Table 2 -- Menu Structure

a

(cont)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and Increment

b

Notes

SYSTEM

SETUP

(cont)

FACTORY DEFAULT

NO

NO or YES

Resets all set points to factory defaults when set to YES. LCD will briefly

flash YES and change to NO but all parameters will change to the

factory default values.

ADVANCED

SETUP

MA LO SET

45

_

F

35 to 55

_

F;

Incremented by 1

_

Temperature to achieve Freeze Protection (close damper and alarm if

temperature falls below setup value)

FREEZE POS

CLO

CLO or MIN

Damper position when freeze protection is active (closed or MIN POS).

CO2 ZERO

0ppm

0 to 500 ppm:

Increment by 10

CO

2

ppm level to match CO

2

Sensor start level.

CO2 SPAN

2000ppm

1000 to 3000 ppm;

Increment by 50

CO

2

ppm span to match CO

2

sensor.

STG3 DLY

2.0h

0 min, 5 min, 15 min, then

15 min intervals. Up to 4 h

or OFF

Delay after stage 2 for cool has been active. Turns on 2

nd

stage of

cooling when economizer is 1

st

stage and mechanical cooling is 2

nd

stage. Allows three stages of cooling, 1 economizer and 2 mechanical.

OFF = no Stage 3 cooling.

SD DMPR POS

CLO

CLO or OPN

Indicates shutdown signal from space thermostat or unitary controller.

When controller receives 24 Vac input on the SD terminal in conventional

mode, the OA damper will open if programmed for OPN and OA damper

will close if programmed for CLO. All other controls, e.g., fans, etc. will

shut off.

DCVCAL ENA

MAN

MAN (manual)

AUTO

Turns on the DCV automatic control of the dampers. Resets ventilation

based on the RA, OA and MA sensor conditions. Requires all 3 RA, OA

and MA sensors.

MAT T CAL

0.0

_

F

+/---2.5

_

F

Allows for the operator to adjust for an out of calibration temperature

sensor

OA T CAL

0.0

_

F

+/---2.5

_

F

Allows for the operator to adjust for an out of calibration temperature

sensor

OA H CAL

0% RH

+/---10% RH

Allows for the operator to adjust for an out of calibration humidity sensor

RA T CAL

0.0

_

F

+/---2.5

_

F

Allows for the operator to adjust for an out of calibration temperature

sensor

RA H CAL

0% RH

+/---10% RH

Allows for the operator to adjust for an out of calibration humidity sensor

DA T CAL

0.0

_

F

+/---2.5

_

F

Allows for the operator to adjust for an out of calibration temperature

sensor

CHECKOUT

DAMPER VMIN---HS

n/a

n/a

Positions damper to VMIN position

DAMPER VMAX---HS

n/a

n/a

Positions damper to VMAX position

DAMPER OPEN

n/a

n/a

Positions damper to the full open position.

Exhaust fan contacts enable during the DAMPER OPEN test. Make sure

you pause in this mode to allow exhaust contacts to energize due to the

delay in the system.

DAMPER CLOSE

n/a

n/a

Positions damper to the fully closed position

CONNECT Y1---O

n/a

n/a

Closes the Y1---O relay (Y1---O)

CONNECT Y2---O

n/a

n/a

Closes the Y2---O relay (Y2---O)

CONNECT AUX

n/a

n/a

Energizes the AUX output. If Aux setting is:

S

NONE --- not action taken

S

ERV --- 24 Vac out. Turns on or signals an ERV that the

conditions are not good for economizing but are good for

ERV operation.

d

S

SYS --- 24 Vac out. Issues a system alarm

ALARMS(_)

MA T SENS ERR

n/a

n/a

Alarms display only when they are active. The menu title “ALARMS(_)”

includes the number of active alarms in parenthesis ( ).

CO2 SENS ERR

n/a

n/a

OA T SENS ERR

n/a

n/a

DA ENTHL ERR

n/a

n/a

SYS ALARM

n/a

n/a

When AUX is set to SYS and there is any alarm (e.g., failed sensors,

etc.), the AUX terminal has 24 Vac out.

NOTE

: The alarms listed are examples. Additional alarms display depending on the parameter settings and configuration.

For example if you do not have a DCV (CO

2

) sensor, then none of the DCV parameters appear.

a

Table 2 illustrates the complete hierarchy. your menu parameters may be different depending on your configuration.

For example if you do not have a DCV (CO

2

) sensor, then none of the DCV parameters appear.

b

When values are displayed, pressing and holding the

Y

or

B

button causes the display to automatically increment.

c

n/a = not applicable

d

ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing --- the ERV terminal will be energized.

In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.

LLECO

N

--

01

S

I

Summary of Contents for EconoMiser X

Page 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Page 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Page 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Page 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Page 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Page 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Page 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Page 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Page 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Page 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Page 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Page 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...