12
Fig. 8 — 42CK Horizontal Cabinet Unit with Telescopic Access Panel,
Front Supply, Bottom Return, and Heater Dimensions
12
11
10
9
13
NOTES:
1. Right hand unit shown; left hand unit opposite.
2. Internal factory valve package and drains may not align with
cabinet knockouts.
3. Dimensions shown in inches (mm). All dimensions are
±
1
/
4
inches.
4. Bottom panel is Arctic White polyester powder coat paint.
*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
UNIT
SIZE
NOM
AIRFLOW
(Cfm)
DIMENSIONS (in.)
QTY/UNIT
BOTTOM
RETURN
FILTER SIZE
(in.)
UNIT WEIGHT*
(lb)
A
B
C
D
E
F
Blower
Motor
02
200
35
16
12
3
/
4
37
32
6
1
1
10 x 23
1
/
2
117
03
300
35
20
8
3
/
4
37
32
6
1
1
10 x 28
122
04
400
41
26
8
3
/
4
43
38
6
2
1
10 x 32
1
/
2
137
06
600
53
31
15
3
/
4
55
50
7
2
1
10 x 37
152
08
800
53
38
8
3
/
4
55
50
7
2
1
10 x 41
157
10
1000
75
52
16
3
/
4
77
72
7
4
2
10 x 54
1
/
2
229
12
1200
75
60
8
3
/
4
77
72
7
4
2
10 x 63
243
a42-4150
LEGEND
1 — Contactor Box
2 — Strip Heater High Limit
3 — Electric Strip Heater Element
4 — L-shape Drip Lip (optional, shipped loose)
5 — Chilled/Hot Water Supply and Return Connection
6 — Resilient Mounting Grommets with
3
/
8
-in. Diameter Hole
(typically 4)
7 — Electrical Knockout,
7
/
8
-in. Diameter
8 — Drain Knockout, 1
1
/
2
-in. Diameter
9 — Stamped Return Air Grille and 1-in. Filter
10 — Condensate Drain Connection,
7
/
8
-in. OD
11 — Hinged Bottom Return Air Panel
12 — Supply Duct Collar, 1-in. OD
13 — Drain Pan