Error Codes

“--” — Thermistor failure
Temperature sensing element in the thermostat cannot
properly read room temperature. All outputs (except fan,
if set to on) will turn off. The thermostat must be re-
placed. In the case where the installer has selected to
average the local sensor and the remote sensor, the
display will alternate between “--” for the failed sensor
and the temperature sensed by the working sensor every
10 seconds. The thermostatl will operate from the
temperature sensed by the working sensor.
E1 — The thermostat and the I/O board cannot communi-
cate via two-wire connection.
E4 — Internal memory failure. When this error is present
and power is cycled to the thermostat all of the installer
configurations, program schedule settings and user
settings will be factory default values.  Replace the
thermostat.

I/O Board  Error Codes —
Error codes for the  I/O board are indicated by the flash rate
of the on board LED. The slow flash rate is the first digit,
and the fast flash rate is the second. During normal
operation the flash rate of the LED will be 1 second on, 1
second off.

23—Flash Memory Error. Replace the  I/O Board.
25—EEProm (Memory) Error. Replace the  I/O board.
27—RAM Memory Error. Replace the I/O Board.
32—Device out of range. Check antenna connection.
34—No communications with thermostat. Check connec-
tions between the I/O board and the thermostat.
36—No communications with the Radio. Check cable
connection between the thermostat radio and the  I/O
board.

Table 4 - Auxiliary Device Program Schedule

M

A

R

G

O

R

P

D

O

I

R

E

P

E

M

I

T

X

U

A

Y

A

L

E

R

e

k

a

W

M

A

0

0

:

4

n

O

y

a

D

M

A

0

0

:

9

f

f

O

e

v

E

M

P

0

0

:

3

n

O

p

e

e

l

S

M

P

0

0

:

1

1

n

O

Summary of Contents for ComfortChoice EDGE

Page 1: ...EMPERATURE SET POINTS 5 HEATING AND COOLING COMFORT SET POINTS 5 Step 6 System Configuration 5 CONFIGURATION 6 To Enter and Exit Configuration Mode 6 While in Configuration Mode 6 Configuration Options Option 1 Equipment Type 6 Option 2 Replace Filter Reminder 6 Option 4 Fan G On With W W1 Selection 6 Option 6 Cooling Lockout 7 Option 8 Auxiliary Heat Lockout Temperature 7 Option 11 Adjustable Set...

Page 2: ...This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measure ...

Page 3: ...ent not supplied by Carrier to facilitate utility auxiliary curtailment or optionally control a residential device remotely through combined wireless internet capabil ity Device is wired to the Utility I O board INSTALLATION CONSIDERATIONS These instructions cover the physical installation and start up of the ComfortChoice system 1 Install thermostat in non condensing areas with ambients between 3...

Page 4: ...ape any unneeded conductors Plan the routing of wiring early to avoid possible problems later on Remember all wires converge at the Utility I O board so its location is important Step 3 Install Components INSTALL UTILITY I O BOARD The Utility I O board is designed so that wires can enter it from behind above or below Plan wire routing before mounting Utility I O Board 1 Remove cover to access moun...

Page 5: ... mounting if needed Make sure all wires extend through hole in mounting base 7 Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1 4 in extra wire 8 Connect two wires from the equipment control module to the display module mounting base being careful not to over tighten the screws Correct polarity must be observed when connecting the two wire...

Page 6: ...e and equipment control module These two wires V and Vg do not provide ordinary 24 Vac They carry a combination of power and communications data that is unique to these products Step 5 Understanding Sequence of Operations TEMPERATURE SET POINTS The ComfortChoice System uses 2 temperature set points the higher for cooling and the lower for heating A minimum difference of 2 F is normally enforced be...

Page 7: ...on options Each option is described below Configuration Options OPTION 01 EQUIPMENT TYPE Determines the control method of the thermostat It should match the type of equipment used Equipment Types are as follows H2 Two speed Heat Pump with a fan coil HP Single speed Heat Pump with a fan coil A2 Two speed AC with a furnace AC Single speed AC with a furnacel H Heat only system Furnace or fan coil onl...

Page 8: ...ammed period that recovery starts Recovery takes place smoothly during the selected recovery time ending at the recovery time and temperature which is programmed Allowable selections are OF off 30 60 and 90 The default is 90 OPTION 13 ROOM AIR TEMPERATURE OFFSET ADJUSTMENT OFFSET Selects the number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the me...

Page 9: ...within the set point limits of OPTION 26 and OPTION 27 and time of day and the calendar The occupied button is functional When set to 2 the user has access to change the set points only The occupied button is functional When set to 3 the entire keypad is locked When a button is pressed the backlight will turn on but none of the operating parameters will be changed When the keypad lock selection is...

Page 10: ...n the triangle icon next to HOLD This will maintain set points not allowing them to change with programmed schedule Use the FAN button to select between AUTO fan on only with equipment and On fan on continuously fan modes OPERATIONAL INFORMATION Five minute Compressor Timeguard This timer prevents the compressor from starting unless it has been off for at least 5 minutes It can be defeated for 1 c...

Page 11: ...he communication network In the event of loss of network communication you can manually set the time and date by following the instructions below To set the clock Press and release the SET button until clock is displayed in the left center of the display along with the time at the bottom center of the screen Use the softkeys to move the box around the digits to be set and use the UP or DOWN button...

Page 12: ...ary programming mode is active the display will show the icon AUXILIARY and the current program period wake day eve sleep will be displayed in place of the room temperature display 3 Press and release the soft key below the days of the week until the weekday icons Mo Tu Wed Thur Fri are displayed 4 Press and release the soft key below the period wake day eve sleep until the wake period is displaye...

Page 13: ...chedule settings and user settings will be factory default values Replace the thermostat I O Board Error Codes Error codes for the I O board are indicated by the flash rate of the on board LED The slow flash rate is the first digit and the fast flash rate is the second During normal operation the flash rate of the LED will be 1 second on 1 second off 23 Flash Memory Error Replace the I O Board 25 ...

Page 14: ...13 Table 5 Temperature Ohm Relationship ...

Page 15: ...ioner Figure 12 1 Stage Furnace with 2 Stage Air Conditioner Figure 13 2 Stage Furnace with 1 Stage Air Conditioner Figure 14 Typical fan Coil with 1 Stage Air Conditioner Figure 10 1 Stage Furnace Figure 11 1 Stage Furnace with 1 Stage Air Conditioner ...

Page 16: ...15 Figure 16 Typical Fan Coil with 2 Stage Air Conditioner Figure 17 Typical Fan Coil with 2 Stage Heat Pump with Reversing Value Active in Cooling Figure 15 2 Stage Furnace with 2 Stage Air Conditioner ...

Page 17: ...16 Figure 18 Typical Fan Coil with 1 Stage Heat Pump with Reversing Valve Active in Cooling ...

Reviews: