background image

10

Table 3 — Liquid Line Refrigerant Chart

Table 4 — Double Discharge Riser Data

The 30MPA units that use air-cooled or evaporative con-

densers must have adequate means for head pressure control

when operating below 60 F (15.6 C) ambient.

The 30MPA remote condenser requirements are as follows: 

• If multiple units are connected to a single condenser,

ensure each refrigerant circuit has its own head pressure

control.

• Condenser must provide 15 F (8.3 C) subcooling, maxi-

mum of 40 F (22.2 C) difference between saturated con-

densing temperature and outdoor ambient temperature

(to prevent overload at high ambient temperatures), and

a minimum of 20 F (11.1 C) difference (to ensure sub-

cooling).

• Do not manifold multiple refrigerant circuits into a

single condenser.

• If air-cooled condenser is located below chiller, refer to

condenser manufacturer’s performance data for avail-

able liquid lift.

• Refer to condenser installation instructions for location

guidelines.

Carrier recommends that a field-supplied pressure relief de-

vice be installed in each discharge line of 30MPA units. Most

local codes require the discharge line relief valve to be vented

directly to the outdoors. The vent 

must not

 be smaller than the

discharge line relief valve outlet.
EVACUATION AND DEHYDRATION — Because the

30MP systems use polyolester oil which can absorb moisture,

it is important to minimize the amount of time that the system

interior is exposed to the atmosphere. Minimizing the exposure

time of the oil to the atmosphere will minimize the amount of

moisture that needs to be removed during evacuation. 

Once all of the piping connections are complete, leak test

the unit and then pull a deep dehydration vacuum. Connect the

vacuum pump to the charging valve in the suction line and to

the liquid line service valve. For best results, it is recommended

that a vacuum of at least 500 microns (0.5 mm Hg) be used. 

Afterwards, to ensure that no moisture is present in the sys-

tem, perform a standing vacuum-rise test. With the unit in deep

vacuum (500 microns or less), isolate the vacuum pump from

the system. Observe the rate-of-rise of the vacuum in the sys-

tem. If the vacuum rises by more than 50 microns in a 30-min-

ute time period, continue the dehydration process. Maintain a

vacuum on the system until the standing vacuum requirement

is met. This will ensure a dry system.

By following these evacuation and dehydration procedures,

the amount of moisture present in the system will be

minimized.   
30MPW CONDENSER DESCRIPTION — All 30MPW

units use a brazed-plate heat-exchanger-type condenser. These

heat exchangers are made of embossed plates of acid-resistant

stainless steel. Every other plate is reversed so that the ridges

of the herringbone pattern intersect one another on adjacent

plates, forming a lattice of contact points. These plates are

vacuum-brazed together to form a compact and pressure-

resistant heat exchanger.

After brazing, the impressions in the plates form 2 separate

systems of channels where the refrigerant and water flows are

counterflow. The number of plates varies depending on unit

tonnage. The condensers provide approximately 10º to 12º F

(6º to 8º C) liquid subcooling at the standard Air Conditioning,

Heating and Refrigeration Institute (AHRI) rating condition.
30MPW CONDENSER — When facing the unit control box,

the condenser is the uninsulated heat exchanger located on the

left-hand side. The water connections are on the right-hand

side of the heat exchanger with the LIQUID-IN connection at

the bottom, and the LIQUID-OUT connection at the top.

A strainer with a minimum of 40 mesh 

must

 be installed

within 10 ft (3 m) of the condenser water inlet to prevent debris

from clogging or damaging the heat exchanger. The strainer is

required for operation and is available as an accessory.

To install the victaulic coupling (see Fig. 11):

1. Use victaulic couplings designed for use on IPS dimen-

sioned materials. For example, Style 75, Style 77, Quick

Vic Style 107, or Style 177.

2. Lubricate the gasket lips and stretch the gasket over the

end of the heat exchanger coupling. Avoid twisting the

gasket when installing.

3. Bring the pipe and heat exchanger coupling ends together

into alignment. Slide the gasket so that it is centered over

the ends. Apply a light film of lubricant to the gasket, or

to the outside diameter of the pipe. Avoid twisting the

gasket during installation.

4. Install the inside coupling half over the gasket and then

install the outer half. Connect with nuts and bolts. Tighten

the nuts equally on both sides. Ensure there is no gap be-

tween the two halves of the coupling.

5. Alternately tighten the nuts with a wrench to draw the

coupling halves together uniformly. The joint is now

complete.

PIPE DIAMETER

(in.)

POUNDS PER 10 LINEAR FEET

(kg per 3m)

1

/

0.6 (0.27)

5

/

8

 

1.0 (0.45)

7

/

8

2.0 (0.91)

30MPA

UNIT

TOTAL LINEAR LENGTH OF 

INTERCONNECTING PIPE

ft (m)

MINIMUM 

TONNAGE WITH 

DOUBLE RISER

0 - 200

(0 - 61.0)

Riser A

D (in.)

Riser B

D (in.)

015

7

/

8

1

1

/

8

1.

8

6

020

7

/

8

1

1

/

8

1.

8

6

030

7

/

8

1

1

/

8

1.

8

6

040

7

/

8

1

3

/

8

1.

8

6

045

7

/

8

1

3

/

8

1.

8

6

Fig. 10 — Double Discharge Riser   

Construction Detail

a30-1245

TO
CONDENSER

B

RED.
TEE

90 DEGREE
STR ELLS

FROM
CHILLER

45 DEGREE
STR ELLS

A

LEGEND

RED. TEE

Reducing Tee

STR ELLS —

Street El

b

ows

a30-1979ef

Summary of Contents for AQUASNAP 30MPA

Page 1: ...ese installation instructions cover the 30MPA MPW units with ComfortLink controls The 30MPA units are condenserless units and the 30MPW units are all fluid cooled See Fig 1 and 2 SAFETY CONSIDERATIONS Installing starting up and servicing this equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualified installe...

Page 2: ... oil to add to the system e Carefully unsweat remaining tubing stubs when nec essary Oil can ignite when exposed to torch flame Failure to follow these procedures may result in personal injury or death CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the...

Page 3: ... TABLE FOR QTY OUT IN OPTIONAL SOUND ENCLOSURE FIELD CONNECTION 4 7 8 K O NON FUSED DISCONNECT OPTIONAL 1 4 FPT ACCESS P T ACCESS PORTS 1 4 SAE FLARE RELIEF CONNECTION POWER ENTRY WATER CONNECTIONS IN OUT 2 VICTAULIC 015 020 2 1 2 VICTAULIC 030 045 COOLER COOLER COOLER CONTROL PANEL END OPPOSITE CONTROL PANEL END MOUNTING HOLES 9 16 MOUNTING HOLES 9 16 IN OUT 040 045 TON ONLY FORK POCKETS SCROLLIN...

Page 4: ...t 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensions in are in millimeters 4 Allow 36 in 914 mm clearance on control panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option a30 5033 ...

Page 5: ... 0 8 1 2 2 4 3 2 3 4 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Fluid Side Pressure psig 300 300 300 300 300 Water Connections in Inlet and Outlet Victaulic IPS 2 2 21 2 21 2 21 2 Drain NPT 1 2 1 2 1 2 1 2 1 2 CONDENSER 30MPW Only Weight lb empty 34 9 43 6 104 6 136 7 188 3 Net Fluid Volume gal 1 2 1 6 2 9 4 1 5 9 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Flu...

Page 6: ...kPa 3482 3482 3896 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 Water Connections in Inlet and Outlet Victaulic IPS 11 2 11 2 2 2 2 CONDENSER REFRIGERANT CONNECTIONS 30MPA Only Liquid Line ODS in 1 2 1 2 5 8 5 8 5 8 Discharge Line ODS in 13 8 13 8 13 8 15 8 15 8 CHASSIS DIMENSIONS mm Length 1397 1397 1397 1397 1397 Width 813 813 813 813 813 Height 1588 1588 1588 1588 1588 MIN...

Page 7: ...t is installed verify that mounting bolt torque is 7 to 10 ft lb 9 to 14 Nm Step 5 Make Piping Connections See Fig 8 and 9 for typical piping applications 30MPA SYSTEM CONDENSER For detailed condenser piping installation instructions for 30MPA systems refer to separate instructions packaged with the remote condenser units Condenser refrigerant piping for 30MPA units should be sized to minimize the...

Page 8: ...ques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addi tion of a holding tank to ensure adequate volume 6 A strainer with a minimum of 40 mesh must be installed within 10 ft 3 m of the evaporator fluid inlet ...

Page 9: ... of Heating Refrigerating and Air Condi tioning Engineers handbook for details on proper piping sizes and design 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addition of a holding tank to ensure adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit Double riser may be required check unit minimum capacity 7 Trap should be inst...

Page 10: ... use a brazed plate heat exchanger type condenser These heat exchangers are made of embossed plates of acid resistant stainless steel Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates forming a lattice of contact points These plates are vacuum brazed together to form a compact and pressure resistant heat exchanger After brazing the...

Page 11: ... evaporator flow switch is standard on all units This is a thermal dispersion type switch that is installed in evaporator fluid outlet The switch is set to open when the evaporator fluid flow drops below the minimum set point For variable primary flow applications it may be necessary to adjust the flow switch set point to avoid nuisance trips Con tact Carrier service engineering for the method nee...

Page 12: ...0 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM 120 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters second 1 2 3 5 4 Fig 12 Condenser Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5037 a30 5036 ...

Page 13: ... 160 170 180 190 200 Water Pressure Drop GPM 1 5 4 3 2 120 3 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Liters second 1 2 4 5 Fig 13 Evaporator Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5035 a30 5034 ...

Page 14: ...the desired slightly alkaline water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 16 during the cleaning process Filter side flow rate should be enough to filter the entire water volume every 3 to 4 hours Change filters as often as neces sary during the cleaning process d Remove temporary bypass when clea...

Page 15: ...ined for the required gpm Step 7 Make Electrical Connections All field wiring must comply with local code requirements Electrical data for the complete unit and for the compressors is shown in Table 8 See Fig 17 for field wiring connections A field supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed Control circuit power is 24 v on all unit...

Page 16: ...voltage 3 0 for unit sizes 015 020 208 230 3 60 voltages 020 040 380 3 60 voltage 030 045 460 3 60 and 575 3 60 voltages 2 AWG for unit sizes 015 380 3 60 voltage 015 020 460 3 60 and 575 3 60 voltages 3 Additional control circuit power is not required 4 Any field modification of factory wiring must be in compliance with all applicable codes Field installed power wires must be rated 75 C minimum 5...

Page 17: ...n power and control power entrance locations 5 Terminal 24 of the LVT is for control of chilled water pump CWP starter Terminal 20 of the LVT is for control of condenser pump CNP starter or condenser fan relay CFR The maximum load allowed for the relays is 5 VA sealed 10 VA inrush at 24 VAC Field power supply is not required 6 Terminal 25 of LVT is for an alarm relay The maximum load allowed for a...

Page 18: ......

Page 19: ......

Page 20: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300077 01 Printed in U S A Form 30MP 5SI Pg 20 612 11 11 Replaces 30MP 1SI Copyright 2011 Carrier Corporation ...

Reviews: