4–39
T-368
AL70
SECONDARY SUPPLY SENSOR (SRS)
Cause:
Secondary Supply Sensor (SRS) is out of range.
Component
Secondary Supply Sensor (SRS)
Troubleshooting
Perform Pre-trip P5:
Corrective Action
If P5 passes, no further action is required.
If P5 fails, replace the defective sensor as determined by P5, refer to Tem-
perature Sensor Service
AL71
SECONDARY RETURN SENSOR (RRS)
Cause:
Secondary Return Sensor (RRS) is out of range.
Component
Secondary Return Sensor (RRS)
Troubleshooting
Perform Pre-trip P5:
Corrective Action
If P5 passes, no further action is required.
If P5 fails, replace the defective sensor as determined by P5, refer to Tem-
perature Sensor Service
AL72
CONTROL TEMP OUT OF RANGE
Cause:
After the unit goes in-range for 30 minutes then out of range for a continuous 120 minutes.
Component
Refrigeration System
Troubleshooting
Ensure unit is operating correctly.
Corrective Action
Power cycle unit.
Control Temperature is in In-range.
Any Pre-trip mode, re sets the timers
Downloaded from
Summary of Contents for 69NT40-541-505
Page 2: ...Downloaded from ManualsNet com search engine...
Page 4: ...Downloaded from ManualsNet com search engine...
Page 10: ...Downloaded from ManualsNet com search engine...
Page 14: ...Downloaded from ManualsNet com search engine...
Page 18: ...Downloaded from ManualsNet com search engine...
Page 80: ...Downloaded from ManualsNet com search engine...
Page 86: ...Downloaded from ManualsNet com search engine...
Page 92: ...Downloaded from ManualsNet com search engine...
Page 124: ...Downloaded from ManualsNet com search engine...
Page 125: ...Downloaded from ManualsNet com search engine...
Page 126: ...Downloaded from ManualsNet com search engine...
Page 142: ...Downloaded from ManualsNet com search engine...