AppController overview and specifications
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
2
Specifications
Driver
drv_acopen_std
Maximum number of control
programs*
2
Maximum number of
BACnet objects*
1050
* Depends on available memory
Power
24 Vac ±10%, 50
–
60 Hz
20 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
BACnet Port
For communication with the controller network using BACnet ARC156 (156 kbps)
or BACnet MS/TP (9600 bps
–
76.8 kbps)
Rnet port
Supports up to 10 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
Supplies 12 Vdc/210 mA power to the Rnet at an ambient temperature of
77°F (25°C) with a 24 Vac nominal power source.
NOTE Ambient temperature and power source fluctuations may reduce the
power supplied by the Rnet port.
NOTE
If the total power required by the sensors on the Rnet exceeds the power
supplied by the Rnet port, use an external power source. The Wireless Adapter,
Equipm
ent Touch, or TruVu™ ET Display must be powered by an external power
source. See the specifications in each device's Installation and Start-up Guide to
determine the power required.
Local Access port
For system start-up and troubleshooting using Field Assistant
Inputs
6 inputs configurable for thermistor or dry contact.
1 and 2 are also configurable for 0
–
5 Vdc sensors.
NOTES
Inputs 7 and 8 are unused.
Input 5 has a maximum temperature of 140°F (60°C).
Input resolution
10 bit A/D
Analog outputs
3 analog outputs, 0
–
10 Vdc (5 mA max)
Binary outputs
5 binary outputs, dry relay contacts rated at 1 A max. @ 24 Vac/Vdc. Configured
normally open
Output resolution
8 bit A/D, using filtered PWM
Real time clock
Battery-backed real time clock keeps track of time in the event of a power failure
Battery
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, graphics, editable
properties, schedules, and trends.