background image

NOTE:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper R-410A
charge. The charging label and the tables shown refer to system
temperatures and pressures.

A refrigerant charging chart label is attached to the outside of the
compressor access door. The chart includes the required suction
line temperature at given suction line pressures and outdoor
ambients.

An accurate superheat, thermocouple- or thermistor-type ther-
mometer, a sling psychrometer, and a gage manifold are required
when using the superheat charging method for evaluating the unit
charge.

Do not use mercury or small dial-type thermometers

because they are not adequate for this type of measurement.

IMPORTANT:

When evaluating the refrigerant charge, an indi-

cated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as insuf-
ficient airflow across either coil or both coils.

Refrigerant charge

The amount of refrigerant charge is listed on the unit nameplate.
Refer to the Refrigeration Service Techniques Manual, Refriger-
ants section.

Unit panels must be in place when unit is operating during
charging procedures.

No charge

Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to system data
plate).

Low charge cooling

Measure outdoor ambient using Cooling Charging Charts (Figs.
15-19). Vary refrigerant until the conditions of the chart are met.
Note that charging charts are different from type normally used.
Charts are based on charging the units to correct superheat for the
various operating conditions. Accurate pressure gage and tempera-
ture sensing devices are required. Connect the pressure gage to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that the outdoor
ambient does not effect the reading. Indoor air CFM must be
within the normal operating range of the unit.

To use cooling charging charts

Take the outdoor ambient temperature and read the suction
pressure gage. Refer to the chart to determine what the suction
temperature should be.

NOTE:

If the problem causing the inaccurate readings is a

refrigerant leak, refer to Check for Refrigerant Leaks section.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

For cooling operation, the recommended airflow is 350 to 450
cfm for each 12,000 Btuh of rated cooling capacity.

Table 4 shows cooling airflows at various external static pressures.
Refer to these tables to determine the airflow for the system being
installed.

NOTE:

Be sure that all supply- and return-air grilles are open,

free from obstructions, and adjusted properly.

Disconnect electrical power to the unit before changing
blower speed. Electrical shock can cause serious injury or
death.

Airflow can be changed by changing the lead connections of the
blower motor.

All 50GL units are factory wired for low speed and may need to be
wired for medium or high speed in the field.

FOR 208/230-V — The motor leads are color-coded as follows:

3-SPEED

2-SPEED

black = high speed

black = high speed

blue = medium speed

-

red = low speed

red = low speed

To change the speed of the blower motor (BM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to terminal BM for 3-phase units. To change the speed,
remove and replace with lead for desired blower motor speed.

Insulate the removed lead to avoid contact with chassis parts.

FOR 460-V GE MOTORS — The motor leads are color coded as
follows:

3-SPEED

2-SPEED

black = high

black = high

violet = jumper

blue = jumper

orange = medium

-

red = low

red = low

To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay (BR) and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM. For low and medium speeds black must
be connected to the jumper wire.

Insulate removed lead end to

avoid contact with chassis parts.

To select high speed on 460-v GE

motors, separate the black female quick connect (QC) from the
jumper lead male quick connect (QC) and connect the black lead
to the BR. Insulate the jumper to avoid contact with any chassis
parts.

COOLING SEQUENCE OF OPERATION — With the room
thermostat SYSTEM switch in the COOL position and the FAN
switch in the AUTO position, the cooling sequence of operation is
as follows:

When the room temperature rises to a point that is slightly above
the cooling control setting of the thermostat, the thermostat
completes the circuit between thermostat terminal R to terminals Y
and G. These completed circuits through the thermostat connect
contactor coil (C) (through unit wire Y) and blower relay coil
(TDR) (through unit wire G) across the 24-v secondary of
transformer (TRAN).

The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to con-
denser (outdoor) fan motor (OFM). Both motors start instantly.

The set of normally open contacts of energized relay TDR close
and complete the circuit through evaporator blower (indoor) fan
motor (IFM).

NOTE:

Once the compressor has started and then has stopped, it

should not be started again until 5 min have elapsed.

The cooling cycle remains ‘‘on’’ until the room temperature drops
to point that is slightly below the cooling control setting of the
room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit
between thermostat terminal R to terminals Y and G. These open
circuits deenergize contactor coil C and relay coil TDR. The
condenser and compressor motors stop. After a 30-sec delay, the
blower motor stops. The unit is in a ‘‘standby’’ condition, waiting
for the next ‘‘call for cooling’’ from the room thermostat.

14

Summary of Contents for 50GL030

Page 1: ...n working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glass...

Page 2: ...n on sides of the unit Do not secure the unit to the slab except when required by local codes GROUND LEVEL If local codes permit the unit can be placed directly on the ground Prepare a level gravel fo...

Page 3: ...6 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED REQ D CLEARANCES TO COMBUSTIBLE MAT L IN MM TOP O...

Page 4: ...0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 00 304 8 FROM...

Page 5: ...N MM D IN MM ROOF CURB 030 036 CPRFCURB006A00 8 203 11 27 32 301 30 5 8 778 28 3 4 730 CPRFCURB007A00 14 356 11 27 32 301 30 5 8 778 28 3 4 730 042 060 CPRFCURB008A00 8 203 15 27 32 402 42 1 8 1070 40...

Page 6: ...e pan from overflowing See Fig 8 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the out...

Page 7: ...Air Conditioning Engineers ASHRAE recommen dations 9 Use flexible transition between rigid ductwork and unit to prevent transmission of vibration The transition may be screwed or bolted to duct flang...

Page 8: ...BLOWER Nominal Airflow Cfm Size in Motor hp 1000 10x10 1 4 1200 10x10 1 2 1400 11x10 3 4 1600 11x10 3 4 1750 11x10 1 HIGH PRESSURE SWITCH psig Cutout Reset Auto 610 15 420 25 LOSS OF CHARGE LOW PRESSU...

Page 9: ...compressor SPECIAL PROCEDURES FOR 208 V OPERATION Make sure that the power supply to the unit is switched OFF before making any wiring changes With disconnect switch open move yellow wire from transfo...

Page 10: ...0 62 0 0 9 3 2 5 0 10 0 15 0 20 0 6 0 12 0 18 0 24 1 15 4 15 4 19 0 26 6 34 1 20 20 20 30 35 Heater capacity KW based on heater voltage of 208v 240v 480v If power distribution voltage to unit varies f...

Page 11: ...us loose parts have been removed START UP CHECK FOR REFRIGERANT LEAKS Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that refrigerant sys...

Page 12: ...Fig 13 208 230 3 60 Wiring Diagram C00061 208 230 3 30 12...

Page 13: ...Fig 14 460 3 60 Wiring Diagram C00062 13...

Page 14: ...al power to the unit before changing blower speed Electrical shock can cause serious injury or death Airflow can be changed by changing the lead connections of the blower motor All 50GL units are fact...

Page 15: ...5 0 6 0 7 0 8 0 9 1 0 30 Low Watts 246 244 243 241 Cfm 910 806 749 680 Med Watts 343 339 336 332 328 322 317 Cfm 1148 1104 1028 958 850 782 645 High Watts 441 432 421 410 400 Cfm 1102 988 896 783 529...

Page 16: ...nit and check for proper blower rotation and motor speeds during heating and cooling cycles CONDENSER COIL EVAPORATOR COIL AND CONDEN SATE DRAIN PAN Inspect the condenser coil evaporator coil and cond...

Page 17: ...nst excessive con denser coil pressure It opens at 610 psig High pressure may be caused by a dirty condenser coil failed fan motor or condenser air recirculation To check switch 1 Turn off all power t...

Page 18: ...3 1172 SUCTION LINE PRESSURE KILOPASCALS SUCTION LINE PRESSURE PSIG 20 0 7 27 21 16 10 4 1 80 0 70 0 60 0 50 0 40 0 30 0 042 60 Hz CHARGING CHART FOR USE WITH UNITS USING R410A REFRIGERANT OUTDOOR TEM...

Page 19: ...ocal codes LIQUID LINE FILTER DRIER The filter drier is specifically designed to operate with Puron Use only factory authorized components Filter drier must be replaced whenever the refrigerant system...

Page 20: ...hoses with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture...

Page 21: ...tage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat...

Page 22: ...___ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Condenser Air Temperature __________ DB Return Air Temperature __________ DB __________ WB Cooling Supply Air __________ DB __________ WB...

Reviews: