background image

26

PRESSURE SWITCHES
Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or

low pressures are present in the refrigeration circuit. These
pressure switches are specifically designed to operate with Puron

(R--410A) systems. R--22 pressure switches must not be used as

replacements for the Puron (R--410A) system.
LOSS OF CHARGE SWITCH

This switch is located on the liquid line and protects against low

suction pressures caused by such events as loss of charge, low

airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch

should be closed. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

NOTE

: Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device
for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover
all system charge so that pressure gauges read 0 psi. Never open
system without breaking vacuum with dry nitrogen.
HIGH--PRESSURE SWITCH

The high--pressure switch is located in the discharge line and

protects against excessive condenser coil pressure. It opens at 650

psig.
High pressure may be caused by a dirty outdoor coil, failed fan

motor, or outdoor air recirculation. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

COPELAND SCROLL COMPRESSOR (PURON REFRIGER-
ANT)
The compressor used in this product is specifically designed to
operate with Puron (R--410A) refrigerant and cannot be

interchanged.
The compressor is an electrical (as well as mechanical) device.

Exercise extreme caution when working near compressors. Power
should be shut off, if possible, for most troubleshooting

techniques. Refrigerants present additional safety hazards.

FIRE/EXPLOSION HAZARD

Failure to follow this warning could result in personal injury

or death and/or property damage.
Wear safety glasses and gloves when handling refrigerants.

Keep torches and other ignition sources away from

refrigerants and oils.

!

WARNING

The scroll compressor pumps refrigerant throughout the system

by the interaction of a stationary and an orbiting scroll. The scroll

compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and

flooded starts. The compressor is equipped with an
anti--rotational device and an internal pressure relief port. The

anti--rotational device prevents the scroll from turning backwards
and replaces the need for a cycle protector. The pressure relief

port is a safety device, designed to protect against extreme high

pressure. The relief port has an operating range between 550
(26.34 kPa) and 625 psi (29.93 kPa) differential pressure.

The Copeland scroll compressor uses Mobil 3MAF POE oil.
Copeland Ultra 22 CC should be used if additional oil is needed

in the field. Mobil Arctic EAL22CC or ICI Emkarate RL22 or
32CF oil may be used to recharge these compressors if Ultra 22 is

not available.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
This system uses Puron (R--410A) refrigerant which has

higher operating pressures than R--22 and other refrigerants.

No other refrigerant may be used in this system. Gauge set,

hoses, and recovery system must be designed to handle Puron.

If you are unsure, consult the equipment manufacturer.

WARNING

!

REFRIGERANT SYSTEM
This information covers the refrigerant system of the 48ES,
including the compressor oil needed, servicing systems on roofs

containing synthetic materials, the filter drier and refrigerant
charging.
Compressor Oil
The compressor in this system uses a polyolester (POE) oil,
Mobil 3MAF POE. This oil is extremely hygroscopic, meaning it

absorbs water readily. POE oils can absorb 15 times as much
water as other oils designed for HCFC and CFC refrigerants.

Take all necessary precautions to avoid exposure of the oil to the

atmosphere.
SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC-
MATERIALS
POE (polyolester) compressor lubricants are known to cause long
term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause

embrittlement (leading to cracking) to occur in one year or more.
When performing any service that may risk exposure of

compressor oil to the roof, take appropriate precautions to protect
roofing. Procedures which risk oil leakage include, but are not

limited to, compressor replacement, repairing refrigerant leaks,

replacing refrigerant components such as filter drier, pressure
switch, metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure

1. Cover extended roof working area with an impermeable

polyethylene (plastic) drip cloth or tarp. Cover an

approximate 10 X 10 ft. area.

2. Cover area in front of the unit service panel with a terry

cloth shop towel to absorb lubricant spills and prevent
run--offs, and protect drop cloth from tears caused by tools

or components.

3. Place terry cloth shop towel inside unit immediately under

component(s) to be serviced and prevent lubricant

run--offs through the louvered openings in the unit base.

4. Perform required service.
5. Remove and dispose of any oil contaminated material per

local codes.

LIQUID LINE FILTER DRIER
This filter drier is specifically designed to operate with Puron.
Use only factory--authorized components. Filter drier must be

replaced whenever the refrigerant system is opened. When

removing a filter drier, use a tubing cutter to cut the drier from the
system. Do not unsweat a filter drier from the system. Heat from

unsweating will release moisture and contaminants from drier
into system.

48E

S

Summary of Contents for 48ES

Page 1: ...Start Up Cooling Make Adjustments 18 Checking Cooling Control Operation 18 Checking Adjusting Refrigerant Charge 18 Indoor Airflow and Airflow Adjustments 19 Cooling Sequence of Operation 19 MAINTENAN...

Page 2: ...t for shipping damage while unit is still on shipping pallet If unit appears to be damaged or is torn loose from its anchorage have it examined by transportation inspectors before removal Forward clai...

Page 3: ...UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 LEGEND CG Center of Gravity COND Condensor EVAP Evaporator...

Page 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 LEGEN...

Page 5: ...eck pan Short Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 48ES018 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8...

Page 6: ...eered and designed to be installed only on Small Packaged Products This bracket is to be used to rig lift a Small Packaged Product onto roofs or other elevated structures Prior to initial use and at m...

Page 7: ...Size in 20x24x1 508x610x25 mm 24x30x1 610x762x25 mm 24x36x1 610x914x25 mm Table 1 Physical Data Con t Unit 48ES UNIT SIZE 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY ton 4 4 4 5 5 5 OPE...

Page 8: ...sure that the outlet of the trap is at least 1 in 25 4 mm lower than the drain pan condensate connection to prevent the pan from overflowing See Fig 7 Prime the trap with water When using agravel apro...

Page 9: ...joint when making pipe connections Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and or national codes Never use Teflon tape 4 Install sediment tra...

Page 10: ...nd power up unit NOTE The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence type air conditioning and ventilating systems...

Page 11: ...when the standard power and low voltage entry points are used See Fig 3 and 4 for acceptable location See unit wiring label and Fig 11 for reference when making high voltage connections Proceed as fol...

Page 12: ...rate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured 3 Do not remove compressor terminal cover until all electrical sources are disconnected a...

Page 13: ...e Refer to unit rating plate for required charge Step 2 Start up Heating and Make Adjustments Complete the required procedures given in the Pre Start Up section before starting the unit Do not jumper...

Page 14: ...h only a minor change in the manifold pressure is required Observe manifold pressure and proceed as follows to adjust gas input 1 Removecoverscrewoverregulatoradjustmentscrew ongas valve 2 Turn regula...

Page 15: ...15 A07230 Fig 15 208 230 1 60 Wiring Diagram 48ES...

Page 16: ...16 A07232 Fig 16 208 230 3 60 Wiring Diagram 48ES...

Page 17: ...17 A07231 Fig 17 460 3 60 Wiring Diagram 48ES...

Page 18: ...e rollout switch reaches the maximum allowable temperature the control circuit trips closing the gas valve and stopping gas flow to the burners The indoor evaporator fan motor IFM and induced draft mo...

Page 19: ...tions and adjusted properly Airflow can be changed using the User Interface ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power...

Page 20: ...a gauge to the service port 2 Measure the Liquid line temperature by attaching a temperature sensing device to it 3 Insulate the temperature sensing device so that the Outdoor Ambient doesn t affect...

Page 21: ...9 994 917 837 702 570 442 Heating Rise oF C 54 30 58 32 62 34 68 38 NA NA NA NA NA Medium Watts 503 491 479 461 450 436 418 404 389 CFM 1320 1244 1162 1081 1005 897 767 662 541 Heating Rise oF C 51 28...

Page 22: ...729 1647 1496 Heating Rise oF C 31 17 32 18 33 18 34 19 36 20 37 21 39 22 41 23 45 25 48ES N 060115 35 65 19 36 Low1 Watts 786 769 754 736 722 705 684 658 616 CFM 2027 1960 1901 1821 1759 1693 1616 15...

Page 23: ...necessary AIR FILTER IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replacethe filterwith thesame dimensional size and type as originally installed...

Page 24: ...ses Observe the main burner flames and adjust if necessary Removal of Gas Train To remove the gas train for servicing 1 Shut off main gas valve 2 Shut off power to unit and install lockout tag 3 Remov...

Page 25: ...function has occurred check each electrical component with the proper electrical instrumentation Refer to the unit wiring label when making these checks REFRIGERANT CIRCUIT Annually inspect all refrig...

Page 26: ...t extreme high pressure The relief port has an operating range between 550 26 34 kPa and 625 psi 29 93 kPa differential pressure The Copeland scroll compressor uses Mobil 3MAF POE oil Copeland Ultra 2...

Page 27: ...ow side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with...

Page 28: ...or Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor Determine cause and replace Faulty o...

Page 29: ...te ensure temperature rise is correct Ensure unit s external static pressure is within application guide lines Limit switch faults LED 2 flashes High temperature limit switch is open Check the operati...

Page 30: ...________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ______...

Reviews: