background image

50VL-C, 50VL-F: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

Introduction

This  packaged  air  conditioner  is fully  self-contained and  designed  for

outdoor  installation  (See 

Fig. 1

).  See 

Fig. 2

  and 

Fig. 3

  for  unit

dimensions. All unit sizes have discharge openings for both horizontal

and downflow configurations, and are factory shipped with all downflow

duct openings covered. The unit may be installed either on a rooftop or

on a ground-level cement slab. (See 

Fig. 4

 for roof curb dimensions.)

Receiving and Installation

Step 1 – Check Equipment

Identify Unit

The  unit  model  number  and  serial  number  are  printed  on  the  unit

informative plate. Check this information against shipping papers.

Inspect Shipment

Inspect  for  shipping  damage  before  removing  packaging  materials.  If

unit appears to be damaged or is torn loose from its anchorage, have it

examined  by  transportation  inspectors  before  removal.  Forward  claim

papers  directly  to  transportation  company.  Manufacturer  is  not

responsible for any damage incurred in transit. Check all items against

shipping  list.  Immediately  notify  the  nearest  equipment  distribution

office if any item is missing. To prevent loss or damage, leave all parts in

original packages until installation.
If the unit is to be mounted on a curb in a downflow application, review

Step 7 to determine which method is to be used to remove the downflow

panels before rigging and lifting into place. The panel removal process

may require the unit to be on the ground.

Step 2 – Provide Unit Support

IMPORTANT: 

The  unit  must  be  secured  to  the  curb  by  installing

screws through the bottom of the curb flange and into the unit base rails.

When installing large base units onto the common curb, the screws must

be installed before allowing the full weight of the unit to rest on the curb.

A minimum of six screws are required for large base units. Failure to

secure unit properly could result in an unstable unit. See Warning near

Rigging/Lifting  information  and  accessory  curb  instructions  for  more

details.
For  hurricane  tie  downs,  contact  distributor  for  details  and  PE

(Professional Engineering) Certificate if required.

Roof Curb

Install accessory roof curb in accordance with instructions shipped with

curb  (See 

Fig. 4

).  Install  insulation,  cant  strips,  roofing,  and  flashing.

Ductwork must be attached to curb.

IMPORTANT: 

 The gasketing of the unit to the roof curb is critical for a

water tight seal. Install gasketing material supplied with the roof curb.

Improperly applied gasketing also can result in air leaks and poor unit

performance.
Curb should be level to within 1/4 in. (6.35 mm) (See 

Fig. 4

). This is

necessary  for  unit  drain  to  function  properly.  Refer  to  accessory  roof

curb installation instructions for additional information as required.
Installation on older “G” series roof curbs.
Two accessory kits are available to aid in installing a new “G” series unit

on an old “G” roof curb.

1. Accessory  kit  number  CPADCURB001A00,  (small  chassis)  and

accessory kit number CPADCURB002A00, (large chassis) includes

roof  curb  adapter  and  gaskets  for  the  perimeter  seal  and  duct

openings.  No  additional  modifications  to  the  curb  are  required

when using this kit.

2. An alternative to the adapter curb is to modify the existing curb by

removing the outer horizontal flange and use accessory kit number

CPGSKTKIT001A00  which  includes  spacer  blocks  (for  easy

alignment to existing curb) and gaskets for the perimeter seal and

duct openings. This kit is used when existing curb is modified by

removing outer horizontal flange.

Slab Mount

Place the unit on a solid, level pad that is at least 2 in. (51 mm) above

grade. The pad should extend approximately 2 in. (51 mm) beyond the

casing on all 4 sides of the unit (See 

Fig. 7

). Do not secure the unit to the

pad except when required by local codes.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.

When removing access panels (see 

Fig. 22

) or performing maintenance

functions  inside  your  unit,  be  aware  of  sharp  sheet  metal  parts  and

screws.  Although  special  care  is  taken  to  reduce  sharp  edges  to  a

minimum, be extremely careful and wear appropriate clothing, safety

glasses and gloves when handling parts or reaching into the unit.

CAUTION

!

UNIT/STRUCTURAL DAMAGE HAZARD

Failure to follow this caution may result in property damage.

Ensure there is sufficient clearance for saw blade when cutting the outer

horizontal flange of the roof curb so there is no damage to the roof or

flashing.

Summary of Contents for Comfort 50VL-F

Page 1: ...refer to the current editions of the Canadian electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manual...

Page 2: ...s and PE Professional Engineering Certificate if required Roof Curb Install accessory roof curb in accordance with instructions shipped with curb See Fig 4 Install insulation cant strips roofing and f...

Page 3: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 3 A200004 Fig 2 24 36 Unit Dimensions...

Page 4: ...50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A150533 Fig 3 42 60 Unit Dimensions...

Page 5: ...1 lb density Fig 4 Roof Curb Dimensions UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm Part Number CPRCURB011B00 can be used on both small and large basepan units The cr...

Page 6: ...des Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to c...

Page 7: ...When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap D...

Page 8: ...nances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for side shot installation 2 Select and size ductwork supply air registers and return a...

Page 9: ...they do not interfere with operation of unit If an accessory electric heater is installed low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 con...

Page 10: ...7 3 17 4 7 3 17 4 7 3 17 5 6 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279...

Page 11: ...rs start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires IMPORTANT Three phase scroll compr...

Page 12: ...lor coding on the indoor fan motor leads see Table 3 The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box near the interface fan board IFB See Fig 11 S...

Page 13: ...Y and G These completed circuits through the thermostat connect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 V secondary of transformer TRAN The nor...

Page 14: ...d Low Pink CFM 1174 1107 1045 985 914 890 825 760 673 572 BHP 0 32 0 32 0 33 0 33 0 34 0 35 0 36 0 37 0 37 0 37 Medium1 Red CFM 1246 1195 1148 1081 1019 953 884 859 795 690 BHP 0 38 0 39 0 39 0 40 0 4...

Page 15: ...ation speed Table 5 Dry Coil Air Delivery Horizontal Discharge Sizes 36 60 3 Phase Models Only Unit Motor Speed Wire Color External Static Pressure IN W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 36 Low Bl...

Page 16: ...20 0 21 Med Low Pink CFM 1002 936 875 821 748 687 613 554 565 518 WATTS 144 155 161 171 176 187 193 203 209 220 BHP 0 15 0 17 0 17 0 18 0 19 0 20 0 21 0 22 0 22 0 24 Medium Red CFM 1255 1210 1145 1074...

Page 17: ...Black CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808 WATTS 1029 1012 995 975 941 908 869 836 796 751 BHP 1 10 1 09 1 07 1 05 1 01 0 97 0 93 0 90 0 85 0 81 Shaded areas indicate speed static co...

Page 18: ...Table IN W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 10 kW 0 00 0 00 0 00...

Page 19: ...nstallation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A150503 Fig 12 Connection Wiring Diagram 24 36 60 Si...

Page 20: ...Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A150513 Fig 13 Ladder Wiring Diagram 24 36 60 Size...

Page 21: ...F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 21 A200013 Fig 14 Connection Wiring Diagram 30 Size...

Page 22: ...L F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 22 A200014 Fig 15 Ladder Wiring Diagram 30 Size 20...

Page 23: ...0VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A150504 Fig 16 Connection Wiring Diagram 208...

Page 24: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 24 A150514 Fig 17 Ladder Wiring Diagram 208 23...

Page 25: ...50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 25 A150505 Fig 18 Connection Wiring Diagram 46...

Page 26: ...C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 26 A150515 Fig 19 Ladder Wiring Diagram 460...

Page 27: ...bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or...

Page 28: ...ation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscrew s that secures wheel to motor shaft remove s...

Page 29: ...pose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs to be removed loosen the setscrew and slide the fan off the motor shaft 5 When replacing fan blade position blade as show...

Page 30: ...ditional safety hazards For models that have a scroll compressor the compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor...

Page 31: ...rough the louvered openings in the unit base 4 Perform required service 5 Remove and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The filter drier is specifically...

Page 32: ...rigerant evacuate system and recharge to capacities shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil De...

Page 33: ...ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN H...

Page 34: ...dianapolis IN 46231 Edition Date 01 20 Catalog No 50VL 17SI Replaces 50VL 16SI 50VL C 50VL F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs...

Reviews: