background image

50VL-C, 50VL-F: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

30

If low cooling performance is suspected, leak-test all refrigerant tubing

using an electronic leak-detector or liquid-soap solution. If a refrigerant

leak is detected, refer to the Check for Refrigerant Leaks section. 
If  no  refrigerant  leaks  are  found  and  low  cooling  performance  is

suspected,  refer  to  the  Checking  and  Adjusting  Refrigerant  Charge

section. 

Evaporator Airflow 

The  heating  and/or  cooling  air-flow  does  not  require  checking  unless

improper performance is suspected. If a problem exists, be sure that all

supply- and return-air grilles are open and free from obstructions, and

that the air filter is clean. When necessary, refer to Indoor Airflow and

Airflow Adjustments section to check the system airflow. 

Puron (R-410A) Items 

The  indoor  metering  device  is  either  a  TXV  or  orifice  type  device

depending on size. 

Pressure Switches 

Pressure switches  are  protective  devices  wired  into  the  control  circuit

(low  voltage).  They  shut  off  compressor  if  abnormally  high  or  low

pressures are present in the refrigeration circuit. These pressure switches

are specifically designed to operate with Puron (R-410A) systems. R-22

pressure  switches  must  not  be  used  as  replacements  for  the  Puron

(R-410A) air conditioner. 

Low Pressure Switch (24 and 30 size only) 

This  switch  is  located  on  the  suction  line  and  protects  against  low

suction pressures caused by such events as loss of charge, low airflow

across  indoor  coil, dirty filters, etc.  It opens at  50

 psig   (957 Pa). If

system pressure is above this, switch should be closed. 
To check switch: 

1. Turn off all power to unit.
2. Disconnect leads on switch. 
3. Apply ohmmeter leads across switch. You should have continuity

on a closed switch. 

NOTE: 

  Because  these  switches  are  attached  to  refrigeration  system

under  pressure,  it  is  not  advisable  to  remove  this  device  for

troubleshooting unless you are reasonably certain that a problem exists.

If switch must be removed, remove and recover all system charge so that

pressure gauges read 0 psi (0 Pa). Never open system without breaking

vacuum with dry nitrogen. 

High-Pressure Switch 

The  high-pressure switch  is  located  in  the  discharge  line  and  protects

against  excessive  condenser  coil  pressure.  It  opens  at  650  psig  (31.1

kPa). High pressure may be caused by a dirty condenser coil, failed fan

motor, or condenser air recirculation. 
To check switch: 

1. Turn off all power to unit. 
2. Disconnect leads on switch. 
3. Apply ohmmeter leads across switch. You should have continuity

on a good switch. 

Compressor (Puron (R-410A) Refrigerant) 

The compressor used in this product is specifically designed to operate

with Puron (R-410A) refrigerant and cannot be interchanged. 
The compressor is an electrical (as well as mechanical) device. Exercise

extreme caution when working near compressors. Power should be shut

off,  if  possible,  for  most  troubleshooting  techniques.  Refrigerants

present additional safety hazards. 

For  models  that  have  a  scroll  compressor,  the  compressor  pumps

refrigerant throughout the system by the interaction of a stationary and

an  orbiting  scroll.  The  scroll  compressor  has  no  dynamic  suction  or

discharge  valves,  and  it  is  more  tolerant  of  stresses  caused  by  debris,

liquid slugging, and flooded starts. The compressor is equipped with a

noise reducing shutdown device and an internal pressure relief port.  The

pressure  relief  port  is  a  safety  device,  designed  to  protect  against

extreme high pressure. The relief port has an operating range between

550 (26.3 kPa) and 625 (29.9 kPa) psig differential pressure.

Refrigerant 

This system uses Puron (R-410A) refrigerant which has higher operating

pressures than R-22 and other refrigerants. No other refrigerant may be

used  in  this  system.  Gage  set,  hoses,  and  recovery  system  must  be

designed  to  handle  Puron  (R-410A).  If  you  are  unsure,  consult  the

equipment  manufacturer.  Failure  to  use  Puron  (R-410A)  compatible

servicing equipment or replacement components may result in property

damage or injury. 

Compressor Oil 

The Copeland scroll compressor uses 3MAF POE oil. If additional oil is

needed,  use  Uniqema  RL32-3MAF.  If  this  oil  is  not  available,  use

Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely

hygroscopic, meaning it absorbs water readily. POE oils can absorb 15

times  as  much  water  as  other  oils  designed  for  HCFC  and  CFC

refrigerants. Take all necessary precautions to avoid exposure of the oil

to the atmosphere.

Rotary Compressor

The 24 and 30 size units use a single cylinder rotary compressor. This

compressor utilizes a rotor which is positioned eccentrically with respect

to  the  shell.  Refrigerant  gas  is  ported  directly  into  the  compression

chamber and discharged into the surrounding area. It is also known as a

“high-side”  design  since  high  pressure  gas  surrounds  the  motor  and

compression chamber. The majority of the shell will be hot to the touch.

The rotary compressor also utilizes an external built-in accumulator to

reduce the likelihood of refrigerant liquid from entering the compressor.

WARNING

!

EXPLOSION, SAFETY AND ENVIRONMENTAL 

HAZARD

Failure to follow this warning could result in personal injury, death or

equipment damage.

This  system  uses  Puron  (R-410A)  refrigerant  which  has  higher

operating  pressures  than  R-22  and  other  refrigerants.  No  other

refrigerant may be used in this system. Gauge set, hoses, and recovery

system must be designed to handle Puron (R-410A). If you are unsure,

consult the equipment manufacturer.

WARNING

!

FIRE/EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death

and/or property damage.

Wear  safety  glasses  and  gloves  when  handling  refrigerants.  Keep

torches and other ignition sources away from refrigerants and oils.

WARNING

!

EXPLOSION, ENVIRONMENTAL  HAZARD

Failure to follow this warning could result in personal injury, death or

equipment damage.

This  system  uses  Puron  (R-410A)  refrigerant  which  has  higher

operating  pressures  than  R-22  and  other  refrigerants.  No  other

refrigerant may be used in this system. Gauge set, hoses, and recovery

system must be designed to handle Puron (R-410A). If you are unsure,

consult the equipment manufacturer.

Summary of Contents for Comfort 50VL-F

Page 1: ...refer to the current editions of the Canadian electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manual...

Page 2: ...s and PE Professional Engineering Certificate if required Roof Curb Install accessory roof curb in accordance with instructions shipped with curb See Fig 4 Install insulation cant strips roofing and f...

Page 3: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 3 A200004 Fig 2 24 36 Unit Dimensions...

Page 4: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A150533 Fig 3 42 60 Unit Dimensions...

Page 5: ...1 lb density Fig 4 Roof Curb Dimensions UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm Part Number CPRCURB011B00 can be used on both small and large basepan units The cr...

Page 6: ...des Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to c...

Page 7: ...When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap D...

Page 8: ...nances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for side shot installation 2 Select and size ductwork supply air registers and return a...

Page 9: ...they do not interfere with operation of unit If an accessory electric heater is installed low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 con...

Page 10: ...7 3 17 4 7 3 17 4 7 3 17 5 6 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279...

Page 11: ...rs start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires IMPORTANT Three phase scroll compr...

Page 12: ...lor coding on the indoor fan motor leads see Table 3 The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box near the interface fan board IFB See Fig 11 S...

Page 13: ...Y and G These completed circuits through the thermostat connect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 V secondary of transformer TRAN The nor...

Page 14: ...d Low Pink CFM 1174 1107 1045 985 914 890 825 760 673 572 BHP 0 32 0 32 0 33 0 33 0 34 0 35 0 36 0 37 0 37 0 37 Medium1 Red CFM 1246 1195 1148 1081 1019 953 884 859 795 690 BHP 0 38 0 39 0 39 0 40 0 4...

Page 15: ...ation speed Table 5 Dry Coil Air Delivery Horizontal Discharge Sizes 36 60 3 Phase Models Only Unit Motor Speed Wire Color External Static Pressure IN W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 36 Low Bl...

Page 16: ...20 0 21 Med Low Pink CFM 1002 936 875 821 748 687 613 554 565 518 WATTS 144 155 161 171 176 187 193 203 209 220 BHP 0 15 0 17 0 17 0 18 0 19 0 20 0 21 0 22 0 22 0 24 Medium Red CFM 1255 1210 1145 1074...

Page 17: ...Black CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808 WATTS 1029 1012 995 975 941 908 869 836 796 751 BHP 1 10 1 09 1 07 1 05 1 01 0 97 0 93 0 90 0 85 0 81 Shaded areas indicate speed static co...

Page 18: ...Table IN W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 10 kW 0 00 0 00 0 00...

Page 19: ...nstallation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A150503 Fig 12 Connection Wiring Diagram 24 36 60 Si...

Page 20: ...Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A150513 Fig 13 Ladder Wiring Diagram 24 36 60 Size...

Page 21: ...F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 21 A200013 Fig 14 Connection Wiring Diagram 30 Size...

Page 22: ...L F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 22 A200014 Fig 15 Ladder Wiring Diagram 30 Size 20...

Page 23: ...0VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A150504 Fig 16 Connection Wiring Diagram 208...

Page 24: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 24 A150514 Fig 17 Ladder Wiring Diagram 208 23...

Page 25: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 25 A150505 Fig 18 Connection Wiring Diagram 46...

Page 26: ...C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 26 A150515 Fig 19 Ladder Wiring Diagram 460...

Page 27: ...bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or...

Page 28: ...ation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscrew s that secures wheel to motor shaft remove s...

Page 29: ...pose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs to be removed loosen the setscrew and slide the fan off the motor shaft 5 When replacing fan blade position blade as show...

Page 30: ...ditional safety hazards For models that have a scroll compressor the compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor...

Page 31: ...rough the louvered openings in the unit base 4 Perform required service 5 Remove and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The filter drier is specifically...

Page 32: ...rigerant evacuate system and recharge to capacities shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil De...

Page 33: ...ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN H...

Page 34: ...dianapolis IN 46231 Edition Date 01 20 Catalog No 50VL 17SI Replaces 50VL 16SI 50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs...

Reviews: