background image

10

Step 6—Provide for Condensate Disposal

NOTE

: Ensure that condensate--water disposal methods comply

with local codes, restrictions, and practices.

The units dispose of condensate through a 3/4 --in. NPT female

fitting that exits on the compressor end of the unit. Condensate water
can be drained directly onto the roof in rooftop installations (where

permitted) or onto a gravel apron in ground level installations.

Install a field--supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of

the trap is at least 1 in. lower than the drain--pan condensate
connection to prevent the pan from overflowing. Prime the trap with

water. When using a gravel apron, make sure it slopes away from the

unit.
If the installation requires draining the condensate water away from

the unit, install a field--supplied 2--in. trap at the condensate
connection to ensure proper drainage. Condensate trap is available

as an accessory or is field--supplied. Make sure that the outlet of the
trap is at least 1 in. lower than the unit drain--pan condensate

connection to prevent the pan from overflowing. Connect a drain

trough using a minimum of field--supplied 3/4 --in. PVC or
field--supplied 3/4 --in. copper pipe at outlet end of the 2 --in. trap

(See Fig. 9). Do not undersize the tube. Pitch the drain trough
downward at a slope of at least 1 in. for every 10 ft. of horizontal run.

Be sure to check the drain trough for leaks. Prime the trap at the

beginning of the cooling season start--up.

Step 7—Install Flue Hood

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury

or death.
The venting system is designed to ensure proper venting. The

flue hood assembly must be installed as indicated in this

section of the unit installation instructions.

!

WARNING

Install the flue hood as follows:

1. This installation must conform with local building codes and

with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in
Canada, CAN/CGA B149.1, and B149.2) or NFPA

(National Fire Protection Association) latest revision. Refer
to provincial and local plumbing or wastewater codes and
other applicable local codes.

2. Remove flue hood from shipping location (inside the return

section of the blower compartment--See Fig. 8). Remove the

return duct cover to locate the flue hood. Remove two screws
on flue panel. Place flue hood assembly over flue panel.
Orient screw holes in flue hood with holes in the flue panel.

3. Secure flue hood to flue panel by inserting a single screw on

the top and the bottom of the hood.

Supply Duct Cover

Return Duct Cover

A06320

Fig. 8 -- 48DU with Duct Covers On

1” (25mm) MIN.

2” (50mm) MIN.

TRAP
OUTLET

C99013

Fig. 9 -- Condensate Trap

Step 8—Install Gas Piping

The gas supply pipe enters the unit through the access hole

provided. The gas connection to the unit is made to the 1/2--in. FPT

gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to

Table 2 and the current edition of NFGC in the U.S. and the current
NSCNGPIC in Canada. Do not use cast--iron pipe. It is

recommended that a black iron pipe is used. Check the local utility

for recommendations concerning existing lines. Size gas supply
piping for 0.5 in. wg maximum pressure drop. Never use pipe

smaller than the 1/2--in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection

must not be less than 4.0 in. wg or greater than 13 in. wg while the
unit is operating. For propane applications, refer to propane

conversion kit instructions.
A 1/8--in. NPT plugged tapping, accessible for test gauge
connection, must be installed immediately upstream of the gas

supply connection to the gas valve and downstream of manual
equipment shutoff valve.
When installing the gas supply line, observe local codes pertaining

to gas pipe installations. Refer to the NFGC ANSI Z223.1--2005
NFPA latest edition (in Canada, CAN/CGA B149.1).

NOTE

:In the state of Massachusetts:

1. Gas supply connections MUST be performed by a licensed

plumber or gas fitter.

2. When flexible connectors are used, the maximum length

shall not exceed 36 inches (915 mm).

3. When lever handle type manual equipment shutoff valves

are used, they shall be T--handle valves.

4. The use of copper tubing for gas piping is NOT approved by

the state of Massachusetts.

In the absence of local building codes, adhere to the following

pertinent recommendations:

1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.

for every 15 ft of length to prevent traps. Grade all horizontal

runs downward to risers. Use risers to connect to heating
section and to meter.

2. Protect all segments of piping system against physical and

thermal damage. Support all piping with appropriate straps,

hangers, etc. Use a minimum of one hanger every 6 ft. For
pipe sizes larger than 1/2 in., follow recommendations of
national codes.

3. Apply joint compound (pipe dope) sparingly and only to

male threads of joint when making pipe connections. Use

only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape.

4. Install sediment trap in riser leading to heating section (See

Fig. 10). This drip leg functions as a trap for dirt and

condensate.

5. Install an accessible, external, manual main shutoff valve in

gas supply pipe within 6 ft of heating section.

6. Install ground--joint union close to heating section between

unit manual shutoff and external manual main shut off valve.

48D

U

Summary of Contents for 48DU Series

Page 1: ...Checking Cooling and Heating Control Operation 25 Checking and Adjusting Refrigerant Charge 25 Refrigerant Charge 25 No Charge 25 Low Charge Cooling 25 To Use Cooling Charging Charts 25 Non Communicat...

Page 2: ...w NOx units designed for California installations These models meet the California maximum oxides of nitrogen NOx emissions requirements of 40 nanograms joule or less as shipped from the factory and m...

Page 3: ...Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 4: ...4 A06323 Fig 5 48DU024 030 Unit Dimensions...

Page 5: ...5 A06324 Fig 6 48DU036 060 Unit Dimensions...

Page 6: ...OIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface i...

Page 7: ...e for high capacity type Air filter pressure drop for non standard filters must not exceed 0 08 in wg Step 3 Provide Clearances The required minimum service clearances are shown in Fig 5 and 6 Adequat...

Page 8: ...strip screws when re securing the unit If a screw is stripped replace the stripped one with a larger diameter screw included WARNING Rigging Lifting of Unit 1 Bend top of brackets down approximately...

Page 9: ...Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning s...

Page 10: ...OUTLET C99013 Fig 9 Condensate Trap Step 8 Install Gas Piping The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on...

Page 11: ...ot use a connector which has previously serviced another gas appliance WARNING 8 Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been compl...

Page 12: ...HUMIDITY CONTROL COMFORT ROLLBACK ETC WILL BE LOST IF THE OAT IS NOT CONNECTED For detailed mounting instructions for the OAT sensor please refer to TSTATXXSEN01 B installation instructions catalog n...

Page 13: ...BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 12 Line Power Connections...

Page 14: ...Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire I fother than 60 C wire is used or if length exceeds wire length in...

Page 15: ...orrectly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hub is positioned correctly with respect to motor housing See Fig 23 d Make sure tha...

Page 16: ...can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Particularly at low airflow requests This is normal do not ass...

Page 17: ...17 6 0 A06310 Fig 16 Wiring Schematic 48DU Single Phase 48DU...

Page 18: ...system defective switch or connections or inadequate combustion air supply flame roll out switch open STATUS CODE 34 IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs...

Page 19: ...rststageandsecondstagecoolingare satisfied the compressorwill shut off NOTE When two stage unit is operating at low stage system vapor suction pressure will be higher than a standard single stage syst...

Page 20: ...age Ther mal Cutout 72 Compressor voltage sensed then disappears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installe...

Page 21: ...nes what heating stage to run based on feedback from the UI If the UI is asking for low stage gas heat the ignition control will changetheinducerspeedtolow speedand keepthe gasvalve energized on low s...

Page 22: ...ate and clockwise in to increase input rate REGULATOR COVER SCREW PLASTIC ADJUST SCREW LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT MANIFOLD PRESSURE TAP INLET PRESSURE TAP ON OFF SWITCH REGULATOR SPRI...

Page 23: ...one revolution takes 84 sec and the heating value of the gas is 1050 Btu ft3 Proceed as follows a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90...

Page 24: ...oblem in the case of a gas component failure To initiate the component test procedure ensure that there arenoUIinputstothecontrol theABCDconnectorcan beremoved fromthe Infinitycontrol boardfor thisope...

Page 25: ...eading Indoor air CFM must be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to...

Page 26: ...578 41 39 36 30 384 108 103 98 88 2647 42 40 37 31 394 110 105 100 90 2716 44 41 38 32 404 112 107 102 92 2785 45 42 39 33 414 114 109 104 94 2854 46 43 40 34 424 116 111 106 96 2923 47 44 41 35 434 1...

Page 27: ...nsional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable type at least twice d...

Page 28: ...ly After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in...

Page 29: ...performing any service that may risk exposure ofcompressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage include but are not limited to compressor r...

Page 30: ...mand for compressor operation the contactor may be stuck closed or there is a wiring error The control will flash the appropriate fault code COMPRESSOR THERMAL CUTOUT If the control senses the compres...

Page 31: ...should fail low ambient cooling will not be allowed Defrost will occur at each time interval during heating operation but will terminate after 5 minutes If there is a thermistor out of range error de...

Page 32: ...h 520 psig low side retard S Use hoses with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S...

Page 33: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Page 34: ...unit 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace fil...

Page 35: ...ESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR...

Page 36: ...W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48DU 2SI Replaces 48DU 1SI Print...

Reviews: