background image

 © 2021 Carrier. All rights reserved.

A Carrier Company 

Edition Date: 12/21

Catalog No: IM-CNPH-13

Replaces: IM-CNPH-12

CNPHP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

8. After  brazing,  allow  joints  to  cool.  Carefully  remove  TXV  bulb

insulation and verify that the TXV bulb is securely fastened with

hose  clamp. Tighten  screw  a  half-turn  past hand  tight  with TXV

bulb placed in the indentation with full contact with the vapor line

tube. Re-wrap TXV bulb with insulation. 

9. Leak check connections before insulating entire suction line.
10. Slide  tubing  plate  with  rubber  grommets  over  joints.  Position

tubing at center of each grommet to ensure an air seal around the

tube. Reinstall cabinet door.

CONDENSATE DRAIN LINE CONNECTION

The coil  is designed  to dispose  of accumulated  water through built-in

condensate drain fittings. It is recommended that PVC fittings be used

on  the condensate pan. Do  not  over-tighten. Finger  tighten plus 1-1/2

turns. Be sure to install plastic plug in unused condensate drain fitting.

Two 3/4-in. female threaded pipe connections are provided in each coil

condensate pan.
A trap is not necessary on the condensate line. Consult local codes for

additional restrictions or precautions. If local codes require a trap then

the following guidelines are suggested to assure proper drainage. Install

a trap in condensate line of coil as close to the coil as possible. Make trap

at  least  3  in.  (76  mm)  deep  and  no  higher  than  the  bottom  of  unit

condensate drain opening (

Fig. 8

). Pitch condensate line 1 in. (25.4 mm)

for every 10 ft. of length to an open drain or sump. Make sure that the

outlet of each trap is below its connection to condensate pan to prevent

condensate  from  overflowing  the  drain  pan.  Prime  all  traps,  test  for

leaks, and insulate traps and lines if located above a living area.

A08067

Fig. 8 – Condensate Trap

NOTE: 

If unit is located in or above a living space, where damage may

result  from  condensate  overflow,  a  field-supplied,  external  condensate

pan  should  be  installed  underneath  the  entire  unit,  and  a  secondary

condensate line (with appropriate trap) should be run from the unit into

the  pan.  Any  condensate  in  this  external  condensate  pan  should  be

drained  to  a  noticeable  place. As  an  alternative  to  using  an  external

condensate  pan,  some  localities  may  allow  the  running  of  a  separate

3/4-in. (19 mm) condensate line (with appropriate trap) per local code to

a  place  where  the  condensate  will  be  noticeable.  The  owner  of  the

structure must be informed that when condensate flows from secondary

drain  or  external  condensate  pan,  the  unit  requires  servicing  or  water

damage  will  occur. To  further  protect  against  water  damage,  install  a

float switch to shut the unit off if the water in the secondary pan gets too

high.

NOTE: 

To  avoid  drainage  problems,  test  the  primary  drain  line  by

slowly pouring water  into the pan. Check  piping  for  leaks and proper

condensate  drainage.  Using  the  secondary  drain  as  explained  in  the

previous  note  provides  further  protection  against  overflow  due  to  a

clogged primary drain.

NOTE: 

In applications where return air humidity levels stay at 70% or

above  for  a  prolonged  period  of  time,  condensation  can  form  on  the

bottom of pan and drip.

WASTE LINE CONNECTION

If the condensate line is to be connected to a waste (sewer) line, an open

trap must be installed ahead of the waste line to prevent escape of sewer

gases (

Fig. 9

).

A10216

Fig. 9 – Condensate Drain to Waste Line

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment failure,

it is essential that periodic maintenance be performed on this equipment.

Consult your local dealer as to the proper frequency of maintenance, but

it should be done at least annually.
The ability to properly perform maintenance on this equipment requires

certain mechanical skills and tools. If you do not possess these, contact

your dealer for maintenance. The only consumer service recommended

or required is filter replacement or cleaning on a monthly basis.

CAUTION

!

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When  installing  over  a  finished  ceiling  and/or  living  area,  install  a

field-fabricated secondary condensate pan under the entire unit.

3” / 76mm

WARNING

!

EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death.

Provide trap with air gap in drain line when connecting to waste (sewer)

line.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental damage.
Remove and recycle all components or materials (i.e., oil, refrigerant,

etc.) before unit final disposal.

Condensate
Line

Trap

Sewer Line

Air Gap Above
Liquid Level

Summary of Contents for CNPHP

Page 1: ...ult in enhanced installation reliability or operation NOTE Nitrogen can leak out through the needle pierce hole in the plugs This does not indicate a leaking coil nor warrant return of the coil INTRODUCTION The CNPHP is a horizontal multi use furnace coil Fig 1 With the use of field supplied transition duct these furnace coils can also be applied to other similar horizontal furnaces on the market ...

Page 2: ...V designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE All TXV S have preset superheat settings and are not field adjustable Cabinet Sweating If the unit is installed in a garage attic or other unconditioned space special attention may need to be given to the potential of cabinet sweating Condensate Management With proper installation these coils will ...

Page 3: ...stall and orientate the components as shown in Fig 4 Use Table 1 and Table 2 to identify which Application Letters A through J are acceptable for the furnace width and coil width being used in a specific situation Orientate and configure the furnace and coil as shown in each application A180215A Fig 4 Horizontal Installation Applications HORIZONTAL RIGHT INSTALLATIONS Acceptable for Air Conditione...

Page 4: ... Fig 5 A05419 Fig 5 Mount Attachment Plates 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace Fig 6 5 Seal joint between coil casing and furnace to create air tight seal using locally approved materials A05420 Fig 6 Attach Coil to Furnace NOTE If the coil and furnace are different widths refer to Fig 4 and Table 1 Table 2 HORIZONTAL ATTIC INSTALLATION Constru...

Page 5: ...acuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line See Table 3 for coil connection tube size 1 Remove cabinet access door 2 Remove rubber plugs suction plug then liquid plug from coil stubs using a pulling and twisting motion Hold coil stubs steady to avoid bending or distorting 3 Remove tubing plate with rub...

Page 6: ...pan should be drained to a noticeable place As an alternative to using an external condensate pan some localities may allow the running of a separate 3 4 in 19 mm condensate line with appropriate trap per local code to a place where the condensate will be noticeable The owner of the structure must be informed that when condensate flows from secondary drain or external condensate pan the unit requi...

Reviews: