background image

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness and check

lubrication each heating and cooling season. Clean when
necessary.

4. Check electrical connections for tightness and controls for

proper operation each heating and cooling season. Service
when necessary.

AIR FILTER

IMPORTANT:

Never operate the unit without a suitable air filter

in the return-air duct system. Always replace the filter with the
same dimensional size and type as originally installed (See Tables
1 for recommended filter sizes).

Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and lint.

EVAPORATOR BLOWER AND MOTOR

NOTE:

All motors are prelubricated. Do not attempt to lubricate

these motors.

For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.

Disconnect and tag electrical power to the unit before
cleaning the blower motor and wheel. Failure to adhere to this
warning could cause serious injury or death.

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. Disconnect motor lead from blower relay (BR). Disconnect

yellow lead from terminal L2 of the contactor.

c. On all units remove blower assembly from unit. Remove

screws securing blower to blower partition and slide
assembly out. Be careful not to tear insulation in blower
compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft,

remove screws that secure motor mount brackets to hous-
ing, and slide motor and motor mount out of housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights (clips)
on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush attach-
ment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are

tightened on motor shaft flats and not on round part of
shaft.

f. Reinstall unit access panel.

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during heating and
cooling cycles.

CONDENSER COIL, EVAPORATOR COIL, AND CONDEN-
SATE DRAIN PAN

Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent-and-water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.

Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
‘‘plumbers snake’’ or similar probe device. Ensure that the
auxiliary drain port above the drain tube is also clear.

CONDENSER FAN

Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit. Damage to unit may result.

4. Remove 6 screws holding condenser grille and motor to top

cover.

5. Turn motor/grille assembly upside down on top cover to

expose the fan blade.

6. Inspect the fan blades for cracks or bends.

7. If fan needs to be removed, loosen the setscrew and slide the

fan off the motor shaft.

8. When replacing fan blade, position blade so that the hub is 1/8

in. away from the motor end ( 1/8 in. of motor shaft will be
visible).

9. Ensure that setscrew engages the flat area on the motor shaft

when tightening.

10. Replace grille.

ELECTRICAL CONTROLS AND WIRING — Inspect and check
the electrical controls and wiring annually.

Be sure to turn off the

electrical power to the unit.

Remove access panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connections are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.

After inspecting the electrical controls and wiring, replace the
access panel. Start the unit, and observe at least one complete
heating cycle and one complete cooling cycle to ensure proper
operation. If discrepancies are observed in either or both operating

16

Summary of Contents for 50GL030

Page 1: ...n working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glass...

Page 2: ...n on sides of the unit Do not secure the unit to the slab except when required by local codes GROUND LEVEL If local codes permit the unit can be placed directly on the ground Prepare a level gravel fo...

Page 3: ...6 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED REQ D CLEARANCES TO COMBUSTIBLE MAT L IN MM TOP O...

Page 4: ...0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 00 304 8 FROM...

Page 5: ...N MM D IN MM ROOF CURB 030 036 CPRFCURB006A00 8 203 11 27 32 301 30 5 8 778 28 3 4 730 CPRFCURB007A00 14 356 11 27 32 301 30 5 8 778 28 3 4 730 042 060 CPRFCURB008A00 8 203 15 27 32 402 42 1 8 1070 40...

Page 6: ...e pan from overflowing See Fig 8 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the out...

Page 7: ...Air Conditioning Engineers ASHRAE recommen dations 9 Use flexible transition between rigid ductwork and unit to prevent transmission of vibration The transition may be screwed or bolted to duct flang...

Page 8: ...BLOWER Nominal Airflow Cfm Size in Motor hp 1000 10x10 1 4 1200 10x10 1 2 1400 11x10 3 4 1600 11x10 3 4 1750 11x10 1 HIGH PRESSURE SWITCH psig Cutout Reset Auto 610 15 420 25 LOSS OF CHARGE LOW PRESSU...

Page 9: ...compressor SPECIAL PROCEDURES FOR 208 V OPERATION Make sure that the power supply to the unit is switched OFF before making any wiring changes With disconnect switch open move yellow wire from transfo...

Page 10: ...0 62 0 0 9 3 2 5 0 10 0 15 0 20 0 6 0 12 0 18 0 24 1 15 4 15 4 19 0 26 6 34 1 20 20 20 30 35 Heater capacity KW based on heater voltage of 208v 240v 480v If power distribution voltage to unit varies f...

Page 11: ...us loose parts have been removed START UP CHECK FOR REFRIGERANT LEAKS Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that refrigerant sys...

Page 12: ...Fig 13 208 230 3 60 Wiring Diagram C00061 208 230 3 30 12...

Page 13: ...Fig 14 460 3 60 Wiring Diagram C00062 13...

Page 14: ...al power to the unit before changing blower speed Electrical shock can cause serious injury or death Airflow can be changed by changing the lead connections of the blower motor All 50GL units are fact...

Page 15: ...5 0 6 0 7 0 8 0 9 1 0 30 Low Watts 246 244 243 241 Cfm 910 806 749 680 Med Watts 343 339 336 332 328 322 317 Cfm 1148 1104 1028 958 850 782 645 High Watts 441 432 421 410 400 Cfm 1102 988 896 783 529...

Page 16: ...nit and check for proper blower rotation and motor speeds during heating and cooling cycles CONDENSER COIL EVAPORATOR COIL AND CONDEN SATE DRAIN PAN Inspect the condenser coil evaporator coil and cond...

Page 17: ...nst excessive con denser coil pressure It opens at 610 psig High pressure may be caused by a dirty condenser coil failed fan motor or condenser air recirculation To check switch 1 Turn off all power t...

Page 18: ...3 1172 SUCTION LINE PRESSURE KILOPASCALS SUCTION LINE PRESSURE PSIG 20 0 7 27 21 16 10 4 1 80 0 70 0 60 0 50 0 40 0 30 0 042 60 Hz CHARGING CHART FOR USE WITH UNITS USING R410A REFRIGERANT OUTDOOR TEM...

Page 19: ...ocal codes LIQUID LINE FILTER DRIER The filter drier is specifically designed to operate with Puron Use only factory authorized components Filter drier must be replaced whenever the refrigerant system...

Page 20: ...hoses with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture...

Page 21: ...tage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat...

Page 22: ...___ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Condenser Air Temperature __________ DB Return Air Temperature __________ DB __________ WB Cooling Supply Air __________ DB __________ WB...

Reviews: