Appendix B: AHU CV (small) inputs and outputs points list
AppController
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
24
This wire list represents all the possible points for this application. The points that are actually used in your application
depend on the equipment options you select in EquipmentBuilder or Snap.
I/O
Type
I/O
Terminal
Gnd
Terminal
Point Name/
Function
Hardware/
Signal
Jumper Position of
Pins
IN-1
BI
1
2 - Gnd
Filter Status
Dry Contact
Middle
IN-2
AI
2
4 - Gnd
Supply Air Temp
10K Thermistor
Middle
IN-3
AI
3
6 - Gnd
Mixed Air Temp
10K Thermistor
Middle
IN-4
AI
4
8 - Gnd
Outdoor Air Temp
5K Thermistor
Middle
IN-5
BI
5
1 - Gnd
Freezestat
Dry Contact
Middle
IN-6
BI
6
1 - Gnd
Fan Status
Dry Contact
Middle
IN-7
Unused
IN-8
Unused
BO-1
BO
1
1 - Bus
Fan S/S
Relay
N/A
BO-2
BO
2
1 - Bus
Electric Heat stage 1
Relay
N/A
BO-3
BO
3
1 - Bus
Electric Heat stage 2
Relay
N/A
BO-4
BO
4
1 - Bus
DX stage 1
Relay
N/A
BO-5
BO
5
1 - Bus
DX Stage 2
Relay
N/A
AO-1
AO
1
2 - Gnd
Modulating OA Damper
0-10 Volt
N/A
AO-2
AO
3
4 - Gnd
Modulating HW Valve
0-10 Volt
N/A
AO-3
AO
5
6 - Gnd
Modulating CW Valve
0-10 Volt
N/A
Legend
AI
- Analog Input
AO
- Analog Output
BI
- Binary Input
BO
- Binary Output
Appendix B: AHU CV (small) inputs and outputs points list