background image

46

Step 3 — Make Electrical Connections — 

Refer

to unit nameplate for required supply voltage, fan and heater

amperage and required circuit ampacity. Refer to unit wir-

ing diagram for unit and field wiring. Since each project is

different and each unit on a project may be different, the in-

staller must be familiar with the wiring diagram and name-

plate on the unit before beginning any wiring. Make sure all

electrical connections are in accordance with unit wiring di-

agram and all applicable codes. The type and sizing of all

wiring and other electrical components such as circuit

breakers, disconnect switches, etc. should be determined by

the individual job requirements, and should not be based on

the size and/or type of connection provided on the equip-

ment. All installations should be made in compliance with

all governing codes and ordinances. Compliance with all

codes is the responsibility of the installing contractor.

The fan motor(s) should never be controlled by any wiring

or device other than the factory-supplied switch or thermostat/

switch combination unless prior factory authorization is

obtained. Fan motor(s) may be temporarily wired for use

during construction only with prior factory approval and only

in strict accordance with the instructions issued at that time.

All components furnished for field installation by either the

factory or the controls contractor should be located and

checked for proper function and compatibility.  All internal

components should be checked for shipping damage, and any

loose connections should be tightened to minimize problems

during start-up.

Any devices such as fan switches or thermostats that have

been furnished from the factory for field installation must be

wired in strict accordance with the wiring diagram that appears

on the unit.  Failure to do so could result in personal injury or

damage to components, and will void all manufacturer's

warranties.

Units with factory-supplied and factory-installed aquastats

may be shipped with the aquastats mounted on a coil stub-out.

If this is the case, remove the aquastat before installing valve

package. When reinstalling aquastats, consult the factory-

piping diagram in the submittal for proper location. If the valve

package is field-supplied, the aquastat must be installed in a

location where it will sense the water temperature regardless of

the control valve position. A bleed bypass may be required to

guarantee proper aquastat operation. The aquastat bypass line

allows a small amount of water to flow from the supply to the

return piping when the control valve is closed.
FACTORY-INSTALLED OPTIONS
Condensate Overflow Switch — The condensate overflow

switch is used to detect a clogged condensate drain pan. The

condensate switch uses a normally closed contact to allow the

system control power to pass through the switch energizing the

water valves and fans allowing normal operation. When an

overflow condition is detected by the switch, it opens the NC

contact and de-energizes the water valve and fans.
Aquastat — The aquastat must be able to sense whether the

flowing water is being chilled or heated and switches a contact

closed to provide automatic summer or winter changeover for

the system. When a two-pipe cooling/heating system with

optional auxiliary electric heat is desired, an additional

aquastat is required.

Units with optional factory furnished and installed aquastats

may be shipped with aquastats mounted on the coil stub out. In

this situation, remove the aquastat before valve package instal-

lation. Refer Fig. 35 for factory piping diagram for proper loca-

tion when reinstalling the aquastats. If the valve package is

field supplied the aquastat must be installed in a location where

it will sense the water temperature regardless of control valve

position. A bleed bypass should be provided for proper opera-

tion of aquastat. The bleed line allows a small amount of water

to flow from supply to return piping when the control valve is

closed for loop temperature sensing.

All field wiring must be in accordance with governing

codes and ordinances. Any modification of unit wiring without

factory authorization will invalidate all factory warranties and

nullify any agency listings. The manufacturer assumes no re-

sponsibility for any damages and/or injuries resulting from im-

proper field installation and/or wiring.

 

Units may be equipped with line voltage controls or

24 VAC control systems. The following descriptions are for

typical control sequences only. For detailed control operating

sequence, refer to thermostat operating instructions.
STANDARD WIRING PACKAGES
Manual Fan Control — On vertical cabinet units, a fan-speed

switch may be furnished unit-mounted and wired. On vertical

furred-in units and horizontal units, the switch may be shipped

separately on a decorative wall plate for field mounting and

wiring.

The standard switch has LOW, MEDIUM, HIGH and OFF

positions plus an auxiliary contact to energize thermostats,

valves, dampers, etc.

NOTE: Wiring diagrams are for typical applications. If other

voltages for heaters or controls are specified, wiring may differ

from that shown. Refer to wiring diagram on unit blower hous-

ing for unit specific wiring.
Thermostatic Electric Valve Control, 2-Pipe — A thermo-

statically controlled 2-position valve provides superior control

to fan cycling. With this control, the fan runs continuously un-

less it is manually switched to the OFF or AUTO position. The

fan must be on before the valve can be opened to supply water

to the coil.

This system can be used for normal 2-pipe changeover systems

and can also be furnished for cooling-only or heating-only ap-

plications by omitting the changeover and specifying which

application is intended. Wiring diagrams show typical applica-

tions. Refer to wiring diagram on unit blower housing for unit

specific wiring.
Thermostatic 2-Pipe Auxiliary Electric Heat with Valve Con-

trol — This system, also called twilight or intermediate season

electric heat, goes a long way towards solving the spring and

fall control problems of 2-pipe systems.

Chilled water can be run late into the fall, turned on early in

the spring and electric heat will still be available to all units

whenever required.

Field

Tubing

Wet Rag

Torch

Supply

or

Return

Adaptor

(Factory Installed)

Stub

From Coil

Fig. 40 — Field Piping Connections

IMPORTANT: Refer to unit wiring label for specific

functions. Standard wiring diagram configurations are

maintained in separate Fan Coil Wiring Diagram litera-

ture.

Summary of Contents for 42VA Series

Page 1: ...equipment location such as a ceiling or elevated structure Only trained qualified installers and service mechanics should install and service this equipment When installing this unit observe precauti...

Page 2: ...n return air plenum UNIT SIZE 42C 02 03 04 06 08 10 12 NOMINAL AIRFLOW cfm 200 300 400 600 800 1000 1200 SHIPPING WEIGHT lb 42CA 36 39 49 59 64 95 107 42CE 55 60 70 82 95 135 154 42CG 98 118 126 168 1...

Page 3: ...in Coil Outlet and Inlet 5 8 OD Drain Connection 3 4 MPT UNIT SIZE 42D 06 08 10 12 14 16 18 20 NOMINAL AIRFLOW cfm 600 800 1000 1200 1400 1600 1800 2000 SHIPPING WEIGHT lb 42DA 64 79 90 108 119 124 1...

Page 4: ...robust materials and presents a rugged appearance Still great care must be taken to assure that no force or pressure is applied to the coil piping or drain stub outs during handling Depending on the...

Page 5: ...0 211 4 311 4 16 13 181 4 61 4 83 4 193 4 1 1 0 83 36 03 300 251 4 361 4 20 14 221 4 61 4 83 4 233 4 1 1 1 08 39 04 400 311 4 431 4 26 15 281 4 61 4 83 4 293 4 2 1 1 35 49 06 600 361 4 431 4 31 10 331...

Page 6: ...rall unit dimension increases by 4 in with optional electric heat 5 Not shown 3 speed fan switch wall plate closed cell foam on main drain pan 6 Units have galvanized finish 7 For optional coil connec...

Page 7: ...nn 7 8 in OD 5 Tell Tale Drain Conn 5 8 in OD optional 6 Drip Lip optional shipped loose 7 Filter 8 Return Duct Collar 1 in 9 Filter Access Panel 10 Access Panel 11 Supply Duct Collar 1 in 12 Air Vent...

Page 8: ...5 Drain Conn 7 8 in OD 6 Strip Heater High Limit 7 Tell Tale Drain Conn 5 8 in OD optional 8 Drip Lip optional shipped loose 9 Filter 10 Return Duct Collar 1 in 11 Filter Access Panel 12 Access Panel...

Page 9: ...16 34 53 4 11 1 1 0 83 98 03 300 42 211 2 101 4 38 53 4 11 1 1 1 08 118 04 400 48 257 8 111 16 44 53 4 11 2 1 1 35 126 06 600 53 345 8 93 16 49 63 4 12 2 1 1 88 168 08 800 60 39 101 2 56 63 4 12 2 1...

Page 10: ...0 and 12 have 2 motors 4 blowers 3 Cabinet has an Arctic White baked finish 4 Refer to supply and return connections above for coil stub out locations 5 Not shown 3 speed fan switch wall plate 1 2 in...

Page 11: ...163 4 77 72 7 4 2 10 x 541 2 227 12 1200 75 60 83 4 77 72 7 4 2 10 x 63 241 LEGEND 1 Junction Box 2 L shape Drip Lip optional shipped loose 3 Chilled Hot Water Supply and Return Connection 4 Resilien...

Page 12: ...wer Motor 02 200 35 16 123 4 37 32 6 1 1 10 x 231 2 117 03 300 35 20 83 4 37 32 6 1 1 10 x 28 122 04 400 41 26 83 4 43 38 6 2 1 10 x 321 2 137 06 600 53 31 153 4 55 50 7 2 1 10 x 37 152 08 800 53 38 8...

Page 13: ...227 12 1200 75 60 83 4 77 72 7 4 2 7 x 52 241 a42 4151 NOTES 1 Right hand unit shown left hand unit opposite 2 Internal factory valve package and drains may not align with cabinet knockouts 3 Dimensio...

Page 14: ...123 4 37 32 6 1 1 7 x 21 117 03 300 35 20 83 4 37 32 6 1 1 7 x 21 122 04 400 41 26 83 4 43 38 6 2 1 7 x 27 137 06 600 53 31 153 4 55 50 7 2 1 7 x 38 152 08 800 53 38 83 4 55 50 7 2 1 7 x 38 157 10 10...

Page 15: ...D E Blower Motor 02 200 35 37 32 1 1 0 83 115 03 300 35 37 32 1 1 1 08 120 04 400 41 43 38 2 1 1 35 135 06 600 53 55 50 2 1 1 88 150 08 800 53 55 50 2 1 2 31 155 10 1000 75 77 72 4 2 3 16 227 12 1200...

Page 16: ...hrough 08 have one motor 2 blowers sizes 10 and 12 have 2 motors 4 blowers 3 Bottom access panel has an Arctic White baked finish 4 Refer to supply and return connections above for coil stub out locat...

Page 17: ...SIZE DIMENSIONS in QTY UNIT UNIT WEIGHT lb A B C D Blower Motor 02 243 16 22 23 16 1 1 42 03 243 16 22 23 18 1 1 47 04 343 16 32 33 26 2 1 57 06 443 16 42 43 36 2 1 77 08 463 16 44 45 38 2 1 79 10 603...

Page 18: ...nts UNIT SIZE DIMENSIONS in QTY UNIT UNIT WEIGHT lb A B C D Blower Motor 02 243 16 22 23 16 1 1 42 03 243 16 22 23 18 1 1 47 04 343 16 32 33 26 2 1 57 06 443 16 42 43 36 2 1 77 08 463 16 44 45 38 2 1...

Page 19: ...MENSIONS in QTY UNIT UNIT WEIGHT lb A B C D E Blower Motor 02 41 22 23 171 4 31 8 1 1 63 03 41 22 23 171 4 31 8 1 1 68 04 51 32 33 26 33 4 2 1 82 06 61 42 43 39 21 4 2 1 99 08 63 44 45 39 31 4 2 1 101...

Page 20: ...ts UNIT SIZE DIMENSIONS in QTY UNIT UNIT WEIGHT lb A B C D E Blower Motor 02 41 22 23 171 4 31 8 1 1 63 03 41 22 23 171 4 31 8 1 1 68 04 51 32 33 26 33 4 2 1 82 06 61 42 43 39 21 4 2 1 99 08 63 44 45...

Page 21: ...NSIONS in QTY UNIT UNIT WEIGHT lb A B C D E Blower Motor 02 41 22 23 171 4 31 8 1 1 64 03 41 22 23 171 4 31 8 1 1 69 04 51 32 33 26 33 4 2 1 83 06 61 42 43 39 21 4 2 1 100 08 63 44 45 39 31 4 2 1 102...

Page 22: ...SIZE DIMENSIONS in QTY UNIT UNIT WEIGHT lb A B C D E Blower Motor 02 41 22 23 171 4 31 8 1 1 64 03 41 22 23 171 4 31 8 1 1 69 04 51 32 33 26 33 4 2 1 83 06 61 42 43 39 21 4 2 1 100 08 63 44 45 39 31...

Page 23: ...60 04 400 36 35 30 2 1 2 08 72 06 600 50 49 44 4 2 3 06 110 NOTES 1 Right hand unit shown left hand unit opposite Coil connection locations are 5 8 inch 2 Unit sizes 02 through 04 have one motor 2 bl...

Page 24: ...1 18 50 03 300 28 27 22 2 1 1 53 60 04 400 36 35 30 2 1 2 08 72 06 600 50 49 44 4 2 3 06 110 NOTES 1 Right hand unit shown left hand unit opposite Coil connection locations are 5 8 inch 2 Unit sizes...

Page 25: ...lter 8 Air Vent 1 8 in MPT 9 Optional Valve Package inside cabinet 10 Drain Pan Auxiliary with 3 4 in MPT Drain Connection 11 Return Air Grille NOTES 1 Right hand unit shown left hand unit opposite Co...

Page 26: ...ille 7 Filter 8 Air Vent 1 8 in MPT 9 Front Panel Fastener 10 Optional Valve Package inside cabinet 11 Drain Pan Auxiliary with 3 4 in MPT Drain Connection 12 Return Air Grille NOTES 1 Right hand unit...

Page 27: ...Unit size 01 has one motor one blower size 03 has 2 motors 2 blowers 5 Unit has 1 2 in flanges for mounting to wall surface 6 Front panel hooks at top of unit swing down and snap in at bottom against...

Page 28: ...Motor Junction Box 2 Motor Blower Assembly 3 Electric Strip Heater Element optional 4 Auxiliary Drip Lip optional shipped loose 5 Tell Tale Drain optional 6 Drain Connection 7 8 in OD 7 Air Vent 1 8 i...

Page 29: ...turn Air Plenum 3 Mounting Clips shipped loose 4 Electrical Strip Heater Element optional 5 Auxiliary Drip Lip shipped loose with 3 8 in Hole 6 Tell Tale Drain optional 7 Drain Connection 7 8 in OD 8...

Page 30: ...A42 4122 NOTES 1 Right hand unit shown left hand unit opposite Coil connection locations are 5 8 inch 2 Standard 4 row coil shown Other coil option dimensional data available on request 3 Sizes 06 08...

Page 31: ...Side Access Panels 5 Electrical Strip Heater Element optional 6 Supply Air Duct Connection 1 in 7 Manual Air Vent 8 Filter Throwaway 1 in 9 Return Air Duct Connection 21 2 in 10 Drain 7 8 in OD 11 Bot...

Page 32: ...ary Drip Lip 5 Electric Strip Heater Element optional 6 Coil Inlet Copper Sweat Connection 7 Coil Outlet Copper Sweat Connection 8 Manual Air Vent 9 Filter Throwaway 10 Bottom Access Panel 11 Drain 7...

Page 33: ...ulation service clearances piping and electrical connections and any necessary ductwork For specific unit dimensions refer to Fig 13 23 Allow clearances according to local and national electric codes...

Page 34: ...and 42DC with bottom inlet may be installed in noncombustible return spaces only 5 Mounting units on the floor a Ensure wall behind the unit is smooth and plumb if necessary install furring strips on...

Page 35: ...drain pan or drip lip This helps minimize field piping insula tion requirements Refer to Fig 34 37 for pipe connection configurations NOTE Chilled water piping determines the hand of the unit Fig 31...

Page 36: ...depending on number of coil rows on factory supplied coil or arrangement of factory supplied valves 42VG 42VG a42 4177 HYDRONIC COIL ARRANGEMENT VERTICAL FLOOR UNITS 42VB VE VF Pipe into cabinet end c...

Page 37: ...package to be used for balancing water flow through the coil When isolation valve ball valve or ball valve with memory stop at position H is used for water flow balancing do not specify additional bal...

Page 38: ...4174 a42 4308 Fig 35 Two Way Motorized Control Valve Package with Aquastat Bleed Bypass Line The 2 way motorized valve motor drives valve open and a spring returns valve to normally closed position no...

Page 39: ...n 3 4 in etc 2 PIPE SYSTEM One Valve Package or 4 PIPE SYSTEM Two Valve Packages Application 2 Pipe Hydronic Heating Only 2 Pipe Hydronic Cooling Only 2 Pipe Hydronic Cooling with Total Electric Heat...

Page 40: ...Valve Package without Motorized Control When isolation valves only are specified they will be brazed to the coil stub outs Check job specifications for system pressure pressure drop limitations and fl...

Page 41: ...evation to ensure continu ous condensate removal Proper steam trap selection and installation is necessary As a guideline in creating a steam trap locate the steam trap dis charge at least 12 in below...

Page 42: ...N A 125 240 NO SWAGE Copper tube end expanded to accept a copper tube of the same size for factory or field brazing Application Used where possible for all tub ing joints for best joint integrity N A...

Page 43: ...system water during normal sys tem operation Should not be used in lieu of main system strainers Strainer screen may have to be removed during initial high pres sure system flushing during start up S...

Page 44: ...way motorized valve except with manual override lever engaged the valve is open to both ports and water flow will take the path of least resistance through the valve pack age not necessarily 100 thro...

Page 45: ...4 0 300 200 N A MODULATING VALVE Requires ETO Spring Return Modulating valves are designed to control the flow in the circuit by making incremental adjustments to the flow path within the valve Appli...

Page 46: ...sed to provide automatic summer or winter changeover for the system When a two pipe cooling heating system with optional auxiliary electric heat is desired an additional aquastat is required Units wit...

Page 47: ...ithout intended ductwork attached Units provided with outside air should have some method of low temperature protection to prevent freeze up This pro tection may be any of several methods such as a lo...

Page 48: ...after start up operations When steady stream of water begins to escape close valve Vent release air slow ly usually dripping water into drain pan in the process Make sure all service valves are open a...

Page 49: ...See Fig 42 and 43 Air System Balancing All duct stubs grilles filters and return access panels must be properly installed to establish actual system operating conditions BEFORE beginning air bal ancin...

Page 50: ...the cooling season to maintain a free flowing condensate Units provided with sec ondary or tell tale drain connection will indicate a clogged main line by flow from the tell tale connection NOTE Shoul...

Page 51: ...ter of the size shown in Tables 1 4 Do not attempt to clean and reuse disposable filters If the replace ment filters are not purchased from the factory the filters used should be the same type and siz...

Page 52: ...otentiometer and to the left of the orange relay 5 Attach the red positive lead of the meter to the red wire that bridges the 0 10 vdc outputs high medium and low 6 High Speed Close high speed relay b...

Page 53: ...below the status light 5 Attach the red positive lead of the meter to the high speed Flo1 terminal below the potentiometer 6 High Speed Using a small screwdriver turn the Flo1 po tentiometer so the m...

Page 54: ...rsion Typ ical 42CEA03 Rear Return Unit Shown in Pic tures Below 1 Remove filter and access panel 2 Install access panel on the rear of the unit with 5 screws 3 Bend the tabs on each of the plenum sid...

Page 55: ...3 Remove access panel 4 Install access panel on the rear of the unit 5 Install duct collar assembly 6 Slide the filter in the duct collar opening and install filter bracket Conversion is complete To...

Page 56: ......

Page 57: ......

Page 58: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420011 01 Printed in U S A Form 42 6SI Pg 58 11 17 Replaces 42 5SI...

Page 59: ...an rotation 7 Unit mounted level and square 39 Record electrical supply voltage 8 Proper access provided for unit and accessories 40 Record ambient temperatures 9 Proper electrical service provided 41...

Page 60: ..._________________________________________________________ ______________________________________________________________________________________________________________________________________________...

Reviews: