19MV PIC6 CFGMETER - Config Metering TABLE CONFIGURATION SHEET
19MV PIC6 SETPOINT TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Eco EXV Option
Disable/Enable
NA
Enable
Cond Liquid Level Determination
0=Capacity Percent, 1=Setpoint
0 to 1
0
Liquid level SP-Cap 0%
%
0.5
Liquid level SP-Cap 25%
%
1.0
Liquid level SP-Cap 50%
%
1.5
Liquid level SP- Cap 75%
%
2.0
Liquid level SP- Cap 100%
%
2.1
Low SST Set Point
°F
34
Eco EXV Option
Disable/Enable
Enable
Eco EXV Active Threshold
%
0
Eco Superheat SP
^F
10
EXCSV Option
Disable/Enable
Enable
EXCSV Activate Threshold
%
95
EXCSV Deactivate Threshold
%
15
EXCSV Open Time
sec
60
EXCXV Close Time
sec
120
EXCSV Open Step
5
EXCSV Close Step
5
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Cooling ECW Setpoint
15 to 120
°F
60
Cooling LCW Setpoint
–12.2 to 48.9
°F
45
Base Demand Limit
10.0 to 100.0
%
100.0
EWT Control Option
Disable/Enable
Disable