40
Table 11 —30MPA,MPW016-045 UNITS
LEGEND
*
Supply Range — Units are suita
b
le for use on electrical systems where
voltage supplied to the unit terminals is not
b
elow or a
b
ove the listed
range limits.
NOTES:
1. All units have one field power terminal
b
lock.
2. Maximum incoming wire size is as follows:
For units with terminal
b
lock:
350 kcmil for unit sizes 030-045;
208/230-3-60 voltages.
2/0 for unit sizes 016-045; all other voltages.
For units with optional non-fused disconnect:
350 kcmil for unit sizes:
030-045; 208/230-3-60 voltages.
045; 380-3-60 voltage.
3/0 AWG for unit sizes:
016,020; 208/230-3-60 voltages.
020-040; 380-3-60 voltage.
030-045; 460-3-60, 380/415-3-50 and 575-3-60 voltages.
2 AWG for unit sizes:
016: 380-3-60 voltage.
016,020; 460-3-60, 380/415-3-50 and 575-3-60 voltages.
For units with optional fused disconnect:
6 AWG to 10 AWG for all voltages.
3. Additional control circuit power is not re
q
uired.
4. Any field modification of factory wiring must
b
e in compliance with
all applica
b
le codes. Field-installed power wires must
b
e rated
75°C minimum.
5. Use copper conductors only.
6. Control circuit power supply is 24-v single phase. Control power is
supplied
b
y the factory-installed control transformer.
7. The MOCP of the electrical distri
b
ution panel is calculated as
follows:
First, calculate the MOCP of each individual chiller. MOCP =
2.25 (Largest RLA) + Sum of the other RLAs. Sum the MOCPs
of each individual chiller. This is the MOCP of the electrical dis-
tri
b
ution panel associated with this
b
ank of chillers. Select the
next size down fuse from this value.
The recommended fuse size in amps (RFA) is calculated as fol-
lows: RFA = 1.50
*
(largest RLA) + (Smallest RLA) for the given
b
ank of chillers.
8. The MCA of the electrical distri
b
ution panel is calculated as
follows:
First, calculate the MCA of each individual chiller. MCA = 1.25
(Largest RLA) + sum of the other RLAs. Sum the MCAs of
each individual chiller. This is the MCA of the electrical distri
b
u-
tion panel associated with this
b
ank of chillers.
UNIT SIZE
30MPA,
MPW
VOLTS
NAMEPLATE
VOLTAGE
COMPRESSOR A1
COMPRESSOR A2
COMPRESSOR A3
UNIT
MIN MAX RLA (EA) LRA (EA) RLA (EA) LRA (EA)
RLA (EA)
LRA (EA)
MCA
ICF
MOCP REC FUSE
016
208/230-3-60
187
253
24.8
240.0
17.2
164
N/A
N/A
48.2
257.2
70
60
380-3-60
342
418
16.0
134.0
12.2
73
32.2
146.2
45
40
460-3-60
414
508
12.4
130.0
8.6
75
24.1
138.6
35
30
575-3-60
518
632
10.0
93.7
7.0
54
19.5
100.7
25
25
380/415-3-50
342
440
12.4
130.0
8.6
75
24.1
138.6
35
30
020
208/230-3-60
187
253
35.8
239.0
35.8
239
N/A
N/A
80.6
274.8
110
90
380-3-60
342
418
23.7
145.0
23.7
145
53.4
168.7
70
60
460-3-60
414
508
17.9
125.0
17.9
125
40.3
142.9
50
45
575-3-60
518
632
14.3
80.0
14.3
80
32.2
94.3
45
40
380/415-3-50
342
440
20.0
118.0
20.0
118
45.0
138.0
60
60
030
208/230-3-60
187
253
55.8
340.0
55.8
340
N/A
N/A
125.6
395.8
175
150
380-3-60
342
418
34.0
196.0
34.0
196
76.5
230.0
110
90
460-3-60
414
508
26.9
179.0
26.9
179
60.5
205.9
80
70
575-3-60
518
632
23.7
132.0
23.7
132
53.3
155.7
70
60
380/415-3-50
342
440
28.6
174.0
28.6
174
64.3
202.6
90
80
040
208/230-3-60
187
253
51.3
300.0
51.3
300
51.3
300
166.7
402.6
200
200
380-3-60
342
418
26.9
139.0
26.9
139
26.9
139
87.4
192.8
110
100
460-3-60
414
508
23.1
150.0
23.1
150
23.1
150
75.1
196.2
90
90
575-3-60
518
632
19.9
109.0
19.9
109
19.9
109
64.7
148.8
80
70
380/415-3-50
342
440
25.0
140.0
25.0
140
25.0
140
81.3
190.0
100
90
045
208/230-3-60
187
253
55.8
340.0
55.8
340
55.8
340
181.4
451.6
225
200
380-3-60
342
418
34.0
196.0
34.0
196
34.0
196
110.5
264.0
125
125
460-3-60
414
508
26.9
179.0
26.9
179
26.9
179
87.4
232.8
110
100
575-3-60
518
632
23.7
132.0
23.7
132
23.7
132
77.0
179.4
100
90
380/415-3-50
342
440
28.6
174.0
28.6
174
28.6
174
92.9
231.1
110
110
UNIT SIZE
30MPW
VOLTS
NAMEPLATE
VOLTAGE
COMPRESSOR A1
COMPRESSOR B1
COMPRESSOR (A/B)2
UNIT
MIN MAX RLA (EA) LRA (EA) RLA (EA) LRA (EA)
RLA (EA)
LRA (EA)
MCA
ICF
MOCP REC FUSE
032
208/230-3-60
187
253
42.0
340
42.0
340
N/A
N/A
94.5
382.0
125
110
460-3-60
414
508
21.0
179
21.0
179
47.3
200.0
60
60
575-3-60
518
632
17.0
132
17.0
132
38.3
149.0
50
45
AWG
—
American Wire Gage
ICF
—
Maximum instantaneous current flow during starting
kcmil
—
Thousand circular mils
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps (for wire sizing). Complies with NEC,
Section 430-24.
MOCP
—
Maximum Overcurrent Protection
Rec
Fuse
—
Recommended dual element fuse amps (150% of compres-
sor RLA). Size up to the next standard fuse size.
RLA
—
Rated Load Amps