Carrier EconoMiser X Installation, Setup And Troubleshooting Manual Download Page 3

3

EconoMi$er X

EconoMi$er X is a low leak economizer system which is

available for 2--stage cooling units equipped with the SAV

2--speed Variable Frequency Drive (VFD) system.

The factory--installed option consist of the following:

S

Low leak economizer assembly

S

W7220 economizer controller

S

20K dry bulb temperature control sensor

S

Enthalpy control sensor (enthalpy economizer only)

W7220 Economizer Controller

The economizer controller used on electro mechanical units

is a Honeywell W7220 which is located in the RTU base

unit’s Control Box. See the Installation Instructions for your

base unit for the location of the Control Box access panel.

The W7220 controller provide the following:

S

2--line LCD interface screen for setup, configuration
and troubleshooting.

S

On--board fault detection and diagnostics

S

Sensor failure loss of communications identification

S

Automatic sensor detection

S

Capabilites for use with multiple--speed indoor fan
systems

User Interface

The user interface consists of an LCD display and a

4--button keypad on the front of the economizer controller.

2 LINE

LCD

MENU UP

(EXIT)

BUTTON

SCROLL

UP/DOWN

BUTTONS

SELECT

(ENTER)
BUTTON

C11548

Fig. 2 -- W7220 Controller

Keypad

The four navigation buttons (see Fig. 2) are used to scroll

through the menus and menu items, select menu items,

and to change parameter and configuration settings.

Using the Keypad with Menus

To use the keypad when working with menus:

S

Press the

(Up arrow) button to move to the previous

menu.

S

Press the

(Down arrow) button to move to the next

menu.

S

Press the

(Enter) button to display the first item in

the currently displayed menu.

S

Press the

(Menu Up/Exit) button to exit a menu’s

item and return to the list of menus.

Using the Keypad with Settings and Parameters

To use the keypad when working with Setpoints, System

and Advanced Settings, Checkout tests and Alarms:

1. Navigate to the desired menu.
2. Press the

(Enter) button to display the first item in

the currently displayed menu.

3. Use the

and

buttons to scroll to the desired

parameter.

4. Press the

(Enter) button to display the value of the

currently displayed item.

5. Press the

button to increase (change) the displayed

parameter value.

6. Press the

button to decrease (change) the displayed

parameter value.

NOTE

: When values are displayed, pressing and

holding the

or

button causes the

display to automatically increment.

7. Press the

(Enter) button to accept the displayed

value and store it in nonvolatile RAM.

8. “CHANGE STORED” displays.
9. Press the

(Enter) button to return to the current

menu parameter.

10. Press the

(Menu Up/Exit) button to return to the

previous menu.

Menu Structure

Table 2 illustrates the complete hierarchy of menus and

parameters for the Economizer X system.

The Menus in display order are:

S

STATUS

S

SETPOINTS

S

SYSTEM SETUP

S

ADVANCED SETUP

S

CHECKOUT

S

ALARMS

LLECO

N

--

01

S

I

Summary of Contents for EconoMiser X

Page 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Page 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Page 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Page 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Page 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Page 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Page 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Page 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Page 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Page 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Page 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Page 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...