background image

50VL-C, 50VL-F: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

13

interface  board  (IFB).    Verify  that  static  pressure  is  in  the

acceptable range for the speed tap to be used for dehumidification

cooling.

7. Use any spare vinyl plugs to cap any unused speed tap wires.

A09059

Fig. 11 – Interface Fan Board (IFB)

Single Speed Cooling with Higher Electric Heat Speed

This unit can also be configured to operate with single speed cooling and

a higher speed for an accessory electric heater.

1. Using 

Fig. 11

, move the two pin DEHUM jumper from the “STD”

position to the “DEHUM” position.

2. See 

Table 2

 for minimum airflow for electric heat operation. Add

electric heater and filter pressure drop to duct system static pressure

to determine total external static pressure.

3. Select  speed  tap  from 

Table 5

  that  will  achieve  required  airflow

from 

Table 2

.

4. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding).

5. Connect the desired speed tap wire to the “HIGH” terminal on the

interface fan board (IFB).

– 

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed will be

the same as cooling fan speed. When the DEHUM feature is used, the

continuous fan will operate on IFB “LOW” speed when the DH control

lead  is  not  energized,  or  IFB  “HIGH”  speed  when  the  DH  lead  is

energized (see 

Fig. 11

).

Cooling Sequence of Operation

With the room thermostat SYSTEM switch in the COOL position and

the FAN switch in the AUTO position, the cooling sequence of operation

is as follows:
When the  room temperature  rises  to a point  that  is slightly above the

cooling control setting of the thermostat, the thermostat completes the

circuit  between  thermostat  terminal  R  to  terminals  Y  and  G.  These

completed  circuits  through  the  thermostat  connect  contactor  coil  (C)

(through unit wire Y) and time delay relay (TDR) (through unit wire G)

across the 24-V secondary of transformer (TRAN).
The  normally  open  contacts  of  energized  contactor  (C)  close  and

complete the  circuit through  compressor  motor (COMP)  to  condenser

(outdoor) fan motor (OFM). Both motors start instantly.
A  set  of  normally  open  contacts  on  the  interface  fan  board  (IFB)  are

closed which energizes a circuit to the indoor fan motor (IFB).

NOTE: 

 Once the compressor has started and then has stopped, it should

not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to a point

that is slightly below the cooling control setting of the room thermostat.

At  this  point,  the  thermostat  breaks  the  circuit  between  thermostat

terminal  R  to  terminals  Y  and  G.  These  open  circuits  deenergize

contactor coil C and IFB. The condenser and compressor motors stop.

After a 90-second delay, the blower motor stops. The unit is in a standby

condition, waiting for the next call for cooling from the room thermostat.

CAUTION

!

 UNIT OPERATION HAZARD

Failure to follow this caution may result in unit component damage or

improper operation.
To use this  mode, a speed connection must be made  on the “HIGH”

terminal that meets or exceeds the minimum airflow found in 

Table 2

.

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med-High Speed

Red = Med Speed

Pink = Med-Low Speed

Blue = Low Speed

HIGH

LOW

COM

QC5

QC4

QC3

KZ

KL

07

09

08

0L0

ALO

R13 C8

R11

Q1

Q3

D2

AL2

DCR

QCR

QC1

C

RL

01

G1

G2

Z1

A7

R9

AB A15

C4

C9

C0

QIL

Z2

06

04

U1

C3

R4

RL4

JWZ

C7

D5

D3

R3 R5

R6

R2

JW5

QCB

Y

R

W2 Y

C

W3 W3 W2 W2 C

JW4

P2

JW3

P4

P1

W2

W3

Y2

Y1

Y

DH

G

C

R

SSTZ-8

P3

SDL

24V

AC/R

3AMP

CDM/C

F1

STD

DEHUM

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before

changing blower speed.

Summary of Contents for Comfort 50VL-F

Page 1: ...refer to the current editions of the Canadian electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manual...

Page 2: ...s and PE Professional Engineering Certificate if required Roof Curb Install accessory roof curb in accordance with instructions shipped with curb See Fig 4 Install insulation cant strips roofing and f...

Page 3: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 3 A200004 Fig 2 24 36 Unit Dimensions...

Page 4: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A150533 Fig 3 42 60 Unit Dimensions...

Page 5: ...1 lb density Fig 4 Roof Curb Dimensions UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm Part Number CPRCURB011B00 can be used on both small and large basepan units The cr...

Page 6: ...des Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to c...

Page 7: ...When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap D...

Page 8: ...nances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for side shot installation 2 Select and size ductwork supply air registers and return a...

Page 9: ...they do not interfere with operation of unit If an accessory electric heater is installed low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 con...

Page 10: ...7 3 17 4 7 3 17 4 7 3 17 5 6 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279...

Page 11: ...rs start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires IMPORTANT Three phase scroll compr...

Page 12: ...lor coding on the indoor fan motor leads see Table 3 The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box near the interface fan board IFB See Fig 11 S...

Page 13: ...Y and G These completed circuits through the thermostat connect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 V secondary of transformer TRAN The nor...

Page 14: ...d Low Pink CFM 1174 1107 1045 985 914 890 825 760 673 572 BHP 0 32 0 32 0 33 0 33 0 34 0 35 0 36 0 37 0 37 0 37 Medium1 Red CFM 1246 1195 1148 1081 1019 953 884 859 795 690 BHP 0 38 0 39 0 39 0 40 0 4...

Page 15: ...ation speed Table 5 Dry Coil Air Delivery Horizontal Discharge Sizes 36 60 3 Phase Models Only Unit Motor Speed Wire Color External Static Pressure IN W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 36 Low Bl...

Page 16: ...20 0 21 Med Low Pink CFM 1002 936 875 821 748 687 613 554 565 518 WATTS 144 155 161 171 176 187 193 203 209 220 BHP 0 15 0 17 0 17 0 18 0 19 0 20 0 21 0 22 0 22 0 24 Medium Red CFM 1255 1210 1145 1074...

Page 17: ...Black CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808 WATTS 1029 1012 995 975 941 908 869 836 796 751 BHP 1 10 1 09 1 07 1 05 1 01 0 97 0 93 0 90 0 85 0 81 Shaded areas indicate speed static co...

Page 18: ...Table IN W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 10 kW 0 00 0 00 0 00...

Page 19: ...nstallation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A150503 Fig 12 Connection Wiring Diagram 24 36 60 Si...

Page 20: ...Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A150513 Fig 13 Ladder Wiring Diagram 24 36 60 Size...

Page 21: ...F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 21 A200013 Fig 14 Connection Wiring Diagram 30 Size...

Page 22: ...L F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 22 A200014 Fig 15 Ladder Wiring Diagram 30 Size 20...

Page 23: ...0VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A150504 Fig 16 Connection Wiring Diagram 208...

Page 24: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 24 A150514 Fig 17 Ladder Wiring Diagram 208 23...

Page 25: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 25 A150505 Fig 18 Connection Wiring Diagram 46...

Page 26: ...C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 26 A150515 Fig 19 Ladder Wiring Diagram 460...

Page 27: ...bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or...

Page 28: ...ation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscrew s that secures wheel to motor shaft remove s...

Page 29: ...pose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs to be removed loosen the setscrew and slide the fan off the motor shaft 5 When replacing fan blade position blade as show...

Page 30: ...ditional safety hazards For models that have a scroll compressor the compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor...

Page 31: ...rough the louvered openings in the unit base 4 Perform required service 5 Remove and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The filter drier is specifically...

Page 32: ...rigerant evacuate system and recharge to capacities shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil De...

Page 33: ...ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN H...

Page 34: ...dianapolis IN 46231 Edition Date 01 20 Catalog No 50VL 17SI Replaces 50VL 16SI 50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs...

Reviews: