CL-5
19MV PIC6 CFGSURGE_SURGE CORRECTION CONFIG TABLE CONFIGURATION SHEET
19MV PIC6 CONF_OPT - Option CONFIG TABLE CONFIGURATION SHEET
19MV PIC6 CONFOPT2 - Option2 CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Surge Line Configuration
PR=0, Delta T=1, PR Table=2
0 to 2
2
Surge Line PR Offset%
1.5 to 7
%
3
Surge Line PR Lower DB%
0 to 4.5
%
0
Surge Line PR Upper DB%
0.2 to 4
%
2
Surge Delay Time
0 to 120
sec
15
Surge Time Period
7 to 10
min
8
Surge Delta Amps %
5 to 40
%
10
Rampdown Factor
0 to 1
0.1
GV1 Close Step Surge
1 to 3
%
2
VFD Speed Step Surge,
1 to 5
%
1.5
EC Valve Step Surge
1 to 10
%
4
Surge Profile Step
0 to 2
^F
0
Surge Profile Offset
0 to 5
^F
0
High Efficiency Mode
Disable/Enable Enable
GV Jumpover Option
Disable/Enable Disable
DTS Height Recycle Offset
0 to 3
^F
1
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Frequent Restart Option
Disable/Enable
Enable
Common Sensor Option
Disable/Enable
Disable
EXCSV Selection
0=Disable, 1=Surge,
2=Low Load, 3=Comb
0 to 3
1
EXCSV Open IGV Position
0.5 to 10
%
5
EXCSV Close IGV Position
1.5 to 20
%
10
ESCSV off DT Low Load
0.5 to 10
^F
4
EXCSV on DT Low Load
0.5 to 10
^F
2
EXCSV Low Load DB
0.5 to 2
^F
1
Head Pres Valve Option
Disable/Enable
Disable
Head Pres Delta P 0%
0 to 85
psi
25
Head Pres Delta P 100%
0 to 85
psi
50
Head Pressure Min Output
0 to 100
%
0
Head Pressure Deadband
0 to 10
psig
1
suggested value is 0
Tower Fan High Setpoint
55 to 105
^F
75
Refrig Leakage Option
Disable/Enable
Disable
Refrig Leakage Alarm mA
4 to 20
mA
20
Customer Alert Option
Disable/Enable
Enable
Ice Build Option
Disable/Enable
Disable
Evap Liquid Temp Opt
Disable/Enable
Enable
Evap App Calc Selection
0=Sat Temp, 1= Ref Temp
0 to 1
1
Cond Liquid Level Option
0=Gems225, 1=Gems3125,
2=Sporlan
0 to 2
1
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
IOB3 Option
No/Yes
No
IOB4 Option
No/Yes
No
Water Pressure Option
0=No
1=Wtr Flow PD Transducer
2=Wtr Flow PD Meter
0 to 2
0
Water Flow Measurement
0=No
1= WTR Flow Meter
2=Wtr Flow PD
0 to 2
0
Water Flow Determination
0=Sat Temp
1=Switch
2=Wtr Flow PD
0 to 2
0