background image

11

TROUBLESHOOTING

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any

power loss or interruption, as all settings are stored in the

Economizer controller’s non--volatile flash memory.

NOTE

: If the power goes below 18 Vac, the W7220

controller module assumes a power loss and the 5 minute
power up delay will become functional when power
returns above 18 Vac.

Alarms

The Economizer module provides alarm messages that

display on the 2--line LCD.

NOTE

:

Upon power up, the module waits several

seconds before checking for alarms. This allows time for
all the configured devices (e.g. sensors, actuator) to
become operational.
If one or more alarms are present and there has been no

keypad activity for at least 5 minutes, the Alarms menu

displays and cycles through the active alarms.

You can also navigate to the Alarms menus at any time.

See Table 2 on page 6 for the Alarms menu.

Clearing Alarms

Once the alarm has been identified and the cause has been

removed (e.g. replaced faulty sensor). the alarm can be

cleared from the display.

To clear an alarm, perform the following:

1. Navigate to the desired alarm.
2. Press the

button.

3. ERASE? displays.
4. Press the

button.

5. ALARM ERASED displays.
6. Press the

(Menu up/Exit) button to complete the

action and return to the previous menu.

NOTE

: If the alarm still exists after you clear it, it is

redisplayed within 5 seconds.

Table 9 – Operating Issues and Concerns

Issue or Concern

Possible Cause and Remedy

My outdoor temperature reading on the

STATUS menu is not accurate.

Check the sensor wiring:

• Enthalpy sensors are to be wired to the S---Bus terminals.

• Temperature sensors are to be wired to the OAT and MAT terminals.

If my enthalpy sensor drifts in accuracy

over time, can I re---calibrate it?

The sensor are not able to be re---calibrated in the field. However there is a menu item under the ADVANCED menu

where you are able to input a limited offset in temperature and humidity for each sensor you have connected to the

economizer.

Can I go back to factory defaults and start

over?

Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults.

Will I be able to see the LCD screen when it

is in the unit?

The LCD screen has a backlight that is always illuminated.

What is a good setpoint for the Mixed Air

Temperature (MAT)?

The mixed air temperature is the temperature of air that you want to supply to the space. In a commercial building, this

is between 50 to 55

_

F (10 to 13

_

C). The mixed air is the mixing of the return air and the outdoor air.

I am using enthalpy sensors. Why did the

control ask me to input a dry bulb

changeover temperature?

In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in the control is to default to the

temperature sensor in the enthalpy sensor.

In checkout, the outdoor damper closes

when i command it to open.

Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper should drive open or closed with

the return air damper having the opposite effect.

How do I set my minimum position?

The minimum position is set using the VENTMIN and VENTMAX setup in the SETPOINTS menu. VENTMIN is the

minimum ventilation required when using an occupancy sensor and VENTMAX is the minimum ventilation when not

using an occupancy sensor for Demand Control Ventilation. The VENTMAX position is set the same as with the

potentiometer on the analog economizers and is the output voltage to the damper actuator. The range is 2 Vdc closed

OA damper and 10 Vdc open OA damper.

What if my damper does not go completely

closed in the checkout operation?

Check the damper linkage or hub to make sure the damper is able to close completely.

How do I set the OCC?

There are two setting for the OCC setting, INPUT and ALWAYS. INPUT is from the space thermostat, if it has an

occupancy output. ALWAYS is the unit in the occupied mode, if the economizer is powered (fan on).

Does the economizer save my program

values if the unit loses power?

Yes, once the changes are stored in the controller they will be stored until they are changed by the operator.

If the unit is left in checkout, how long will

the unit stay in checkout mode without

input?

The unit will remain in checkout for 10 minutes, then return to normal operation.

LLECO

N

--

01

S

I

Summary of Contents for EconoMiser X

Page 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Page 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Page 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Page 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Page 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Page 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Page 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Page 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Page 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Page 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Page 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Page 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...

Reviews: