Heat modes, the G signal

is not present and the auxiliary terminals are not energized. If the

installation includes the use of these operating modes, do not use
these terminals to control accessories. See Electronic Air Cleaner

and Humidifier sections for further information.

C. Electronic Air Cleaner Connections

The AUX1 and AUX2 terminals are not always energized during
blower operation, as described above. When using an electronic air

cleaner with the FV4C Fan Coil, use Airflow Sensor Part No.
KEAAC0101AAA. The airflow sensor turns on electronic air

cleaner when the fan coil blower is operating.

D. Humidifier/Humidistat Connections

Easy Select Board terminals HUM1 and HUM2 are provided for

direct connection to the low--voltage control of a humidifier
through a standard humidistat. (See Fig. 19.) These terminals are

energized with 24vac when G thermostat signal is present. (See
Fig. 20.) Alternately, the 24--vac signal may be sourced from the W

and C terminal block connections when electric heaters are used as

primary heating source. When using a Thermidistat

t

Control,

Zone Perfect Plus or Comfort Zone II, the 24--vac signal may be

sourced directly from the Thermidistat HUM terminal. (See Fig. 9,
10, 11, and 12.)

HUMIDISTAT

TO HUMIDIFIER

HUMIDIFIER WIRING

HUM 1

(C)

HUM 2

(G)

24-VAC

A95317

Fig. 19 -- Humidifier Wiring

E. Dehumidify Capability with Standard Humidistat Connec-

tion

Latent capacities for systems using the FV4C Fan Coil are better

than average systems. If increased latent capacity is an application
requirement, the field wiring terminal block provides connection

terminals for use of a standard humidistat. The FV4C Fan Coil will
detect the humidistat contacts opening on increasing humidity and

reduce its airflow to approximately 80% of nominal cooling mode

airflow. This reduction will increase the system latent capacity until
the humidity falls to a level which causes the humidistat to close its

contacts. When the contacts close, the airflow will return to 100%
of the selected cooling airflow. To activate this mode, remove

Jumper J1 and wire in a standard humidistat. (See Fig. 20.)

EASY SELECT

BOARD TERMINAL

BLOCK

D

H

J1

R

HUMIDISTAT

REMOVE

JUMPER

A95316

Fig. 20 -- Humidistat Wiring for De--Humidify Mode

F. Dehumidify and Super Dehumidify Capabilities

This model fan coil is capable of responding to a signal from
indoor system control (Thermidistat, zoning control) to operate in

comfort control modes such as Super Dehumidify Mode. Consult

literature provided with indoor system control to determine if these
operating modes are available, and to see control set up

instructions. No special setup or wiring of fan coil is required.

Procedure 10 — FV4C FAN COIL SEQUENCE

OF OPERATION

The FV4C will supply airflow in a range which is more than twice

the range of a standard fan coil. It is designed to provide nominal

cooling capacities at a 50

_

F (10

_

C) evaporator temperature and the

required airflow which enables it to match with 4 air conditioner or

heat pump system sizes. Table 2 outlines the CFM range for the
different FV4C Fan Coil sizes.

A. Continuous Fan

S

Thermostat closes circuit R to G.

S

The blower runs at continuous fan airflow.

B. Cooling Mode -- Single speed

S

If indoor temperature is above temperature set point and
humidity is below humidity set point, thermostat closes circuits
R to G, R to Y/Y2 and R to O.

S

The fan coil delivers single speed cooling airflow.

C. Cooling Mode -- Dehumidification

S

If indoor temperature is above temperature set point and
humidity is above humidity set point, thermostat or
Thermidistat

t

closes circuits R to G, R to O, and R to Y/Y2,

and humidistat or Thermidistat opens R to DH.

S

The fan coil delivers airflow which is approximately 80% of the
nominal cooling airflow to increase the latent capacity of the
system.

D. Cooling Mode -- Super Dehumidify Operation (See Fig. 22

for Quick Reference Guide)

NOTE

: The indoor control used, such as Thermidistat, must be

capable of providing Super Dehumidify operation mode and
control must be configured as outlined in its installation
instructions. Consult indoor control literature to determine if
control is capable of providing Super Dehumidify inputs and for
configuration instructions.
If the indoor temperature is below the temperature set point and the
humidity is above the humidity set point, the Thermidistat closes

circuit R to O, opens circuits R to DH and R to G, and cycles
circuit R to Y/Y2 (for single speed system R to Y1, or R to Y1 and

Y/Y2 for 2--speed system).
The ECM motor reads the G signal to the fan coil while the heat

pump is operating, (circuit R to Y/Y2 for single speed system, R to

Y1 or R to Y1 and Y/Y2 for 2--speed system), closed (24 vac). If
circuit R to G is closed (24 vac), the motor will deliver airflow at

FV4

C

 

 

 

Summary of Contents for FV4C

Page 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Page 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Page 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Page 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Page 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Page 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Page 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Page 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Page 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Page 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Page 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Page 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Page 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Page 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Page 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Page 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Page 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Page 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: