background image

22

Gas input rates on rating plate are for installations at altitudes up to
2000 ft. Input rate must be within

±

2% of rating plate input.

1. Determine the correct gas input rate.

a. The rated gas inputs shown in Table 4 are for altitudes

from sea level to 2000 ft above sea level. These inputs are

based on natural gas with a heating value of 1050 Btu/ft3
at .65 specific gravity.

IN THE U.S.A.:
The input rating for altitudes above 2,000 ft. must be reduced by 4
percent for each 1,000 ft. above sea level.
For installations below 2,000 ft., refer to the unit rating plate.
For installations above 2,000 ft., multiply the input by on the rating

plate by the derate multiplier in Table 6 for the correct input rate.

Table 6—

Altitude Derate Multiplier for U.S.A.

Altitude (Ft)

Percent of Derate

Derate Multiplier

Factor*

0--2000

0

1.00

2001--3000

8--12

0.90

3001--4000

12--16

0.86

4001--5000

16--20

0.82

5001--6000

20--24

0.78

6001--7000

24--28

0.74

7001--8000

28--32

0.70

8001--9000

32--36

0.66

9001--10,000

36--40

0.62

*Derate multiplier factors are based on midpoint altitude for altitude range.

IN CANADA:
The input rating for altitudes from 2,000 to 4,500 ft above sea level

must be derated 10 percent by an authorized Gas Conversion Station

or Dealer.
EXAMPLE:

90,000 Bhuh Input Furnace Installed at 4300 Ft.

Furnace Input Rate

Derate Multiplier

Furnace Input Rate

at Sea Level

X

Factor

=

at Installation Altitude

90,000

X

0.90

=

81,000

b. When the gas supply being used has a different heating

value or specific gravity, refer to national and local codes,

or contact your distributor to determine the required
orifice size.

2. Adjust manifold pressure to obtain low stage input rate (See

Fig. 18).

a. Turn off gas supply to unit.

b. Remove pipe plug on manifold (See Fig. 19) and connect

manometer. Turn on gas supply to unit.

c. Turn gas valve switch to ON.

d. Set unit to run for 20 minutes in low--stage gas heat

operation using the ”INSTALLER CHECKOUT” menu
on the User Interface.

e. Remove regulator adjustment cap from low stage gas

valve pressure regulator (See Fig. 18) and turn low--stage
adjusting screw (3/16 or smaller flat--tipped screwdriver)

counterclockwise (out) to decrease rate and clockwise
(in) to increase input rate.

REGULATOR COVER SCREW

PLASTIC ADJUST SCREW

LOW STAGE  
GAS PRESSURE 
REGULATOR ADJUSTMENT

MANIFOLD
PRESSURE TAP

INLET
PRESSURE TAP

ON/OFF SWITCH

REGULATOR SPRING

HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT

A04167

Fig. 18 -- Redundant Automatic Gas Control Valve

NOTE

: DO NOT set low stage manifold pressure less than 1.4 in

wc or more than 2.0 in wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.

f. Re--install low stage regulator adjustment cap.

g. Leave manometer connected.

NOTE

: If orifice hole appears damaged or it is suspected to have

been re--drilled, check orifice hole with a numbered drill bit of the
correct size. Never re--drill an orifice. A burr--free and squarely
aligned orifice hole is essential for proper flame characteristics.

3. Verify natural gas low stage input rate.

a. Turn off all other gas appliances and pilots served by the

gas meter.

b. If unit is not running, set unit to run for 20 minutes in

low--stage gas heat operation using the ”INSTALLER

CHECKOUT” menu on the UI.

c. Record number of seconds for gas meter to complete one

revolution.

d. Divide number of seconds in step c. into 3600 (number

of seconds in 1 hour).

e. Multiply result of step d. by the number of cubic feet

shown for one revolution of test dial to obtain cubic feet

of gas flow per hour.

f. Multiply result of step f. by Btu heating value of the gas

to obtain total measured input shown in Table 4. (Consult
the local gas supplier if the heating value of gas is not
known).

EXAMPLE: Assume a 90,000 high stage input unit is being

installed. Assume that the size of the dial is 2 cubic ft., one
revolution takes 129 sec., and the heating value of the gas is 1050

Btu/ft3. Proceed as follows:

a. 129 sec. to complete one revolution

b. 3600/129 = 27.9

c. 27.9 x 2 = 55.8 ft3 of gas flow/hr.

d. 55.8 x 1050 = 58,590 Btuh input.

In this example, the nominal input rate for low stage is 58,500

Btu/hr, so the low stage manifold pressure is correctly set.
If the measured low stage rate is too low, increase the manifold

pressure to increase rate. If the measured low stage rate is too high,

decrease the manifold pressure to decrease rate.

NOTE

: Double--check that UI is running on low stage gas heat

while clocking the low stage firing rate.

4. Verify proper low stage gas heat temperature rise.

48D

U

Summary of Contents for 48DU Series

Page 1: ...Checking Cooling and Heating Control Operation 25 Checking and Adjusting Refrigerant Charge 25 Refrigerant Charge 25 No Charge 25 Low Charge Cooling 25 To Use Cooling Charging Charts 25 Non Communicat...

Page 2: ...w NOx units designed for California installations These models meet the California maximum oxides of nitrogen NOx emissions requirements of 40 nanograms joule or less as shipped from the factory and m...

Page 3: ...Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 4: ...4 A06323 Fig 5 48DU024 030 Unit Dimensions...

Page 5: ...5 A06324 Fig 6 48DU036 060 Unit Dimensions...

Page 6: ...OIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface i...

Page 7: ...e for high capacity type Air filter pressure drop for non standard filters must not exceed 0 08 in wg Step 3 Provide Clearances The required minimum service clearances are shown in Fig 5 and 6 Adequat...

Page 8: ...strip screws when re securing the unit If a screw is stripped replace the stripped one with a larger diameter screw included WARNING Rigging Lifting of Unit 1 Bend top of brackets down approximately...

Page 9: ...Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning s...

Page 10: ...OUTLET C99013 Fig 9 Condensate Trap Step 8 Install Gas Piping The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on...

Page 11: ...ot use a connector which has previously serviced another gas appliance WARNING 8 Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been compl...

Page 12: ...HUMIDITY CONTROL COMFORT ROLLBACK ETC WILL BE LOST IF THE OAT IS NOT CONNECTED For detailed mounting instructions for the OAT sensor please refer to TSTATXXSEN01 B installation instructions catalog n...

Page 13: ...BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 12 Line Power Connections...

Page 14: ...Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire I fother than 60 C wire is used or if length exceeds wire length in...

Page 15: ...orrectly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hub is positioned correctly with respect to motor housing See Fig 23 d Make sure tha...

Page 16: ...can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Particularly at low airflow requests This is normal do not ass...

Page 17: ...17 6 0 A06310 Fig 16 Wiring Schematic 48DU Single Phase 48DU...

Page 18: ...system defective switch or connections or inadequate combustion air supply flame roll out switch open STATUS CODE 34 IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs...

Page 19: ...rststageandsecondstagecoolingare satisfied the compressorwill shut off NOTE When two stage unit is operating at low stage system vapor suction pressure will be higher than a standard single stage syst...

Page 20: ...age Ther mal Cutout 72 Compressor voltage sensed then disappears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installe...

Page 21: ...nes what heating stage to run based on feedback from the UI If the UI is asking for low stage gas heat the ignition control will changetheinducerspeedtolow speedand keepthe gasvalve energized on low s...

Page 22: ...ate and clockwise in to increase input rate REGULATOR COVER SCREW PLASTIC ADJUST SCREW LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT MANIFOLD PRESSURE TAP INLET PRESSURE TAP ON OFF SWITCH REGULATOR SPRI...

Page 23: ...one revolution takes 84 sec and the heating value of the gas is 1050 Btu ft3 Proceed as follows a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90...

Page 24: ...oblem in the case of a gas component failure To initiate the component test procedure ensure that there arenoUIinputstothecontrol theABCDconnectorcan beremoved fromthe Infinitycontrol boardfor thisope...

Page 25: ...eading Indoor air CFM must be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to...

Page 26: ...578 41 39 36 30 384 108 103 98 88 2647 42 40 37 31 394 110 105 100 90 2716 44 41 38 32 404 112 107 102 92 2785 45 42 39 33 414 114 109 104 94 2854 46 43 40 34 424 116 111 106 96 2923 47 44 41 35 434 1...

Page 27: ...nsional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable type at least twice d...

Page 28: ...ly After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in...

Page 29: ...performing any service that may risk exposure ofcompressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage include but are not limited to compressor r...

Page 30: ...mand for compressor operation the contactor may be stuck closed or there is a wiring error The control will flash the appropriate fault code COMPRESSOR THERMAL CUTOUT If the control senses the compres...

Page 31: ...should fail low ambient cooling will not be allowed Defrost will occur at each time interval during heating operation but will terminate after 5 minutes If there is a thermistor out of range error de...

Page 32: ...h 520 psig low side retard S Use hoses with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S...

Page 33: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Page 34: ...unit 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace fil...

Page 35: ...ESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR...

Page 36: ...W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48DU 2SI Replaces 48DU 1SI Print...

Reviews: