background image

5

Step 4 — Final Wiring

                 UTILITY I/O BOARD WIRING

Bring all Utility I/O board wires together at Utility I/O
board. Make all connections as indicated in Fig. 7.
Figures 9 through 18 show the connection between the
Utility I/O board and the HVac equipment. Select proper
diagram for your equipment and connect accordingly. This
connection will require as few as 4 or as many as 7 conduc-
tors.

It is good practice to mark each wire as the final
connection is made. This will preserve its identity if it is
ever disconnected.

NOTE: Wiring diagrams appear near the end of this
document.

                  WIRING CONSIDERATIONS

ComfortChoice treats all furnaces as if they were 2-stage.
For single stage equipment, connect to W. The same holds
true for auxiliary heat in fan coils. With any 2-stage furnace,
configure the furnace so that low heat is controlled by W
and high heat is controlled by W and W2 together.
All 2-stage air conditioners and heat pumps need to be
configured so that Y controls low speed and Y and Y2
together control high speed in both heating and cooling.

                               

POWER WIRING

The thermostat is powered by 24 Vac only. The
thermostat requires the 24 Vac (Rh and/or Rc and C
terminals) of the low-voltage transformer to be connected
to it for proper operation. The thermostat will not operate
without these connections. The Rh and Rc terminals are
connected via the PCB breakout jumper. For applications
using a single 24 Vac transformer for power, the breakout
jumper should remain intact. For applications using two 24
Vac transformers, the breakout jumper must be broken
because possible voltage differences between the two
transformers could cause irregular operation or damage to
the thermostat. See Figure 8. For applications using two 24
Vac transformers, one in the indoor unit and one in the
outdoor unit, connect the common wire from each to the C
terminal. Connect R from the indoor unit to the Rh terminal.
Connect R from the outdoor unit to the Rc terminal. Break
the jumper on the circuit board. See Figure 8. The W and
HUM signals are taken from the Rh power and the G signal
is taken from the Rc power. If the control has been installed
in a two-transformer application that is later changed to a
single-transformer installation, the installer must install a
field-supplied jumper between Rc and Rh. Depending on
the installation, up to 14 wires may be required. Installation
as two-piece unit is recommended. Only 2 wires are required
for connection between display module and equipment
control module. These two wires (V+ and Vg) do not
provide ordinary 24 Vac. They carry a combination of
power and communications data that is unique to these
products.

Step 5 — Understanding Sequence of Operations

                 TEMPERATURE SET POINTS

The ComfortChoice System uses 2 temperature set points,
the higher for cooling and the lower for heating. A minimum
difference of 2

°

F is normally enforced between heating and

cooling set points, although this value may be adjusted by
the installer. Each set point may be manually adjusted or
controlled by a programmed time schedule established by
the home owner.

The ComfortChoice thermostat can also be configured for
Heat Only or Cool Only operation. In these modes a single
set point is used to control a furnace (Heat Only) or an air
conditioner (Cool Only).

 HEATING AND COOLING COMFORT SET POINTS

If space temperature is between heating and cooling set
points, then it is said to be “satisfied” with respect to
temperatures. When a space is satisfied, no heating or
cooling is required. When the space is satisfied, there is no
demand and the equipment is turned off. For example, if
cooling set point is 76°F and heating set point is 72°F,
then a space temperature of 73°F is assumed to be satisfac-
tory and no heating or cooling of the space is required.
If space temperature falls below heating set point, then that
space needs to have heat added which will raise space
temperature back to heating set point. For example, if
heating set point is 72°F and space temperature is 70°F,
then space temperature must be raised 2°F in order for the
space to be satisfied. In this case, temperature “heating
demand” for zone is 2°F (72° minus 70°F). Otherwise, if
temperature in a space rises above cooling set point, then
that space needs to have heat removed which will lower
space temperature back to cooling set point. For example, if
cooling set point is 76°F and space temperature is 77°F,
space temperature must be lowered 1°F in order for space to
be satisfied. In this case, cooling demand for space is 1°
(77°minus 76°F).

Step 6 — System Configuration
Make sure this step is not left out
.
The ComfortChoice thermostat must be configured to
match the type of equipment connected to it. There are
several choices of configuration based on how the user
wants the system to operate. Configuration is done by
setting the equipment type and other options in the
thermostat on power up. Configuration options enable the
installer to configure the thermostat for a particular
installation. Most options are not presented to the home-
owner and therefore must be properly set by the installer.
Turn on power to the thermostat.

Fig. 8 - System Wiring

Summary of Contents for ComfortChoice EDGE

Page 1: ...EMPERATURE SET POINTS 5 HEATING AND COOLING COMFORT SET POINTS 5 Step 6 System Configuration 5 CONFIGURATION 6 To Enter and Exit Configuration Mode 6 While in Configuration Mode 6 Configuration Options Option 1 Equipment Type 6 Option 2 Replace Filter Reminder 6 Option 4 Fan G On With W W1 Selection 6 Option 6 Cooling Lockout 7 Option 8 Auxiliary Heat Lockout Temperature 7 Option 11 Adjustable Set...

Page 2: ...This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measure ...

Page 3: ...ent not supplied by Carrier to facilitate utility auxiliary curtailment or optionally control a residential device remotely through combined wireless internet capabil ity Device is wired to the Utility I O board INSTALLATION CONSIDERATIONS These instructions cover the physical installation and start up of the ComfortChoice system 1 Install thermostat in non condensing areas with ambients between 3...

Page 4: ...ape any unneeded conductors Plan the routing of wiring early to avoid possible problems later on Remember all wires converge at the Utility I O board so its location is important Step 3 Install Components INSTALL UTILITY I O BOARD The Utility I O board is designed so that wires can enter it from behind above or below Plan wire routing before mounting Utility I O Board 1 Remove cover to access moun...

Page 5: ... mounting if needed Make sure all wires extend through hole in mounting base 7 Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1 4 in extra wire 8 Connect two wires from the equipment control module to the display module mounting base being careful not to over tighten the screws Correct polarity must be observed when connecting the two wire...

Page 6: ...e and equipment control module These two wires V and Vg do not provide ordinary 24 Vac They carry a combination of power and communications data that is unique to these products Step 5 Understanding Sequence of Operations TEMPERATURE SET POINTS The ComfortChoice System uses 2 temperature set points the higher for cooling and the lower for heating A minimum difference of 2 F is normally enforced be...

Page 7: ...on options Each option is described below Configuration Options OPTION 01 EQUIPMENT TYPE Determines the control method of the thermostat It should match the type of equipment used Equipment Types are as follows H2 Two speed Heat Pump with a fan coil HP Single speed Heat Pump with a fan coil A2 Two speed AC with a furnace AC Single speed AC with a furnacel H Heat only system Furnace or fan coil onl...

Page 8: ...ammed period that recovery starts Recovery takes place smoothly during the selected recovery time ending at the recovery time and temperature which is programmed Allowable selections are OF off 30 60 and 90 The default is 90 OPTION 13 ROOM AIR TEMPERATURE OFFSET ADJUSTMENT OFFSET Selects the number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the me...

Page 9: ...within the set point limits of OPTION 26 and OPTION 27 and time of day and the calendar The occupied button is functional When set to 2 the user has access to change the set points only The occupied button is functional When set to 3 the entire keypad is locked When a button is pressed the backlight will turn on but none of the operating parameters will be changed When the keypad lock selection is...

Page 10: ...n the triangle icon next to HOLD This will maintain set points not allowing them to change with programmed schedule Use the FAN button to select between AUTO fan on only with equipment and On fan on continuously fan modes OPERATIONAL INFORMATION Five minute Compressor Timeguard This timer prevents the compressor from starting unless it has been off for at least 5 minutes It can be defeated for 1 c...

Page 11: ...he communication network In the event of loss of network communication you can manually set the time and date by following the instructions below To set the clock Press and release the SET button until clock is displayed in the left center of the display along with the time at the bottom center of the screen Use the softkeys to move the box around the digits to be set and use the UP or DOWN button...

Page 12: ...ary programming mode is active the display will show the icon AUXILIARY and the current program period wake day eve sleep will be displayed in place of the room temperature display 3 Press and release the soft key below the days of the week until the weekday icons Mo Tu Wed Thur Fri are displayed 4 Press and release the soft key below the period wake day eve sleep until the wake period is displaye...

Page 13: ...chedule settings and user settings will be factory default values Replace the thermostat I O Board Error Codes Error codes for the I O board are indicated by the flash rate of the on board LED The slow flash rate is the first digit and the fast flash rate is the second During normal operation the flash rate of the LED will be 1 second on 1 second off 23 Flash Memory Error Replace the I O Board 25 ...

Page 14: ...13 Table 5 Temperature Ohm Relationship ...

Page 15: ...ioner Figure 12 1 Stage Furnace with 2 Stage Air Conditioner Figure 13 2 Stage Furnace with 1 Stage Air Conditioner Figure 14 Typical fan Coil with 1 Stage Air Conditioner Figure 10 1 Stage Furnace Figure 11 1 Stage Furnace with 1 Stage Air Conditioner ...

Page 16: ...15 Figure 16 Typical Fan Coil with 2 Stage Air Conditioner Figure 17 Typical Fan Coil with 2 Stage Heat Pump with Reversing Value Active in Cooling Figure 15 2 Stage Furnace with 2 Stage Air Conditioner ...

Page 17: ...16 Figure 18 Typical Fan Coil with 1 Stage Heat Pump with Reversing Valve Active in Cooling ...

Reviews: