Table 12 — Electrical Data — 30MPA,MPW050-071 Units with High Condensing Option
LEGEND
*
Supply Range — Units are suita
b
le for use on electrical systems
where voltage supplied to the unit terminals is not
b
elow or a
b
ove
the listed range limits.
NOTES:
1. All units have one field power terminal
b
lock.
2. Maximum incoming wire size is as follows:
For units with terminal
b
lock:
500 kcmil for all unit sizes 050-071; all voltages
For units with optional non-fused disconnect:
350 kcmil for unit sizes 050-071, 208/230-3-60 voltages.
3/0 AWG for all other voltages.
3. Additional control circuit power is not re
q
uired.
4. Any field modification of factory wiring must
b
e in compliance
with all applica
b
le codes. Field-installed power wires must
b
e
rated 75 C minimum.
5. Use copper conductors only.
6. Control circuit power supply is 24-v single phase. Control power
is supplied
b
y the factory-installed control transformer.
7. The MOCP of the electrical distri
b
ution panel is calculated as
follows:
First, calculate the MOCP of each individual chiller. MOCP =
2.25 (Largest RLA) + Sum of the other RLAs. Sum the MOCPs
of each individual chiller. This is the MOCP of the electrical dis-
tri
b
ution panel associated with this
b
ank of chillers. Select the
next size down fuse from this value.
The recommended fuse size in amps (RFA) is calculated as fol-
lows: RFA = 1.50
*
(largest RLA) + (Smallest RLA) for the given
b
ank of chillers.
8. The MCA of the electrical distri
b
ution panel is calculated as
follows:
First, calculate the MCA of each individual chiller. MCA = 1.25
(Largest RLA) + sum of the other RLAs. Sum the MCAs of
each individual chiller. This is the MCA of the electrical distri
b
u-
tion panel associated with this
b
ank of chillers.
UNIT SIZE
30MPA,
MPW
VOLTS
NAMEPLATE
VOLTAGE*
COMPRESSOR A1
COMPRESSOR A2
UNIT
RLA
LRA
RLA
LRA
MCA
ICF
MOCP
REC
FUSE
MIN
MAX
050
208/230-3-60
187
253
85.1
436
85.1
436
191.5
521.1
250
225
380-3-60
342
418
49.3
252
49.3
252
110.9
301.3
150
125
460-3-60
414
508
40.7
212
40.7
212
91.6
252.7
125
110
575-3-60
518
632
32.6
168
32.6
168
73.4
200.6
100
90
380/415-3-50
342
440
40.7
212
40.7
212
91.6
252.7
125
110
055
208/230-3-60
187
253
85.1
436
106.2
578
217.9
663.1
300
250
380-3-60
342
418
49.3
252
64.3
355
129.7
404.3
175
150
460-3-60
414
508
40.7
212
53.1
290
107.1
330.7
150
125
575-3-60
518
632
32.6
168
42.5
255
85.7
287.6
125
100
380/415-3-50
342
440
40.7
212
53.1
290
107.1
330.7
150
125
060
208/230-3-60
187
253
85.1
436
102.8
635
213.6
720.1
300
250
380-3-60
342
418
49.3
252
62.2
355
127.1
404.3
175
150
460-3-60
414
508
40.7
212
51.4
280
105.0
320.7
150
125
575-3-60
518
632
32.6
168
41.1
225
84.0
257.6
125
100
380/415-3-50
342
440
40.7
212
51.4
280
105.0
320.7
150
125
065
208/230-3-60
187
253
85.1
436
128.2
602
245.4
687.1
350
300
380-3-60
342
418
49.3
252
77.6
367
146.3
416.3
200
175
460-3-60
414
508
40.7
212
64.1
298
120.8
338.7
175
150
575-3-60
518
632
32.6
168
51.3
229
96.7
261.6
125
110
380/415-3-50
342
440
40.7
212
64.1
298
120.8
338.7
175
150
071
208/230-3-60
187
253
106.2
578
128.2
602
266.5
708.2
350
300
380-3-60
342
418
64.3
355
77.6
367
161.3
431.3
225
200
460-3-60
414
508
53.1
290
64.1
298
133.2
351.1
175
150
575-3-60
518
632
42.5
255
51.3
229
106.6
297.5
150
125
380/415-3-50
342
440
53.1
290
64.1
298
133.2
351.1
175
150
AWG
—
American Wire Gage
ICF
—
Maximum instantaneous current flow during starting.
kcmil
—
Thousand circular mils
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps (for wire sizing). Complies with
NEC, Section 430-24.
MOCP
—
Maximum Overcurrent Protection
Rec
Fuse
—
Recommended dual element fuse amps (150% of
compressor RLA). Size up to the next standard fuse
size.
RLA
—
Rated Load Amps