background image

CNPHP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

HORIZONTAL CRAWL SPACE INSTALLATION

As an alternate to horizontal attic installation, the CNPHP horizontal coil

can be installed in a crawl space by mounting on suitable blocks, pads or

by hanging from floor joists.
To suspend CNPHP:

1. Cut metal plumbers strap to desired lengths.
2. Attach metal plumbers strap to four corners of coil casing (

Fig. 7

).

3. Use a minimum of two screws per corner to attach metal plumbers

strap to casing.

4. Position and secure coil in front of furnace discharge end.
5. Make sure coil is level for proper condensate drainage.
6. Using appropriate fasteners from duct type, connect supply-air duct

to coil.

A05421

Fig. 7 – Suspension with Plumbers Strap

REFRIGERANT LINE CONNECTIONS

NOTE: 

Factory nitrogen  charge may escape past rubber plugs  during

storage. This does not indicate a leaking coil nor warrant return of the

coil.
Refrigerant  lines must be configured per local  building codes  and  the

guidelines outlined in the OD units installation instructions.
Size and install refrigerant lines according to information provided with

outdoor  unit.  Coil  connection  tube  sizes  are  shown  in 

Table 3

.  Route

refrigerant  lines  to  the  coil  in  a  manner  that  will  not  obstruct  service

access to the unit or removal of the filter.

NOTE: 

The filter dryer should be placed just before the indoor unit.

Connect Refrigerant Liquid and Suction Lines

For matched and mismatched systems, use line sizes recommended in

outdoor unit Installation Instructions.
The coil can be connected to outdoor units using accessory refrigerant

line sets or field-supplied lines of refrigerant grade. 
See 

Table 3

 for coil connection tube size.

The coil can be connected to outdoor units using field-supplied tubing of

refrigerant grade. Always evacuate tubing and reclaim refrigerant when

making  connections  or  flaring  tubing.  Leak  check  connections  before

insulating entire suction line.
See 

Table 3

 for coil connection tube size.

1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from coil stubs

using a pulling and twisting motion. Hold coil stubs steady to avoid

bending or distorting.

3. Remove  tubing  plate  with  rubber  grommets  and  slide  plate  with

grommets  onto  the  refrigerant  lines  (field  line-set),  away  from

braze joints.

4. Fit  refrigerant  lines  into coil  stubs. Wrap  a  heat  sinking  material

such as a wet cloth behind braze joints.

5. Wrap TXV and nearby tubing with a heat-sinking material such as a

wet cloth. 

6. Use 1/2 psig Nitrogen purge in the suction and out the liquid line.
7. Braze using a Sil-Fos or Phos-copper alloy. Do not use soft solder.

WARNING

!

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury.

Wear eye protection.

Coil is factory charged with 15 psi nitrogen. The coil is under pressure

and TXV screen is in place behind liquid line plug. DO NOT remove

liquid  line  plug  first;  always  remove  the  suction  line  plug  first  to

depressurize the coil.

2 Screws for
  Attachment 
     to Casing

Plumbers
       Strap

Table 3 – Coil Connection Tube Size

MODEL NUMBER 

COIL CONNECTION TUBE SIZE

in (mm)

Liquid

Suction

CNPHP2417ALA

3/8 (10)

5/8 (16)

CNPHP3017ALA

3/8 (10)

3/4 (19)

CNPHP3617ALA

3/8 (10)

3/4 (19)

CNPHP4221ALA

3/8 (10)

7/8 (22)

CNPHP4321ALA

3/8 (10)

7/8 (22)

CNPHP4821ALA

3/8 (10)

7/8 (22)

CNPHP6024ALA

3/8 (10)

7/8 (22)

CNPHP6124ALA

3/8 (10)

7/8 (22)

CAUTION

!

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
Take  precautions  to  ensure  aluminum  tubes  do  not  come  in  direct

contact  or  allow  for  condensate  run-off  with  a  dissimilar  metal.

Dissimilar metals can cause galvanic corrosion and possible premature

failure.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product damage.
To avoid valve damage to the refrigerant control device while brazing,

valves  must  be  wrapped  with  a  heat-sinking  material  such  as  a  wet

cloth.

Summary of Contents for CNPHP

Page 1: ...ult in enhanced installation reliability or operation NOTE Nitrogen can leak out through the needle pierce hole in the plugs This does not indicate a leaking coil nor warrant return of the coil INTRODUCTION The CNPHP is a horizontal multi use furnace coil Fig 1 With the use of field supplied transition duct these furnace coils can also be applied to other similar horizontal furnaces on the market ...

Page 2: ...V designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE All TXV S have preset superheat settings and are not field adjustable Cabinet Sweating If the unit is installed in a garage attic or other unconditioned space special attention may need to be given to the potential of cabinet sweating Condensate Management With proper installation these coils will ...

Page 3: ...stall and orientate the components as shown in Fig 4 Use Table 1 and Table 2 to identify which Application Letters A through J are acceptable for the furnace width and coil width being used in a specific situation Orientate and configure the furnace and coil as shown in each application A180215A Fig 4 Horizontal Installation Applications HORIZONTAL RIGHT INSTALLATIONS Acceptable for Air Conditione...

Page 4: ... Fig 5 A05419 Fig 5 Mount Attachment Plates 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace Fig 6 5 Seal joint between coil casing and furnace to create air tight seal using locally approved materials A05420 Fig 6 Attach Coil to Furnace NOTE If the coil and furnace are different widths refer to Fig 4 and Table 1 Table 2 HORIZONTAL ATTIC INSTALLATION Constru...

Page 5: ...acuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line See Table 3 for coil connection tube size 1 Remove cabinet access door 2 Remove rubber plugs suction plug then liquid plug from coil stubs using a pulling and twisting motion Hold coil stubs steady to avoid bending or distorting 3 Remove tubing plate with rub...

Page 6: ...pan should be drained to a noticeable place As an alternative to using an external condensate pan some localities may allow the running of a separate 3 4 in 19 mm condensate line with appropriate trap per local code to a place where the condensate will be noticeable The owner of the structure must be informed that when condensate flows from secondary drain or external condensate pan the unit requi...

Reviews: