Checkout Tests

Use the Checkout menu (see Table 2 on page 6) to test

the damper operation and any configured outputs. Only

items that are configured are shown in the Checkout

menu.

NOTE

: See User Interface on page 3 for information

about menu navigation and use of the keypad.
To perform a Checkout test:

1. Scroll to the desired test in the Checkout menu using

the the

and

buttons.

2. Press the

button to select the item.

3. RUN? appears.
4. Press the

button to start the test.

5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press

the

(Menu up) button to end the test.

Checkout tests can be performed at ay time during the

operation of the system as a test that the system is operable.

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
Be sure to allow enough time for compressor startup

and shutdown between checkout tests so that you do

not short--cycle the compressors.

CAUTION

!

SETUP AND CONFIGURATION

W7220 Economizer Module Wiring

Use Fig. 3 and Tables 3 and 4 to locate the wiring

terminals for the Economizer module.

NOTE

: The four terminal blocks are removable. You can

slide out each terminal block, wire it, and then slide it back
into place.

W7220 Controller

Left Terminal

Block Label

Right Terminal

Block Label

C12014

Fig. 3 -- W7220 Economizer Module Terminal

Connection Labels

Table 3 – Economizer Module --

Left Hand Terminal Blocks

Label

Type

Description

Top Left Terminal Block

MAT

MAT

20k NTC

and

COM

Mixed Air Temperature Sensor

(polarity insensitive connection)

OAT

OAT

20k NTC

and

COM

Outdoor Air Temperature Sensor

(polarity insensitive connection)

S---BUS

S---BUS

S---Bus

(Sylk Bus)

Enthalpy Control Sensor

(polarity insensitive connection)

Bottom Left Terminal Block

IAQ 2---10

2---10 Vdc

Air Quality Sensor Input

(e.g. CO

2

sensor)

IAQ COM

COM

Air Quality Sensor Common

IAQ 24V

24 Vac

Air Quality Sensor 24 Vac Source

ACT 2---10

2---10 Vdc

Damper Actuator Output (2---10 Vdc)

ACT COM

COM

Damper Actuator Output Common

ACT 24V

24 Vac

Damper Actuator 24 Vac Source

Table 4 – Economizer Module --

Right Hand Terminal Blocks

Label

Type

Description

Top Right Terminal Block

n/a

The first terminal is not used

AUX2 I

24 Vac IN

Shut Down (SD) or Heat (W)

Conventional only

or

Heat Pump Changeover (O?B) in

Heat Pump mode.

OCC

24 Vac IN

Occupied / Unoccupied Input

E---GND

E---GND

Earth Ground --- System Required

EXH1

24 Vac OUT Exhaust Fan 1 Output

AUX1 O

24 Vac OUT Programmable:

Exhaust fan 2 output

or

Erv

or

System Alarm output

Bottom Right Terminal Block

Y2---I

24 Vac IN

Y2 in --- Cooling Stage 2 Input from

space thermostat

Y2---O

24 Vac OUT Y2 out --- Cooling Stage 2 Output to

stage 2 mechanical cooling

Y1---I

24 Vac IN

Y1 in --- Cooling Stage 2 Input from

space thermostat

Y1---O

24 Vac OUT Y1 out --- Cooling Stage 2 Output to

stage 2 mechanical cooling

C

COM

24 Vac Common

R

24 Vac

24 Vac Power (Hot)

Time--out and Screen Saver

When no buttons have been pressed for 10 minutes, the

LCD displays a screen saver, which cycles through the

Status items. Each Status item displays in turn and cycles

to the next item after 5 seconds.

LLECO

N

--

01

S

I

Summary of Contents for EconoMiser X

Page 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Page 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Page 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Page 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Page 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Page 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Page 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Page 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Page 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Page 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Page 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Page 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...

Reviews: