background image

14

It may not be possible to install air separators at the place of

lowest pressure and highest temperature. In such cases, prefer-

ence should be given to the points of highest temperature. It is

important that pipe be sized correctly so that free air can be

moved to the point of separation. Generally, a water velocity of

at least 2 feet per second will keep free air entrained and

prevent it from forming air pockets.

Automatic vents should be installed at all physically elevat-

ed points in the system so that air can be eliminated during

system operation. Provision should also be made for manual

venting during the water loop fill. It is important that the

automatic vents be located in accessible locations for

maintenance purposes, and that they be located where they can

be prevented from freezing.

Step 6 — Fill the Chilled Water Loop

WATER SYSTEM CLEANING — Proper  water  system

cleaning is of vital importance. Excessive particulates in the

water system can cause excessive pump seal wear, reduce or

stop flow, and cause damage of other components. Water

quality should be maintained within the limits indicated in

Table 7. Failure to maintain proper water quality may result in

heat exchanger failure.

1. Install a temporary bypass around the chiller to avoid cir-

culating dirty water and particulates into the pump pack-

age and chiller during the flush. Use a temporary circulat-

ing pump during the cleaning process. Also, be sure that

there is capability to fully drain the system after cleaning.

(See Fig 15.)

2. Be sure to use a cleaning agent that is compatible with all

system materials. Be especially careful if the system

contains any galvanized or aluminum components. Both

detergent-dispersant and alkaline-dispersant cleaning

agents are available.

3. It is a good idea to fill the system through a water meter.

This provides a reference point for the future for loop

volume readings, but it also establishes the correct

quantity of cleaner needed in order to get the required

concentration.

4. Use a feeder/transfer pump to mix the solution and fill the

system. Circulate the cleaning system for the length of

time recommended by the cleaning agent manufacturer.

a. After cleaning, drain the cleaning fluid and flush the

system with fresh water.

b. A slight amount of cleaning residue in the system can

help keep the desired, slightly alkaline, water pH of 8

to 9. Avoid a pH greater than 10, since this will

adversely affect pump seal components.

c. A side stream filter is recommended (see Fig. 16)

during the cleaning process. Filter side flow rate

should be enough to filter the entire water volume

every 3 to 4 hours. Change filters as often as neces-

sary during the cleaning process.

d. Remove temporary bypass when cleaning is

complete.

Table 7 — Water Quality Characteristics

and Limitations

 *Sulfides in the water 

q

uickly oxidize when exposed to air, re

q

uiring that

no agitation occur as the sample is taken. Unless tested immediately
at the site, the sample will re

q

uire sta

b

ilization with a few drops of one

Molar zinc acetate solution, allowing accurate sulfide determination up
to 24 hours after sampling. A low pH and high alkalinity cause system
pro

b

lems, even when 

b

oth values are within the ranges shown. The

term pH refers to the acidity, 

b

asicity, or neutrality of the water supply.

Below 7.0, the water is considered to 

b

e acidic. A

b

ove 7.0, water is

considered to 

b

b

asic. Neutral water contains a pH of 7.0.

†Dissolved car

b

on dioxide can either 

b

e calculated from the pH and

total alkalinity values, shown 

b

elow, or measured on the site using a

test kit. Dissolved Car

b

on Dioxide, PPM = TA x 2

[(6.3-pH)/0.3]

 where TA

= Total Alkalinity, PPM as CaCO

3

.

Di

s

trib

u

tion P

u

mp

Exp

a

n

s

ion

T

a

nk(

s

)

Air 

S

ep

a

r

a

tor

with Vent

Deco

u

pler

Chiller 1

Chiller 2

Zone 1

Zone 2

Zone 

3

NOTE: Expansion tanks must 

b

e disconnected for chillers placed parallel in the primary water loop.

Fig. 14 — Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems

a30-3226

CAUTION

Failure to properly clean all piping and components of the

chilled water system before unit start-up may result in

plugging of the heat exchanger, which can lead to poor per-

formance, nuisance alarms and damage from freezing.

Freezing damage caused by an improperly cleaned system

represents abuse and may impair or otherwise negatively

affect the Carrier product warranty.

 WATER CHARACTERISTIC

QUALITY LIMITATION

Alkalinity (HCO

3

-

)

70 – 300 ppm

Sulfate (SO

4

2-

)

Less than 70 ppm

HCO

3

-

/SO

4

2-

Greater than 1.0

Electrical Conductivity

10 – 500



S/cm

pH

7.5 – 9.0

Ammonium (NH

3

)

Less than 2 ppm

Chorides (Cl

-

)

Less than 300 ppm

Free chlorine (Cl

2

)

Less than 1 ppm

Hydrogen Sulfide (H

2

S)*

Less than 0.05 ppm

Free (aggressive) Carbon
Dioxide (CO

2

)†

Less than 5 ppm

Total Hardness (dH)

4.0 – 

8

.5

Nitrate (NO

3

)

Less than 100 ppm

Iron (Fe)

Less than 0.2 ppm

Aluminum (Al)

Less than 0.2 ppm

Manganese (Mn)

Less than 0.1 ppm

Summary of Contents for AQUASNAP 30MPA

Page 1: ...ese installation instructions cover the 30MPA MPW units with ComfortLink controls The 30MPA units are condenserless units and the 30MPW units are all fluid cooled See Fig 1 and 2 SAFETY CONSIDERATIONS Installing starting up and servicing this equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualified installe...

Page 2: ... oil to add to the system e Carefully unsweat remaining tubing stubs when nec essary Oil can ignite when exposed to torch flame Failure to follow these procedures may result in personal injury or death CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the...

Page 3: ... TABLE FOR QTY OUT IN OPTIONAL SOUND ENCLOSURE FIELD CONNECTION 4 7 8 K O NON FUSED DISCONNECT OPTIONAL 1 4 FPT ACCESS P T ACCESS PORTS 1 4 SAE FLARE RELIEF CONNECTION POWER ENTRY WATER CONNECTIONS IN OUT 2 VICTAULIC 015 020 2 1 2 VICTAULIC 030 045 COOLER COOLER COOLER CONTROL PANEL END OPPOSITE CONTROL PANEL END MOUNTING HOLES 9 16 MOUNTING HOLES 9 16 IN OUT 040 045 TON ONLY FORK POCKETS SCROLLIN...

Page 4: ...t 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensions in are in millimeters 4 Allow 36 in 914 mm clearance on control panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option a30 5033 ...

Page 5: ... 0 8 1 2 2 4 3 2 3 4 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Fluid Side Pressure psig 300 300 300 300 300 Water Connections in Inlet and Outlet Victaulic IPS 2 2 21 2 21 2 21 2 Drain NPT 1 2 1 2 1 2 1 2 1 2 CONDENSER 30MPW Only Weight lb empty 34 9 43 6 104 6 136 7 188 3 Net Fluid Volume gal 1 2 1 6 2 9 4 1 5 9 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Flu...

Page 6: ...kPa 3482 3482 3896 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 Water Connections in Inlet and Outlet Victaulic IPS 11 2 11 2 2 2 2 CONDENSER REFRIGERANT CONNECTIONS 30MPA Only Liquid Line ODS in 1 2 1 2 5 8 5 8 5 8 Discharge Line ODS in 13 8 13 8 13 8 15 8 15 8 CHASSIS DIMENSIONS mm Length 1397 1397 1397 1397 1397 Width 813 813 813 813 813 Height 1588 1588 1588 1588 1588 MIN...

Page 7: ...t is installed verify that mounting bolt torque is 7 to 10 ft lb 9 to 14 Nm Step 5 Make Piping Connections See Fig 8 and 9 for typical piping applications 30MPA SYSTEM CONDENSER For detailed condenser piping installation instructions for 30MPA systems refer to separate instructions packaged with the remote condenser units Condenser refrigerant piping for 30MPA units should be sized to minimize the...

Page 8: ...ques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addi tion of a holding tank to ensure adequate volume 6 A strainer with a minimum of 40 mesh must be installed within 10 ft 3 m of the evaporator fluid inlet ...

Page 9: ... of Heating Refrigerating and Air Condi tioning Engineers handbook for details on proper piping sizes and design 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addition of a holding tank to ensure adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit Double riser may be required check unit minimum capacity 7 Trap should be inst...

Page 10: ... use a brazed plate heat exchanger type condenser These heat exchangers are made of embossed plates of acid resistant stainless steel Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates forming a lattice of contact points These plates are vacuum brazed together to form a compact and pressure resistant heat exchanger After brazing the...

Page 11: ... evaporator flow switch is standard on all units This is a thermal dispersion type switch that is installed in evaporator fluid outlet The switch is set to open when the evaporator fluid flow drops below the minimum set point For variable primary flow applications it may be necessary to adjust the flow switch set point to avoid nuisance trips Con tact Carrier service engineering for the method nee...

Page 12: ...0 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM 120 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters second 1 2 3 5 4 Fig 12 Condenser Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5037 a30 5036 ...

Page 13: ... 160 170 180 190 200 Water Pressure Drop GPM 1 5 4 3 2 120 3 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Liters second 1 2 4 5 Fig 13 Evaporator Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5035 a30 5034 ...

Page 14: ...the desired slightly alkaline water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 16 during the cleaning process Filter side flow rate should be enough to filter the entire water volume every 3 to 4 hours Change filters as often as neces sary during the cleaning process d Remove temporary bypass when clea...

Page 15: ...ined for the required gpm Step 7 Make Electrical Connections All field wiring must comply with local code requirements Electrical data for the complete unit and for the compressors is shown in Table 8 See Fig 17 for field wiring connections A field supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed Control circuit power is 24 v on all unit...

Page 16: ...voltage 3 0 for unit sizes 015 020 208 230 3 60 voltages 020 040 380 3 60 voltage 030 045 460 3 60 and 575 3 60 voltages 2 AWG for unit sizes 015 380 3 60 voltage 015 020 460 3 60 and 575 3 60 voltages 3 Additional control circuit power is not required 4 Any field modification of factory wiring must be in compliance with all applicable codes Field installed power wires must be rated 75 C minimum 5...

Page 17: ...n power and control power entrance locations 5 Terminal 24 of the LVT is for control of chilled water pump CWP starter Terminal 20 of the LVT is for control of condenser pump CNP starter or condenser fan relay CFR The maximum load allowed for the relays is 5 VA sealed 10 VA inrush at 24 VAC Field power supply is not required 6 Terminal 25 of LVT is for an alarm relay The maximum load allowed for a...

Page 18: ......

Page 19: ......

Page 20: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300077 01 Printed in U S A Form 30MP 5SI Pg 20 612 11 11 Replaces 30MP 1SI Copyright 2011 Carrier Corporation ...

Reviews: