10
installation manual
Fig.6-6
Table 6-1
mm
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of
the outdoor units.
(Refer to Fig.6-6)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.
(Refer to
Fig.6-6)
6.4 Moving and installation
Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling.
>
60
cm
Fix with bolt
7. REFRIGERANT PIPE
Use the vacuum pump which vacuum level lower than
-0.1MPa and the air discharge capacity above 40L/min.
The outdoor unit is not necessary to vacuum, don’t open the
outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump could result as -0.1MPa or
below after 2 hrs or above operation. If the pump operated 3
hrs or above could not achieve to -0.1MPa or below, please
check whether water mix or gas leak inside of the pipe.
7.1 Vacuum with vacuum pump
1)
2)
3)
MODEL
A
B
C
D
E
H
F
38TSV
067P1
38TSV
052P1
38TSV
080P1
845
560
335
360
312
700
320
900
590
333
355
302
860
315
990
624
366
396
340
966
354
38TSV
130P1
Fig.6-2
Fig.6-2
Fig.6-2
634
404
448
368
1369
392
938
Fig.6-3
All the figures in this manual are for explanation
purpose only. They may be slightly different from the air
The actual unit shall prevail.
NOTE
conditioner you purchased.
Foundation could be on flat and is recommended be 100-300mm
higher than ground level.
Install a drainage around foundation for smooth drain
When installing the outdoor unit fix the unit by anchor bolts of
M10.
When installing the unit on a roof or a veranda,drain water
sometimes turns to ice on a cold morning. Therefore, avoid
draining in an area that people often use because it is slippery.
1
2
3
4
Concrete Foundation
No
Description
1 Outdoor Unit
2
Vibration-proof rubber
3 Anchor Bolt M10
4 Drainage (Wide 100×Depth 150)
5 Drainage
6 Mortar Hole (
Φ
100×Depth 150)
Table 6-4
Fig.6-7
≥
100
00
1
00
3
36
48
60
36
24
18
>30cm
>30cm
>200cm
>60cm
(Wall or obstacle)
Maintain channel
Air outlet
Air inlet
M
P
Air inlet
N
Fig.6-5
6.3 Space of installation and maintenance
Split type
outdoor unit
38TSV
110P1
634
404
448
368
1369
392
938
Fig.6-3