background image

7

Step 1 — Inspect Shipment — 

Inspect unit for dam-

age or missing parts. If damaged, or if shipment is incomplete,

file a claim immediately with the shipping company.

Step 2 — Position the Unit — 

The unit may be

moved by means of rollers under the rails or a forklift truck.

If accessory mobility kit is to be used, install this accessory

after bringing unit into building and before moving the unit to

its final location per installation instructions provided with the

accessory. The factory-installed mobility kit option consists of

4 swivel-type wheels that are field-mounted to the legs of the

unit. See Fig. 7.
NOTE: The wheels are equipped with a thumb-screw brake.

Step 3 — Place the Unit

NOTE: 

These units are not suitable for unprotected outdoor

use

.

Carrier recommends that these units be located in the base-

ment or on the ground floor. However, if it is necessary to lo-

cate the unit on an upper floor, be sure the structure has been

designed to support the unit weight. If necessary, add structural

support to floor. Also, be sure the surface for installation is

level. Refer to Fig. 4 and 5 for space requirements and weight

distribution.

Only electrical power connections, water connections for

condenser, fluid connections for evaporator, and strainer

installation are required for 30MPW installation. Installation of

30MPA units varies only in field piping required for the remote

condenser.

When the unit is in its final position, remove the packaging

and remove the mobility kit wheels (if equipped). Remove

3

/

8

-in. wheel nuts to remove wheels from unit legs. Level the

unit (using a level), and bolt the unit to the floor or pad.

If unit is to be mounted on unit external vibration

isolators, follow the mounting instructions included with

the accessory vibration isolator.
If unit has accessory leveling kit installed, follow the instruc-

tions provided with the accessory to make sure unit is level and

in the correct position.

Step 4 — Check Compressor Mounting — 

As

shipped, units with two compressors are held down with 6 bolts

through rubber grommets. All units with three compressors are

held down with 8 bolts per pair through grommets. After unit is

installed, verify that mounting bolt torque is 7 to 10 ft-lb (9 to

14 Nm).

Step 5 — Make Piping Connections — 

See

Fig. 8 and 9 for typical piping applications.
30MPA SYSTEM CONDENSER — For detailed condenser

piping installation instructions for 30MPA systems, refer to

separate instructions packaged with the remote condenser

units.

Condenser refrigerant piping for 30MPA units should be

sized to minimize the amount of refrigerant required. Consider

the length of piping required between the condenser and indoor

unit, the amount of liquid lift, and the compressor oil return.

Suction and liquid lines should be sized in accordance with

Table 2. Liquid line refrigerant chart is shown in Table 3.

Double discharge risers may be required for proper oil return if

condenser is located  above the chiller and if hot gas bypass is

installed, or if unit is used for medium temperature brine

application.  Double discharge risers are required for all units

with digital compressors. See Table 4 and Fig. 10.

Table 2 — Single Circuit 30MPA Line Sizing Chart

         

LEGEND

NOTES:

1. Shaded areas indicate dou

b

le discharge riser re

q

uired if unit is

e

q

uipped with hot gas 

b

ypass or operation 

b

elow 40 F LWT (Leaving

Water Temperature).

2. All units with digital compressors re

q

uire dou

b

le discharge riser. 

CAUTION

Unit is top heavy. Unit may tip if handled without care.

Damage to unit or injury may result.

A

D

CONTROL
PANEL

S

IDE

WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE — L

b

 (kg)

UNIT 30MP

MOUNTING HOLE

A

B

C

D

A015

156   (71)

A020

159   (72)

A030

1

8

1   (

8

2)

A040

22

8

 (104)

A045

234 (106)

W015

170   (77)

W020

176   (

8

0)

W030

216   (9

8

)

W040

275 (125)

W045

29

8

 (135)

Fig. 6 — Mounting Hole Weight Distribution

a30-5040

Fig. 7 — Mobility Kit

a30-5041

30MPA

UNIT

UNIT 

REFRIGERANT 

CONNECTIONS

(CHILLER 

CONNECTION 

SIZE)

ODS

TOTAL LINEAR LENGTH OF 

INTERCONNECTING PIPE

ft (m)

0 - 50

(0 - 15.4)

Equiv. Pipe 

Length = 75 ft 

50 - 100

(15.4 - 30.5)

Equiv. Pipe 

Length = 150 ft

100 - 200

(30.5 - 61.0)

Equiv. Pipe 

Length = 300 ft

L (in.)

D (in.)

L (in.)

D (in.)

L (in.)

D (in.)

L (in.)

D (in.)

015

1

/

2

1

3

/

8

1

/

2

1

3

/

8

5

/

8

1

3

/

8

5

/

8

1

3

/

8

020

1

/

2

1

3

/

8

5

/

8

1

3

/

8

5

/

8

1

3

/

8

7

/

8

1

3

/

8

030

5

/

8

1

3

/

8

7

/

8

1

3

/

8

7

/

8

1

3

/

8

7

/

8

1

3

/

8

040

5

/

8

1

5

/

8

7

/

8

1

5

/

8

7

/

8

1

5

/

8

1

1

/

8

1

5

/

8

045

5

/

8

1

5

/

8

7

/

8

1

5

/

8

7

/

8

1

5

/

8

1

1

/

8

1

5

/

8

D

Discharge Line Size (discharge line size is e

q

ual to the chiller 

connection size)

L

Li

q

uid Line Size (li

q

uid line size is e

q

ual to or greater than the 

chiller connection size)

Summary of Contents for AQUASNAP 30MPA

Page 1: ...ese installation instructions cover the 30MPA MPW units with ComfortLink controls The 30MPA units are condenserless units and the 30MPW units are all fluid cooled See Fig 1 and 2 SAFETY CONSIDERATIONS Installing starting up and servicing this equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualified installe...

Page 2: ... oil to add to the system e Carefully unsweat remaining tubing stubs when nec essary Oil can ignite when exposed to torch flame Failure to follow these procedures may result in personal injury or death CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the...

Page 3: ... TABLE FOR QTY OUT IN OPTIONAL SOUND ENCLOSURE FIELD CONNECTION 4 7 8 K O NON FUSED DISCONNECT OPTIONAL 1 4 FPT ACCESS P T ACCESS PORTS 1 4 SAE FLARE RELIEF CONNECTION POWER ENTRY WATER CONNECTIONS IN OUT 2 VICTAULIC 015 020 2 1 2 VICTAULIC 030 045 COOLER COOLER COOLER CONTROL PANEL END OPPOSITE CONTROL PANEL END MOUNTING HOLES 9 16 MOUNTING HOLES 9 16 IN OUT 040 045 TON ONLY FORK POCKETS SCROLLIN...

Page 4: ...t 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensions in are in millimeters 4 Allow 36 in 914 mm clearance on control panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option a30 5033 ...

Page 5: ... 0 8 1 2 2 4 3 2 3 4 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Fluid Side Pressure psig 300 300 300 300 300 Water Connections in Inlet and Outlet Victaulic IPS 2 2 21 2 21 2 21 2 Drain NPT 1 2 1 2 1 2 1 2 1 2 CONDENSER 30MPW Only Weight lb empty 34 9 43 6 104 6 136 7 188 3 Net Fluid Volume gal 1 2 1 6 2 9 4 1 5 9 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Flu...

Page 6: ...kPa 3482 3482 3896 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 Water Connections in Inlet and Outlet Victaulic IPS 11 2 11 2 2 2 2 CONDENSER REFRIGERANT CONNECTIONS 30MPA Only Liquid Line ODS in 1 2 1 2 5 8 5 8 5 8 Discharge Line ODS in 13 8 13 8 13 8 15 8 15 8 CHASSIS DIMENSIONS mm Length 1397 1397 1397 1397 1397 Width 813 813 813 813 813 Height 1588 1588 1588 1588 1588 MIN...

Page 7: ...t is installed verify that mounting bolt torque is 7 to 10 ft lb 9 to 14 Nm Step 5 Make Piping Connections See Fig 8 and 9 for typical piping applications 30MPA SYSTEM CONDENSER For detailed condenser piping installation instructions for 30MPA systems refer to separate instructions packaged with the remote condenser units Condenser refrigerant piping for 30MPA units should be sized to minimize the...

Page 8: ...ques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addi tion of a holding tank to ensure adequate volume 6 A strainer with a minimum of 40 mesh must be installed within 10 ft 3 m of the evaporator fluid inlet ...

Page 9: ... of Heating Refrigerating and Air Condi tioning Engineers handbook for details on proper piping sizes and design 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addition of a holding tank to ensure adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit Double riser may be required check unit minimum capacity 7 Trap should be inst...

Page 10: ... use a brazed plate heat exchanger type condenser These heat exchangers are made of embossed plates of acid resistant stainless steel Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates forming a lattice of contact points These plates are vacuum brazed together to form a compact and pressure resistant heat exchanger After brazing the...

Page 11: ... evaporator flow switch is standard on all units This is a thermal dispersion type switch that is installed in evaporator fluid outlet The switch is set to open when the evaporator fluid flow drops below the minimum set point For variable primary flow applications it may be necessary to adjust the flow switch set point to avoid nuisance trips Con tact Carrier service engineering for the method nee...

Page 12: ...0 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM 120 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters second 1 2 3 5 4 Fig 12 Condenser Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5037 a30 5036 ...

Page 13: ... 160 170 180 190 200 Water Pressure Drop GPM 1 5 4 3 2 120 3 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Liters second 1 2 4 5 Fig 13 Evaporator Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5035 a30 5034 ...

Page 14: ...the desired slightly alkaline water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 16 during the cleaning process Filter side flow rate should be enough to filter the entire water volume every 3 to 4 hours Change filters as often as neces sary during the cleaning process d Remove temporary bypass when clea...

Page 15: ...ined for the required gpm Step 7 Make Electrical Connections All field wiring must comply with local code requirements Electrical data for the complete unit and for the compressors is shown in Table 8 See Fig 17 for field wiring connections A field supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed Control circuit power is 24 v on all unit...

Page 16: ...voltage 3 0 for unit sizes 015 020 208 230 3 60 voltages 020 040 380 3 60 voltage 030 045 460 3 60 and 575 3 60 voltages 2 AWG for unit sizes 015 380 3 60 voltage 015 020 460 3 60 and 575 3 60 voltages 3 Additional control circuit power is not required 4 Any field modification of factory wiring must be in compliance with all applicable codes Field installed power wires must be rated 75 C minimum 5...

Page 17: ...n power and control power entrance locations 5 Terminal 24 of the LVT is for control of chilled water pump CWP starter Terminal 20 of the LVT is for control of condenser pump CNP starter or condenser fan relay CFR The maximum load allowed for the relays is 5 VA sealed 10 VA inrush at 24 VAC Field power supply is not required 6 Terminal 25 of LVT is for an alarm relay The maximum load allowed for a...

Page 18: ......

Page 19: ......

Page 20: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300077 01 Printed in U S A Form 30MP 5SI Pg 20 612 11 11 Replaces 30MP 1SI Copyright 2011 Carrier Corporation ...

Reviews: