T-368
3–6
3.2
REFRIGERATION SYSTEM DATA
* Rupture Disc, part number 14 -00215 -04 may be installed as an alternate for the receiver mounted fusible plug.
a. Compressor/Motor
Assembly
Number of Cylinders
6
Model
06DR
CFM
41
Weight (Dry)
118kg (260 lb)
Approved Oil
Castrol Icematic
Oil Charge degrees
3.6 liters (7.6 U.S. pints)
Oil Sight Glass
The oil level range, with the compressor off, should
be between the bottom and one-eighth level of the
sight glass.
b. Expansion Valve Super-
heat
Verify at -18C (0°F) container
box temperature
4.4 to 6.7°C (8 to 12°F)
c. Heater Termination
Thermostat
Opens
54° (+/
−
3) C = 130° (+/
−
5) F
Closes
38° (+/
−
4) C = 100° (+/
−
7) F
d. High Pressure Switch
Cutout
25 (+/
−
1.0) kg/cm2 = 350 (+/
−
10) psig
Cut-In
18 (+/
−
0.7) kg/cm2 = 250 (+/
−
10) psig
WARNING
!
EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal
injury and / or property damage.
Never use air or gas mixtures containing oxygen (O2) for leak testing or operating the product.
Charge Only With R
−
134a: Refrigerant must conform to AHRI Standard 700 specification.
e. Refrigerant
R
−
134a
Conforming to AHRI standard 700 specifications.
f. Refrigerant Charge
Unit Configuration
Charge Requirements
−
R-134a
Receiver
3.3 kg (7.3 lbs)
NOTE
When replacing components (g.) and (h.), refer to installation instructions included with replacement
part.
g. Fusible Plug, Receiver*
Melting point
99°C = (210°F)
Torque*
6.2 to 6.9mkg (45 to 50ft-lbs)
h. Sight Glass/Moisture In-
dicator
Torque
8.9 to 9.7mkg (65 to 70ft-lbs)
i. Condenser Pressure
Transducer
Condenser Fan Starts
Condenser fan will start if condenser pressure is
greater than 14.06kg/cm2 (200psig) OR the con-
denser fan is OFF for more than 60 seconds.
Condenser Fan Stops
Condenser fan will stop if condenser pressure is less
than 9.14kg/cm2 (130psig) AND the condenser fan
remains ON for at least 30 seconds.
j. Unit Weight
Refer to unit model number plate.
Downloaded from
Summary of Contents for 69NT40-541-505
Page 2: ...Downloaded from ManualsNet com search engine...
Page 4: ...Downloaded from ManualsNet com search engine...
Page 10: ...Downloaded from ManualsNet com search engine...
Page 14: ...Downloaded from ManualsNet com search engine...
Page 18: ...Downloaded from ManualsNet com search engine...
Page 80: ...Downloaded from ManualsNet com search engine...
Page 86: ...Downloaded from ManualsNet com search engine...
Page 92: ...Downloaded from ManualsNet com search engine...
Page 124: ...Downloaded from ManualsNet com search engine...
Page 125: ...Downloaded from ManualsNet com search engine...
Page 126: ...Downloaded from ManualsNet com search engine...
Page 142: ...Downloaded from ManualsNet com search engine...