MANUAL DE INSTALAÇÃO, OPERAÇÃO E MANUTENÇÃO / MANUAL DE INSTALACIÓN,
OPERACIÓN Y MANTENIMIENTO / INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Carrier
To avoid unnecessary servicing check the
following items carefully:
* Is the equipment properly connected to the
main network, with all the manual and/or
2 or 3-way Valve Kits
12
Initial Start Up
13
TABLE 01 - APPLICATION AND OPERATION LIMIT CONDITIONS
Before starting up the unit, check the above
conditions and the following items:
* Check the correct fixation of all the
electrical connections;
* Assure a perfect draining and no
obstructions in the drain hose.
Situation
Maximum Accepted Value
Procedure
1) Voltage
+/- 10% variation concerning
Check your installation and/or contact
the rated value
you local electricity supplier.
2) Net imbalance
Voltage: 2%
Check your installation and/or contact
you local electricity supplier.
3) Water temperature
Max.: 77°C
4) Room temperature
Min.: 18
O
C Máx.: 30
O
C
Maintenance
14
14.1
General
automatic trip/ circuit protection devices turned on,
without breaks as: burnt fuses, open switches, etc.?
* Is the thermostat properly calibrated for the
desired conditions?
* Is the fan switch/circuit breaker in the
correct position?
Btu/h
TR
9.000
0,75
1/2" 2-way On/Off valve
46101621
12.000
1,00
1/2" 2-way On/Off valve
46101621
18.000
1,50
1/2" 2-way On/Off valve
46101621
24.000
2,00
1/2" 2-way On/Off valve
46101621
30.000
2,50
1/2" 2-way On/Off valve
46101621
36.000
3,00
1/2" 2-way On/Off valve
46101621
44.000
3,70
3/4" 2-way On/Off valve
46101622
55.000
4,60
3/4" 2-way On/Off valve
46101622
Capacity
Fins (Chilled w ater) / Fins (Hot water)
Model
Code
Btu/h
TR
9.000
0,75
1/2" 3-way On/Off valve
46101623
12.000
1,00
1/2" 3-way On/Off valve
46101623
18.000
1,50
1/2" 3-way On/Off valve
46101623
24.000
2,00
1/2" 3-way On/Off valve
46101623
30.000
2,50
1/2" 3-way On/Off valve
46101623
36.000
3,00
1/2" 3-way On/Off valve
46101623
44.000
3,70
3/4" 3-way On/Off valve
46101624
55.000
4,60
3/4" 3-way On/Off valve
46101624
Fins (Chilled w ater) / Fins (Hot water)
Capacity
Model
Code
Before performing any maintenance, turn off
the equipment power supply.
The unit fan motors are factory lubricated. Do
not lubricate when installing the units. Before
starting up, check if the fan propeller or
turbines are not loose.
The table below defines application and operation limit conditions of the units.
These kits only have the 2 or 3-way valve control .