background image

CNPHP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

INSTALLATION

A06031

Fig. 1 – Furnace Coil

CNPHP  furnace coils  are  NOT  designed to be  installed with furnaces

that measure wider than the coil itself.
Before  installation,  there  are  several  other  performance  requirements

that  must be considered because  poor  installation can  negatively  alter

performance. The following section will briefly discuss those factors.

Airflow

Airflow  amount  and  distribution  are  vital  to  adequate  system

performance.  Problems  that can  be experienced  with  incorrect airflow

include:

• low system performance

• restricted TXV

• frosted coil

• poor humidity control

• water blow-off

NOTE: 

In  addition,  heat  pump  applications  require  airflow  in  a

particular direction for best performance. See decal on front of coil for

correct direction.
When attaching the coil and building the plenum, pay special attention to

the effect these details will have on airflow. After system start-up, check

the cfm to insure that it is correct. (Generally, the cfm should be 350 to

400 cfm/ton during normal cooling operation.)

TXV

A  thermal  expansion  valve  is  utilized  in  this  coil  design  to  optimize

performance and  comfort  throughout the entire operating  range of  the

system. Special attention needs to be taken to the TXV when installing

the coil

• Do not overheat valve. Temperatures that exceed 212°F (100°C) can

harm valve performance. Use a wet cloth or heat sink when brazing.

• Place  liquid  filter  dryer  near  ID  unit  to  reduce  the  risk  of  debris

clogging the valve.

• Make  sure  TXV  bulb  is  securely  fastened  and  wrapped  in  the

indentation on vapor line tube.

CNPHP Models:
These coils have a factory-installed hard-shutoff TXV designed only for

use with R-410A refrigerant. Use only with outdoor units designed for

R-410A.

NOTE: 

All  TXV’S  have  preset  superheat  settings  and  are  not

field-adjustable.

Cabinet Sweating

If the unit is installed in a garage, attic, or other unconditioned space,

special  attention  may  need  to  be  given  to  the  potential  of  cabinet

sweating. 

Condensate Management

With proper installation, these coils will manage the condensate without

blow-off into the duct work. The 43, 60, and 61 size coils require the

addition of a pan extension for both horizontal left and horizontal right

position, which is supplied with the coils. See detailed instructions for

more info. Also, refer to Connect Condensate Drain Line section of this

instruction.

HORIZONTAL-RIGHT AND HORIZONTAL-LEFT 

WITH PAN EXTENSION (43, 60, and 61 Sizes Only)

There  are  two  separate  pan  extensions  shipped  with  the  unit.  For

horizontal  left  installations,  use  the  pan  attached  to  the  left  shipping

bracket.  For  horizontal  right  installations,  use  the  pan  attached  to  the

right shipping bracket. Be sure to use the correct pan extension for the

application.  There  should  not  be  any  gaps  between  the  plastic

condensate pan and the pan extension. All condensate should flow from

the pan extension to the plastic condensate pan and not leak into the coil

cabinet or duct.

NOTE: 

Discard the pan not used and both shipping brackets.

For  horizontal-left  installation,  install  pan  extension  onto  left  end  of

horizontal-condensate  pan.  Pan  extension  is  slotted  to  fit  onto

condensate pan edge and will extend into supply plenum (

Fig. 2

).

A06032

Fig. 2 – Horizontal-Left Installation of Pan Extension

(43, 60 & 61 sizes only)

Shipping Brace

Remove
 2 Screws

Pan Extension

CAUTION

!

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When  installing  over  a  finished  ceiling  and/or  living  area,  install  a

field-fabricated secondary condensate pan under the entire unit.

Supply
Plenum

Condensate Pan

Pan Extension

Summary of Contents for CNPHP

Page 1: ...ult in enhanced installation reliability or operation NOTE Nitrogen can leak out through the needle pierce hole in the plugs This does not indicate a leaking coil nor warrant return of the coil INTRODUCTION The CNPHP is a horizontal multi use furnace coil Fig 1 With the use of field supplied transition duct these furnace coils can also be applied to other similar horizontal furnaces on the market ...

Page 2: ...V designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE All TXV S have preset superheat settings and are not field adjustable Cabinet Sweating If the unit is installed in a garage attic or other unconditioned space special attention may need to be given to the potential of cabinet sweating Condensate Management With proper installation these coils will ...

Page 3: ...stall and orientate the components as shown in Fig 4 Use Table 1 and Table 2 to identify which Application Letters A through J are acceptable for the furnace width and coil width being used in a specific situation Orientate and configure the furnace and coil as shown in each application A180215A Fig 4 Horizontal Installation Applications HORIZONTAL RIGHT INSTALLATIONS Acceptable for Air Conditione...

Page 4: ... Fig 5 A05419 Fig 5 Mount Attachment Plates 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace Fig 6 5 Seal joint between coil casing and furnace to create air tight seal using locally approved materials A05420 Fig 6 Attach Coil to Furnace NOTE If the coil and furnace are different widths refer to Fig 4 and Table 1 Table 2 HORIZONTAL ATTIC INSTALLATION Constru...

Page 5: ...acuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line See Table 3 for coil connection tube size 1 Remove cabinet access door 2 Remove rubber plugs suction plug then liquid plug from coil stubs using a pulling and twisting motion Hold coil stubs steady to avoid bending or distorting 3 Remove tubing plate with rub...

Page 6: ...pan should be drained to a noticeable place As an alternative to using an external condensate pan some localities may allow the running of a separate 3 4 in 19 mm condensate line with appropriate trap per local code to a place where the condensate will be noticeable The owner of the structure must be informed that when condensate flows from secondary drain or external condensate pan the unit requi...

Reviews: