Table 10—

Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan

will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, or high--

pressure, loss--of--charge or low--pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

UI setting too low/too high

Reset UI setting

DO NOT bypass this compressor time

delay–wait for 5 minutes until time--delay

relay is de--energized

Units have a 5--minute time delay

Compressor will not start but condenser fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

Low input voltage (20 percent low)

Determine cause and correct

Compressor cycles (other than normally sat-

isfying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

UI temperature set too low

Reset UI setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

High heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

Insufficient coil airflow

Check filter–replace if necessary

Temperature too low in conditioned area

Reset UI setting

Outdoor ambient below 55

°

F

Verify low--ambient cooling enabled in UI

Filter drier restricted

Replace

IFM does not run

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly sealed

Connectors should snap easily; do not force

IFM operation is intermittent

Water dripping into motor

Verify proper drip loops in connector wires

Connectors not firmly sealed

Gently pull wires individually to be sure they are

crimped into the housing

48D

U

Summary of Contents for 48DU Series

Page 1: ...Checking Cooling and Heating Control Operation 25 Checking and Adjusting Refrigerant Charge 25 Refrigerant Charge 25 No Charge 25 Low Charge Cooling 25 To Use Cooling Charging Charts 25 Non Communicat...

Page 2: ...w NOx units designed for California installations These models meet the California maximum oxides of nitrogen NOx emissions requirements of 40 nanograms joule or less as shipped from the factory and m...

Page 3: ...Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 4: ...4 A06323 Fig 5 48DU024 030 Unit Dimensions...

Page 5: ...5 A06324 Fig 6 48DU036 060 Unit Dimensions...

Page 6: ...OIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface i...

Page 7: ...e for high capacity type Air filter pressure drop for non standard filters must not exceed 0 08 in wg Step 3 Provide Clearances The required minimum service clearances are shown in Fig 5 and 6 Adequat...

Page 8: ...strip screws when re securing the unit If a screw is stripped replace the stripped one with a larger diameter screw included WARNING Rigging Lifting of Unit 1 Bend top of brackets down approximately...

Page 9: ...Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning s...

Page 10: ...OUTLET C99013 Fig 9 Condensate Trap Step 8 Install Gas Piping The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on...

Page 11: ...ot use a connector which has previously serviced another gas appliance WARNING 8 Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been compl...

Page 12: ...HUMIDITY CONTROL COMFORT ROLLBACK ETC WILL BE LOST IF THE OAT IS NOT CONNECTED For detailed mounting instructions for the OAT sensor please refer to TSTATXXSEN01 B installation instructions catalog n...

Page 13: ...BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 12 Line Power Connections...

Page 14: ...Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire I fother than 60 C wire is used or if length exceeds wire length in...

Page 15: ...orrectly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hub is positioned correctly with respect to motor housing See Fig 23 d Make sure tha...

Page 16: ...can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Particularly at low airflow requests This is normal do not ass...

Page 17: ...17 6 0 A06310 Fig 16 Wiring Schematic 48DU Single Phase 48DU...

Page 18: ...system defective switch or connections or inadequate combustion air supply flame roll out switch open STATUS CODE 34 IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs...

Page 19: ...rststageandsecondstagecoolingare satisfied the compressorwill shut off NOTE When two stage unit is operating at low stage system vapor suction pressure will be higher than a standard single stage syst...

Page 20: ...age Ther mal Cutout 72 Compressor voltage sensed then disappears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installe...

Page 21: ...nes what heating stage to run based on feedback from the UI If the UI is asking for low stage gas heat the ignition control will changetheinducerspeedtolow speedand keepthe gasvalve energized on low s...

Page 22: ...ate and clockwise in to increase input rate REGULATOR COVER SCREW PLASTIC ADJUST SCREW LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT MANIFOLD PRESSURE TAP INLET PRESSURE TAP ON OFF SWITCH REGULATOR SPRI...

Page 23: ...one revolution takes 84 sec and the heating value of the gas is 1050 Btu ft3 Proceed as follows a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90...

Page 24: ...oblem in the case of a gas component failure To initiate the component test procedure ensure that there arenoUIinputstothecontrol theABCDconnectorcan beremoved fromthe Infinitycontrol boardfor thisope...

Page 25: ...eading Indoor air CFM must be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to...

Page 26: ...578 41 39 36 30 384 108 103 98 88 2647 42 40 37 31 394 110 105 100 90 2716 44 41 38 32 404 112 107 102 92 2785 45 42 39 33 414 114 109 104 94 2854 46 43 40 34 424 116 111 106 96 2923 47 44 41 35 434 1...

Page 27: ...nsional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable type at least twice d...

Page 28: ...ly After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in...

Page 29: ...performing any service that may risk exposure ofcompressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage include but are not limited to compressor r...

Page 30: ...mand for compressor operation the contactor may be stuck closed or there is a wiring error The control will flash the appropriate fault code COMPRESSOR THERMAL CUTOUT If the control senses the compres...

Page 31: ...should fail low ambient cooling will not be allowed Defrost will occur at each time interval during heating operation but will terminate after 5 minutes If there is a thermistor out of range error de...

Page 32: ...h 520 psig low side retard S Use hoses with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S...

Page 33: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Page 34: ...unit 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace fil...

Page 35: ...ESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR...

Page 36: ...W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48DU 2SI Replaces 48DU 1SI Print...

Reviews: