background image

GB - 2

AQUASMART Room Controller

The Room Controller Location

The Room Controller can be positioned on the unit or fitted to
the wall.

If fitted to a wall, the Room Controller must be mounted:

• In the same area where the unit is located, preferably on an

inside partitioning wall.

• Approximately 1.5 m from floor.

• On a section of wall without pipes or duct work.

General information and choosing the installation site

IMPORTANT:
Read the entire instruction manual before starting the
installation.

• For trouble-free installation, which should be carried out by a

qualified installer, follow the installation chart sequence.

• Follow all current national safety code requirements. In particular

ensure that a properly sized and connected ground wire is in place.

• After installation thoroughly test the system operation and

explain all system functions to the owner.

• Leave this manual with the owner for consultation during

future periodic maintenance.

• Dispose of packaging material in accordance with local

requirements.

• The manufacturer denies any responsibility and warranty shall

be void if these installation instructions are not observed.

• Inspect equipment for damage due to improper transportation or

handling: file an immediate claim with the shipping company.
Do not install or use damaged units.

• In case of any malfunctioning turn the unit off, disconnect the

mains power supply and contact a qualified service engineer.

Models

Products that the Room Controller can interface with

42GW

CASSETTE

42WHC/WHE

HI-WALL

42Y

FAN COIL

42JW

SATELLITE

42EL

AQUALIA

Room Controller

Power

Note that the Room Controller requires no batteries and is not
“power stealing”.  It requires 12 VDC to be connected for
proper operation, which is easily obtained from the Unit
connected to it.
The Room Controller will not operate without this connection.

If the indoor air sensor on the Room Controller has been
selected, it should NOT be mounted:

• Close to a window, on an outside wall, or next to a door

leading to the outside.

• Exposed to direct light and heat from a lamp, sun, fireplace,

or other temperature-radiating object which may cause a false
reading.

• Close to or in direct airflow of a heating or cooling supply.

• In areas with poor air circulation, such as behind a door or in

an alcove.

• Maximum of 150 m of total network wiring.

Choosing the installation site and installation

Minimum clearances

Summary of Contents for AQUASMART

Page 1: ...42GW 42WH 42Y 42JW 42EL 001 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 9001 AQUASMART Room Controller INSTALLATION MANUAL...

Page 2: ...For installation instructions of this unit refer to the relevant manuals Contents Page General information 2 Choosing the installation site 2 Installation 3 Electrical connections 4 Room controller co...

Page 3: ...se installation instructions are not observed Inspect equipment for damage due to improper transportation or handling file an immediate claim with the shipping company Do not install or use damaged un...

Page 4: ...lly at hinge to separate mounting base from remainder of the Room Controller Route the Room Controller wires through the large hole in the mounting base Level mounting base against wall for aesthetic...

Page 5: ...screws P DC Power G GROUND and C SIGNAL present on the rear base of the Room Controller P DC power G Ground C Signal Make the connections on the terminal block of the Room Controller as per diagram 2...

Page 6: ...2 will be displayed Press the DOWN button and the display will change to 1 up down up down 2 AIR SENSOR SELECTION Program if you want to use the air temperature sensor present in the Room Controller...

Page 7: ...on To perform this configuration proceed as follows Press and hold down the UP and DOWN keys at the same time for around 5 seconds Press UP button until 4 is displayed Press the MODE button to select...

Page 8: ...press any buttons for 10 seconds up down Troubleshooting 12 volts applied to Room Controller at the correct terminals and still does not operate Symptom Possible Cause Things to check Solution No LCD...

Page 9: ...nzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 16005 74 September 2001 Supersedes Order No 16005 74 Ma...

Reviews: