7.7 -
Humidifier (option)
The immersed-electrode humidifier is fitted with a microprocessor-based controller that adapts, within the allowable operating limits,
to the physical and chemical properties of the water used.
Voltage is applied to the electrodes immersed in the water; an electrical current passes between them, heating the water to boiling
point.
The water acts as an electrical resistance, ensuring continuity between the electrodes and a minimum of dissolved salts.
Unit W
X unit
W5/8/12
X 5/8/10
W 16/27
X 12/15/19/24/31/36/38/48
Make/model
KUE T1 COW21
KUE T2 COW21
Control voltage
V
24
24
Absorbed power in control circuit
Without 9 V A valve
With 35 V A valve
High power circuit voltage
3-PH/400 V
3-PH/400 V
Power circuit current
A
3,2
8,7
Protection rating
A
10
16
Max. steam flow rate
kg/h
3
8
Maximum power
kW
2,25
6
Factory steam flow rate setting
kg/h
W 5/X 5 :
1.5
W 8/X 8 :
1.9
W 12/X 10 :
2.4
W 16/X 12/15 :
3.9
W 27/X 19/24 :
5.7
X 31/36 :
7.7
X 38/48 :
8.0
Factory power setting
kW
W 5/X 5 :
1.13
W 8/X 8 :
1.45
W 12/X 10 :
1.80
W 16/X 12/15 :
2.88
W 27/X 19/24 :
4.32
X 31/36 :
5.75
X 38/48 :
6.00
Water supply pressure
bar
1 to 10
Max. water supply flow rate
l/min
0,6
1,2
Conductivity of supply water
µS/cm
350 to 1250
Hardness of supply water
TH in mg/l
CaC03
100 to 400
Drain water flow rate
l/min
10
Water supply Ø
G 3/4 M
Drain Ø
32 M
Weight
kg
2
3.3
If a water softener or water treatment system is used, the water hardness should not be less than 40% of the initial hardness and
should never be less than 15°F. (TH = 150 mg/l CaC03)
7 - TECHNICAL CHARACTERISTICS