background image

cycles, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.

NOTE:

Refer to the heating and/or cooling sequence of operation

in this publication as an aid in determining proper control
operation.

REFRIGERANT CIRCUIT — Inspect all refrigerant tubing con-
nections and the unit base for oil accumulations annually. Detect-
ing oil generally indicates a refrigerant leak.

System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal to avoid
serious injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak-detector,
halide torch, or liquid-soap solution. If a refrigerant leak is
detected, refer to Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low cooling performance is
suspected, refer to Checking and Adjusting Refrigerant Charge
section.

EVAPORATOR AIRFLOW — The heating and/or cooling air-
flow does not require checking unless improper performance is
suspected.

If a problem exists, be sure that all supply- and

return-air grilles are open and free from obstructions, and that the
air filter is clean.

When necessary, refer to Indoor Airflow and

Airflow Adjustments section to check the system airflow.

METERING DEVICE—ACCURATOR® PISTON — This me-
tering device is a fixed orifice and is contained in the brass
hex-body in the liquid line.

PRESSURE SWITCHES — Pressure switches are protective de-
vices wired into control circuit (low voltage). They shut off
compressor if abnormally high or low pressures are present in the
refrigeration circuit. These pressure switches are specifically
designed to operate with Puron (R-410A) systems. R-22 pressure
switches

must not

be used as replacements for the Puron (R-

410A) air conditioner.

LOSS OF CHARGE/LOW-PRESSURE SWITCH (AIR CONDI-
TIONER ONLY) — This switch is located on the liquid line and
protects against low suction pressures caused by such events as
loss of charge, low airflow across indoor coil, dirty filters, etc. It
opens on a pressure drop at about 20 psig. If system pressure is
above this, switch should be closed.

To check switch:

1. Turn off all power to unit.

2. Disconnect leads on switch.

3. Apply ohmeter leads across switch. You should have conti-

nuity on a good switch.

NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gages read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

HIGH-PRESSURE SWITCH — The high-pressure switch is lo-
cated in the discharge line and protects against excessive con-
denser coil pressure. It opens at 610 psig.

High pressure may be caused by a dirty condenser coil, failed fan
motor, or condenser air recirculation.

To check switch:

1. Turn off all power to unit.

2. Disconnect leads on switch.

3. Apply ohmeter leads across switch. You should have conti-

nuity on a good switch.

COPELAND SCROLL COMPRESSOR (PURON REFRIGER-
ANT —

The compressor used in this product is specifically

designed to operate with Puron (R-410A) refrigerant and
cannot be interchanged.

The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power
should be shut off, if possible, for most troubleshooting tech-
niques. Refrigerants present additional safety hazards.

Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger-
ants and oils. Failure to follow this warning can cause a fire,
serious injury, or death.

The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an anti-rotational
device and an internal pressure relief port. The anti-rotational
device prevents the scroll from turning backwards and replaces the
need for a cycle protector. The pressure relief port is a safety
device, designed to protect against extreme high pressure. the
relief port has an operating range between 550 and 625 psi
differential pressure.

The Copeland scroll compressor uses Mobil 3MA POE oil.
This is the only oil allowed for oil recharge.

REFRIGERANT SYSTEM

REFRIGERANT

This system uses Puron® (R-410A) refrigerant which has
higher operating pressures than R-22 and other refrigerants.
No other refrigerant may be used in this system. Gage set,
hoses, and recovery system must be designed to handle
Puron. If you are unsure consult the equipment manufacturer.
Failure to use Puron compatible servicing equipment or
replacement components may result in property damage or
injury.

COMPRESSOR OIL — The compressor in this system uses a
polyolester (POE) oil, Mobil 3MA POE. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can
absorb 15 times as much water as other oils designed for HCFC
and CFC refrigerants. Take all necessary precautions to avoid
exposure of the oil to the atmosphere.

SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC MA-
TERIALS — POE (polyolester) compressor lubricants are known
to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause embrittle-
ment (leading to cracking) to occur in one year or more. When
performing any service that may risk exposure of compressor oil to
the roof, take appropriate precautions to protect roofing. Proce-
dures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch, me-
tering device, coil, accumulator, or reversing valve.

17

Summary of Contents for 50GL030

Page 1: ...n working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glass...

Page 2: ...n on sides of the unit Do not secure the unit to the slab except when required by local codes GROUND LEVEL If local codes permit the unit can be placed directly on the ground Prepare a level gravel fo...

Page 3: ...6 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED REQ D CLEARANCES TO COMBUSTIBLE MAT L IN MM TOP O...

Page 4: ...0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 00 304 8 FROM...

Page 5: ...N MM D IN MM ROOF CURB 030 036 CPRFCURB006A00 8 203 11 27 32 301 30 5 8 778 28 3 4 730 CPRFCURB007A00 14 356 11 27 32 301 30 5 8 778 28 3 4 730 042 060 CPRFCURB008A00 8 203 15 27 32 402 42 1 8 1070 40...

Page 6: ...e pan from overflowing See Fig 8 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the out...

Page 7: ...Air Conditioning Engineers ASHRAE recommen dations 9 Use flexible transition between rigid ductwork and unit to prevent transmission of vibration The transition may be screwed or bolted to duct flang...

Page 8: ...BLOWER Nominal Airflow Cfm Size in Motor hp 1000 10x10 1 4 1200 10x10 1 2 1400 11x10 3 4 1600 11x10 3 4 1750 11x10 1 HIGH PRESSURE SWITCH psig Cutout Reset Auto 610 15 420 25 LOSS OF CHARGE LOW PRESSU...

Page 9: ...compressor SPECIAL PROCEDURES FOR 208 V OPERATION Make sure that the power supply to the unit is switched OFF before making any wiring changes With disconnect switch open move yellow wire from transfo...

Page 10: ...0 62 0 0 9 3 2 5 0 10 0 15 0 20 0 6 0 12 0 18 0 24 1 15 4 15 4 19 0 26 6 34 1 20 20 20 30 35 Heater capacity KW based on heater voltage of 208v 240v 480v If power distribution voltage to unit varies f...

Page 11: ...us loose parts have been removed START UP CHECK FOR REFRIGERANT LEAKS Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that refrigerant sys...

Page 12: ...Fig 13 208 230 3 60 Wiring Diagram C00061 208 230 3 30 12...

Page 13: ...Fig 14 460 3 60 Wiring Diagram C00062 13...

Page 14: ...al power to the unit before changing blower speed Electrical shock can cause serious injury or death Airflow can be changed by changing the lead connections of the blower motor All 50GL units are fact...

Page 15: ...5 0 6 0 7 0 8 0 9 1 0 30 Low Watts 246 244 243 241 Cfm 910 806 749 680 Med Watts 343 339 336 332 328 322 317 Cfm 1148 1104 1028 958 850 782 645 High Watts 441 432 421 410 400 Cfm 1102 988 896 783 529...

Page 16: ...nit and check for proper blower rotation and motor speeds during heating and cooling cycles CONDENSER COIL EVAPORATOR COIL AND CONDEN SATE DRAIN PAN Inspect the condenser coil evaporator coil and cond...

Page 17: ...nst excessive con denser coil pressure It opens at 610 psig High pressure may be caused by a dirty condenser coil failed fan motor or condenser air recirculation To check switch 1 Turn off all power t...

Page 18: ...3 1172 SUCTION LINE PRESSURE KILOPASCALS SUCTION LINE PRESSURE PSIG 20 0 7 27 21 16 10 4 1 80 0 70 0 60 0 50 0 40 0 30 0 042 60 Hz CHARGING CHART FOR USE WITH UNITS USING R410A REFRIGERANT OUTDOOR TEM...

Page 19: ...ocal codes LIQUID LINE FILTER DRIER The filter drier is specifically designed to operate with Puron Use only factory authorized components Filter drier must be replaced whenever the refrigerant system...

Page 20: ...hoses with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture...

Page 21: ...tage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat...

Page 22: ...___ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Condenser Air Temperature __________ DB Return Air Temperature __________ DB __________ WB Cooling Supply Air __________ DB __________ WB...

Reviews: