22 - ELECTRICAL SPECIFICATIONS
CL2
28
35
50
65
75
Compressor
Voltage
400 V - 3 Ph - 50 Hz
Maximum current
A
6,9
8,0
10,3
15,0
15,0
Fans
Maximum current
A
0,46
0,97
0,92
1,94
Rated voltage of unit
V
400 V - 3 Ph+N - 50 Hz
Total current
A
7,5
9,0
11,3
17,0
17,0
Starting current
A
38
43
65,5
75,5
102,5
Electrical cables not supplied*
mm²
5G1,5
5G2,5
5G4
5G6
5G6
Recommended rating
for the proximity switch
Am
10
16
20
20
* Cable with 2 or 3 charged conductors in a raceway or duct, exposed mounting, for temperatures below 60°C and a maximum length of 30 m.
Note:
For different conditions, refer to the current standard in the country of installation (example for France: NFC 15-100).