background image

15

FILLING THE SYSTEM — The  initial  fill  of  the  chilled

water system must accomplish three purposes:

1. The entire piping system must be filled with water.

2. The pressure at the top of the system must be high enough

to vent air from the system (usually 4 psig is adequate for

most vents).

3. The pressure at all points in the system must be high

enough to prevent flashing in the piping or cavitation in

the pump.

The pressure created by an operating pump affects system

pressure at all points except one, the connection of the com-

pression tank to the system. This is the only location in the sys-

tem where pump operation will not give erroneous pressure in-

dications during the fill. Therefore, the best location to install

the fill connection is close to the expansion tank. An air vent

should be installed close by to help eliminate air that enters

during the fill procedure.

Ensure the following when filling the system:

1. Remove temporary bypass piping and cleaning/flushing

equipment.

2. Check to make sure all drain plugs are installed.

3. Open the blow-down valve to flush the strainer.

Normally, a closed system needs to be filled only once. The

actual filling process is generally a fairly simple procedure. All

air should be purged or vented from the system. Thorough

venting at the high points and circulation at room temperature

for several hours is recommended.
NOTE:  Local codes concerning backflow devices and other

protection of the city water system should be consulted and

followed to prevent contamination of the public water

supply. This is especially important when antifreeze is used

in the system.
Set Water Flow Rate — Once the system is cleaned, pressur-

ized, and filled, the flow rate through the chiller needs to be

established.
NOTE: Carrier recommends a differential pressure gage when

measuring pressures across the pumps or balancing valves.

This provides for greater accuracy and reduces error build-up

that often occurs when subtracting pressures made by different

gages.

On primary/secondary systems, it is advisable to set the

30MP balancing valve to maintain design flow plus 10%

through the chiller.

A rough estimate of water flow can also be obtained from

measuring the pressure drop across the 30MP heat exchanger.

Figures 12 and 13 show the relationship between gpm (l/s) and

heat exchanger pressure drop. It should be noted that these

curves are for “clean” heat exchangers; they do not apply to

heat exchangers with fouling. Adjust the external balancing

valve until the correct pressure drop is obtained for the required

gpm.

Step 7 — Make Electrical Connections — 

 All

field wiring must comply with local code requirements.

Electrical data for the complete unit and for the compressors is

shown in Table 8. See Fig. 17 for field wiring connections. A

field-supplied branch circuit disconnect switch that can be

locked in either OPEN or OFF position 

must

 be installed.

Control circuit power is 24 v on all units. Factory-installed

control transformer (TRAN 1) uses line voltage for all units.

All control transformers are factory-installed and wired. For

208/230-3-60 units operating at 208-3-60 line voltage, TRAN1

primary connections must be moved to terminals H3 and H4.

Inside the control box are terminals for field power and

ground (earth) wiring. A ground wire must be installed with

each field power supply. Compressors are wired for across-the-

line start. Refer to Table 8 for electrical data.
FLOW SWITCH —  A condenser flow switch is available as

an accessory for all 30MPW units, and can be field-installed.

The Carrier flow switch accessory (part no. 30MP-900---004)

is available for this purpose. Flow switch wiring terminals are

located in the field wiring compartment of the control box. The

flow switch should be wired between terminals LVT-16 and

LVT-17 for all units.
CONTROL BOX, POWER SECTION — The  electrical

power supply is brought in through the top left-hand side of the

control box. Pressure-lug connections on the terminal blocks

are suitable for only for copper conductors.

The control box power section contains the following

components:
• power terminal block

• optional disconnect switch

• compressor circuit breaker(s)

• compressor contactor(s)

• current sensor boards

• control transformer

• ground lug

• neutral terminal (380-3-60 units only)

• crankcase heater relay (30MPA units only)

• fuses
CONTROL BOX, CONTROLS SECTION — The  control

box controls section contains the following components:
• main base board (MBB)

• scrolling marquee display

• optional energy management module

• control-circuit breakers for 24-v circuits

• control-circuit ON-OFF switch 

• unit Enable/Off/Remote contact switch

• unit Alarm/Alert indicator light
CONTROL BOX, FIELD CONTROL WIRING SEC-

TION —  Inside this section is the low-voltage, field-wiring

terminal strip (LVT). All low-voltage field-wiring connections

are made to this terminal block. There are three 

7

/

8

-in. (22 mm)

knockouts provided for field wiring in this section.

x

x

DILUTED

CLEANING

AGENT

S

Y

S

TEM

POT FEEDER AND
TRAN

S

FER PUMP

3

0MP UNIT

TO DRAIN

TEMPORARY
 PUMP

TEMPORARY
BYPA

SS

Fig. 15 — Typical Set Up for Cleaning Process

a30-5047

x

x

DILUTED

CLEANING

AGENT

S

Y

S

TEM

S

IDE

S

TREAM

FILTER

POT FEEDER AND
TRAN

S

FER PUMP

3

0MP UNIT

TO DRAIN

TEMPORARY
 PUMP

TEMPORARY
BYPA

SS

Fig. 16 — Cleaning Using a Side Stream Filter

a30-5048

Summary of Contents for AQUASNAP 30MPA

Page 1: ...ese installation instructions cover the 30MPA MPW units with ComfortLink controls The 30MPA units are condenserless units and the 30MPW units are all fluid cooled See Fig 1 and 2 SAFETY CONSIDERATIONS Installing starting up and servicing this equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualified installe...

Page 2: ... oil to add to the system e Carefully unsweat remaining tubing stubs when nec essary Oil can ignite when exposed to torch flame Failure to follow these procedures may result in personal injury or death CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the...

Page 3: ... TABLE FOR QTY OUT IN OPTIONAL SOUND ENCLOSURE FIELD CONNECTION 4 7 8 K O NON FUSED DISCONNECT OPTIONAL 1 4 FPT ACCESS P T ACCESS PORTS 1 4 SAE FLARE RELIEF CONNECTION POWER ENTRY WATER CONNECTIONS IN OUT 2 VICTAULIC 015 020 2 1 2 VICTAULIC 030 045 COOLER COOLER COOLER CONTROL PANEL END OPPOSITE CONTROL PANEL END MOUNTING HOLES 9 16 MOUNTING HOLES 9 16 IN OUT 040 045 TON ONLY FORK POCKETS SCROLLIN...

Page 4: ...t 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensions in are in millimeters 4 Allow 36 in 914 mm clearance on control panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option a30 5033 ...

Page 5: ... 0 8 1 2 2 4 3 2 3 4 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Fluid Side Pressure psig 300 300 300 300 300 Water Connections in Inlet and Outlet Victaulic IPS 2 2 21 2 21 2 21 2 Drain NPT 1 2 1 2 1 2 1 2 1 2 CONDENSER 30MPW Only Weight lb empty 34 9 43 6 104 6 136 7 188 3 Net Fluid Volume gal 1 2 1 6 2 9 4 1 5 9 Maximum Refrigerant Pressure psig 505 505 565 565 565 Maximum Flu...

Page 6: ...kPa 3482 3482 3896 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 Water Connections in Inlet and Outlet Victaulic IPS 11 2 11 2 2 2 2 CONDENSER REFRIGERANT CONNECTIONS 30MPA Only Liquid Line ODS in 1 2 1 2 5 8 5 8 5 8 Discharge Line ODS in 13 8 13 8 13 8 15 8 15 8 CHASSIS DIMENSIONS mm Length 1397 1397 1397 1397 1397 Width 813 813 813 813 813 Height 1588 1588 1588 1588 1588 MIN...

Page 7: ...t is installed verify that mounting bolt torque is 7 to 10 ft lb 9 to 14 Nm Step 5 Make Piping Connections See Fig 8 and 9 for typical piping applications 30MPA SYSTEM CONDENSER For detailed condenser piping installation instructions for 30MPA systems refer to separate instructions packaged with the remote condenser units Condenser refrigerant piping for 30MPA units should be sized to minimize the...

Page 8: ...ques Refer to Carrier System Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addi tion of a holding tank to ensure adequate volume 6 A strainer with a minimum of 40 mesh must be installed within 10 ft 3 m of the evaporator fluid inlet ...

Page 9: ... of Heating Refrigerating and Air Condi tioning Engineers handbook for details on proper piping sizes and design 5 See Tables 1A and 1B for minimum system fluid volume This system may require the addition of a holding tank to ensure adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit Double riser may be required check unit minimum capacity 7 Trap should be inst...

Page 10: ... use a brazed plate heat exchanger type condenser These heat exchangers are made of embossed plates of acid resistant stainless steel Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates forming a lattice of contact points These plates are vacuum brazed together to form a compact and pressure resistant heat exchanger After brazing the...

Page 11: ... evaporator flow switch is standard on all units This is a thermal dispersion type switch that is installed in evaporator fluid outlet The switch is set to open when the evaporator fluid flow drops below the minimum set point For variable primary flow applications it may be necessary to adjust the flow switch set point to avoid nuisance trips Con tact Carrier service engineering for the method nee...

Page 12: ...0 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM 120 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters second 1 2 3 5 4 Fig 12 Condenser Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5037 a30 5036 ...

Page 13: ... 160 170 180 190 200 Water Pressure Drop GPM 1 5 4 3 2 120 3 100 80 e Drop kPa 40 60 Water Pressure 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Liters second 1 2 4 5 Fig 13 Evaporator Water Pressure Drop ENGLISH SI LEGEND 1 30MP015 2 30MP020 3 30MP030 4 30MP040 5 30MP045 a30 5035 a30 5034 ...

Page 14: ...the desired slightly alkaline water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 16 during the cleaning process Filter side flow rate should be enough to filter the entire water volume every 3 to 4 hours Change filters as often as neces sary during the cleaning process d Remove temporary bypass when clea...

Page 15: ...ined for the required gpm Step 7 Make Electrical Connections All field wiring must comply with local code requirements Electrical data for the complete unit and for the compressors is shown in Table 8 See Fig 17 for field wiring connections A field supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed Control circuit power is 24 v on all unit...

Page 16: ...voltage 3 0 for unit sizes 015 020 208 230 3 60 voltages 020 040 380 3 60 voltage 030 045 460 3 60 and 575 3 60 voltages 2 AWG for unit sizes 015 380 3 60 voltage 015 020 460 3 60 and 575 3 60 voltages 3 Additional control circuit power is not required 4 Any field modification of factory wiring must be in compliance with all applicable codes Field installed power wires must be rated 75 C minimum 5...

Page 17: ...n power and control power entrance locations 5 Terminal 24 of the LVT is for control of chilled water pump CWP starter Terminal 20 of the LVT is for control of condenser pump CNP starter or condenser fan relay CFR The maximum load allowed for the relays is 5 VA sealed 10 VA inrush at 24 VAC Field power supply is not required 6 Terminal 25 of LVT is for an alarm relay The maximum load allowed for a...

Page 18: ......

Page 19: ......

Page 20: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300077 01 Printed in U S A Form 30MP 5SI Pg 20 612 11 11 Replaces 30MP 1SI Copyright 2011 Carrier Corporation ...

Reviews: