7 - TECHNICAL CHARACTERISTICS
7.1 - Filters
EN 779-2012 efficiency:
M5
ISO16890 efficiency:
ePM10 50%
Thickness: 48 mm.
Efficiency: 90% gravimetric
Filter area: 2 x the face area
Fire rating: M1.
EN 779-2012 efficiency: F7
ISO16890 efficiency: ePM1 60%
Thickness: 48 mm
Efficiency: 85% opacimetric
Filter area: 17 x face area with a thickness of 48 mm
Fire rating: M1
Unit W
X unit
W5
X5
W8
X8
W12
X10
W16
X 12/15
W27
X 19/24
X 31/36
X 38/48
Dimensions
508 x 465
604 x 465
700 x 465
945 x 565
945 x 400
945 x 565
945 x 500
Number
1
1
1
1
2
2
4
■
Pressure drops - clean filters
Unit W
X unit
W5
X5
W8
X8
W12
X10
W16
X 12/15
W27
X 19/24
X 31/36
X 38/48
Nominal flow rate (m³/h)
1 300
2 000
2 500
4 000
6 000
8 000
12 000
∆P (Pa)
M5/ePM10 50%
33
49
55
53
58
53
58
∆P (Pa) F7/ePM1-60%
35
53
59
57
63
57
63
∆P (Pa)
M5+F7(ePM10 50%+ePM1 60%)
-
-
-
110
121
110
121
Filter fouling is measured by a pressure sensor located in the electrics box.
It is set to 1.5 times the pressure drop value for the filter when clean (pressure tapping upstream and downstream of the filter).
7.2 - Cooling coil:
Note
: make sure that the chilled water supply pipes are insulated.
Moderately tighten the coil supply connections to avoid damaging the manifolds.
■
Coil specifications
Unit W
W5
W8
W12
W16
W27
Coil
specifications
Rated water flow rate
(1)
m³/h
1,1
1,4
1,67
2,57
3,7
Capacity (I)
2,2
2,74
3,87
9,2
13,1
Valve
specifications
KV valve
1,6
2,5
4
4
10
∆Pmax (Pa) 2-way valve
1200
400
400
600
600
∆Pmax (Pa) 3-way valve
250
100
240
600
600
(1) Return air conditions 24°C RH 50%, water temperature 7/12 °C
NOTE: Refer to your temperature range selection sheet for the technical information (capacity, water flow, water flow rates,
pressure drops, etc.).
52