background image

1

48/50HG014---028, 48/50PG20---28

Single---Package Rooftop Units

with

COMFORT

Link

t

and Electro---Mechanical Controls

Return and Supply Smoke Detectors Accessory

Installation Instructions

PART NO. CRSMKDET001D00, CRSMKSUP001B00, CRSMKSEN001A00

TABLE OF CONTENTS

GENERAL

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Package Contents

2

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Return Air Smoke Detector Installation

2

. . . . . . . . . . . . . . .

Supply Air Smoke Detector Installation

5

. . . . . . . . . . . . . . .

Sensor Installation

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring the

Comfort

Link

t

Controller

8

. . . . . . . . . . . .

OPERATION

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cleaning Procedure

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Recommended Service Schedule

9

. . . . . . . . . . . . . . . . . . . .

Sensor Tests

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Controller Tests

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Dirty LED

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power LED

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Trouble LED

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IMPORTANT

: There are two different design revision 48/50HG

units that have been produced. Because of these differences, there
are two different versions of this accessory. This accessory
literature covers accessories manufactured for units with design
revision 1. This revision designator is found in the 13th digit of
the unit model number located on the units’ rating plate. Design
revision 0 units are not covered in this accessory book.
To determine the design revision, refer to the full unit model
number. See Fig. 1 for an example of an HG model number. The
design revision number in the model number nomenclature is
located in position 13.

Position No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Example:

4

8 H G D 0

1

6 A

A

C

6

1

1

A

A

DESIGN REVISION NUMBER

C07172

Fig. 1

---

Model Number Chart

GENERAL

An HVAC (heating, ventilation and air-conditioning) system
supplies conditioned air to virtually every area of a building.

Smoke introduced into this air duct system will be distributed
throughout the entire building. Smoke detectors designed for use

inside the unit are used to sense the presence of smoke passing

through the unit.
The smoke detector utilizes photoelectric technology for the

detection of smoke. This detection method, when combined with
an efficient ducting design, samples air passing through the unit.

If sufficient smoke is sensed, an alarm signal is initiated and the

Comfort

Link controls will shut down the unit. With the unit shut

down, the unit will not blow toxic smoke and fire gases

throughout the areas served by the duct system.
The

return

air

smoke

detector

is

part

number

CRSMKDET001D00, which includes a Smoke Sensor and a
Smoke Control Module combined with sampling tube, harnesses

and hardware. The supply air smoke detector is part number

CRSMKSUP001B00, which includes a Smoke Sensor and a
Smoke Control Module combined with sampling tube, harnesses

and hardware. Part number CRSMKSEN001A00 is a Smoke
Sensor only for use as a second (Supply with existing Return, or

Return with existing Supply) Air Smoke Detector with sampling

tube, harnesses and hardware.
The Control Module can be attached to a Smoke Sensor and

installed as an assembled unit, or it can be installed separate from
a sensor. One Controller can be used to control up to two

detectors (Smoke Sensors).

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be

hazardous due to system pressure and electrical components.

Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions
of cleaning coils and filters and replacing filters. All other

operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe

precautions in the literature, tags and labels attached to the unit,

and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use

care when handling and installing the accessory.
Recognize safety information. This is the safety--alert symbol

. When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.

Summary of Contents for 48/50HG014-028

Page 1: ...ric technology for the detection of smoke This detection method when combined with an efficient ducting design samples air passing through the unit If sufficient smoke is sensed an alarm signal is initiated and the ComfortLink controls will shut down the unit With the unit shut down the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system The return air smok...

Page 2: ...UST be operated within ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct WARNING INSTALLATION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage When installing the smoke detector in the unit follow all local codes CAUTION C...

Page 3: ...ke detector prior to making duct connections 1 Open the hinged electrical compressor access door and secure 2 Find the 2 plugs located above compressor B1 A2 remove and discard Cut holes in the insulation located be hind the partition 3 Remove cover from smoke detector The screws will remain captured in the cover 4 Slide exhaust tube into the sensor The exhaust tube should be inserted from the bac...

Page 4: ...50PG Humidi MiZert units because they have plug 19 harness already installed in the control box The harness assembly part number 50TG403507 that came with the accessory is not used Factory installed PL 19 can be located outside the contol box by its appropriate label For Humidi MiZer smoke detector wiring refer to Fig 8 16 Connect PL 19 from the smoke detector control module to the PL 19 on the co...

Page 5: ...to installation of this accessory make sure all power is disconnected to the unit and locked out and tagged WARNING 1 Open the indoor fan access door and secure 2 Open and secure hinged electrical compressor access door 3 Disconnect wires located on the right hand side of the fan deck On gas heat units the indoor fan plug and the limit switch quick connects must be disconnected On units without ga...

Page 6: ...6 C07178 Fig 7 Smoke Detector Wiring on Electro Mechanical Control Units C07179 Fig 8 48 50PG Humidi MiZert Smoke Detector Wiring CRSMK ...

Page 7: ...On 48PG Humidi MiZer units the control box harness has a jumper plug attached This needs to be disconnected so PL 19 from the smoke detector can be snapped in 20 Route cable from supply smoke sensor along the outside of the control box through the control module knockout and connect to the J1 RJ 45 connector 21 Using wire ties secure the wiring so it does not interfere with unit operation 22 Repla...

Page 8: ...d in the unit Default password is 1111 Use the arrow keys to scroll the red LED on the display to the Configuration position and press ENTER Scroll through the menu until UNIT is found and press ENTER After reaching the UNIT sub menu scroll to FS SW Fire Shutdown Input and press ENTER twice change the value to 1 Normal Open with the arrow keys press ENTER again Press ESCAPE three times to return t...

Page 9: ...after S Perform a sensor alarm test on each sensor connected to the controller upon installation and once every 12 months thereafter S Perform a sensor dirty test upon installation and once every 6 months thereafter or more frequently as conditions warrant Sensor Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires the use of a SD MAG ...

Page 10: ...nd JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply in put terminals If power is not present replace or repair wir ing as required Trouble LED Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on determine the cause and make the necessary repairs 2 Che...

Reviews: