CAUTION

8.    INSTALL THE CONNECTING PIPE

Check whether the height drop between the indoor unit 
and outdoor unit, the length of refrigerant pipe
meet the following requirements:

All field piping must be provided by a licensed 
refrigeration technician and must comply with the 
relevant local and national codes.

Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation.

The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already.

Keep the connecting pipe dry, and do not let moisture in 
during installation.

   The Procedure of Connecting Pipes

8.1

Table 8-1

Model

42TSV052P1

42TSV067P1

42TSV080P1

42TSV110P1

The type of models

R410A inverter Split type air 

conditioner 

30

25 

25

25

15

10 

10

10

refrigerant pipe

The length of 

height drop

The max 

42TSV130P1

30

15

CAUTION

How to connect the pipes

Drill a hole in the wall (suitable just for the size of the wall 
conduit), then set on the fittings such as the wall conduit and 
its cover.

Bind the connecting pipe and the cables together tightly with 
binding tapes.
Pass the bound connecting pipe through the wall conduct 
from outside. Be careful of the pipe allocation to do on 
damage to the tubing.
 
Connect the pipes. Refer to "How to Connect the pipes" for 
details.

Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details.

open the stop values of the outdoor unit to make the 
refrigerant pipe connecting the indoor unit with the outdoor 
unit in fluent flow.

Check the leakage. Check all the joints with the leak detector 
or soap water.

Cover the joints of the connecting pipe with the soundproof / 
insulating sheath (fittings), and bind it well with the tapes to 
prevent leakage.

Execute heat insulation work completely on both sides of 
the gas piping and the liquid piping. Otherwise, this can 
sometimes result in water leakage.

1

2

3

5

6

7

4

Be sure to with insulating materials cover all the exposed 
parts of the flare pipe joints and refrigerant pipe on the 
liquid-side and the gas-side. Ensure that there is no gap 
between them.
Incomplete insulation may cause water condensation.

Flaring

1

Cut a pipe with a pipe cutter. 

(refer to Fig.8-1)

Table 8-2

(mm)

Ø6.4

14.2

17.2 N  m

(144

176 kgf  cm)

8.3         8.3

Ø9.5

32.7

39.9 N  m

(333

407 kgf   cm)

12.0       12.4

Ø12.7

49.5

60.3 N  m

(504

616 kgf  cm)

15.4       15.8

Ø15.9

Ø19.1

61.8

75.4 N   m

(630

770 kgf   cm)

97.2

118.6 N  m

(990

1210 kgf  cm)

18.6       19.0

22.9       23.3

R0.4~0.8

45

°±

2

90

°     

±

4

A

Insert a flare nut into a pipe and flare the pipe.

Refer to Table 8-2 for the dimension of flare nut spaces.

Fig.8-1

min

max

Pipe  gauge

Tightening   torque

Flare dimensin A

Flare     shape

90

Lean     crude     burr

11

installation manual

Fig.7-2

CAUTION

Don’t mix up the different refrigerants or abuse the tools and 
measurements which directly contact with refrigerants.

Don’t adopt refrigerant gas for air vacuuming.

If vacuum level could not get to -0.1MPa, please check whether 
resulted by leakage and confirm the leakage site.If no leakage, 
please operate the vacuum pump again 1 or 2 hrs. 

Connect with vacuum pump

Perform the pump (last for 2 hrs or above)

When get the vacuum level 
-0.1MPa, the pump should 
keep running for 20-60 mins

Shut down the 
vaccun pump

Place the vaccum state unused (1 hrs or above)

1. Close-off the valve of 
vacuum meter.
2. Cut off the connection 
between pressure meter 
and vacuum pump.
3. Close the vacuum 
pump.

Summary of Contents for 42TSV052P1

Page 1: ...NSTALLATION MANUAL Indoor Unit Outdoor Unit Power Supply 42TSV052P1 42TSV067P1 42TSV080P1 42TSV110P1 38TSV052P1 38TSV067P1 38TSV080P1 38TSV110P1 220 240V 50Hz 42TSV130P1 38TSV130P1 220 240V 50Hz 220 2...

Page 2: ...Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Page 3: ...m location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance must be installed 2 5m above f...

Page 4: ...y not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locat...

Page 5: ...rest TV set or stereo equipment it is necessary to prevent image disturbances or noise interferences Do not install the remote controller in a place exposed to direct sunlight or close to a heating so...

Page 6: ...LING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the service agent When handling the unit take into account the following 5 INDOOR UNIT INSTALLA...

Page 7: ...In general L is half of the screw length of the installation hook Refer to Fig 5 4 Locate the air conditioner firmly by wrenching the nuts after having adjusted the body s position well Refer to Fig...

Page 8: ...ight of the indoor unit through the openings on the panel s four corners if the lift of the indoor unit and the drainpipe is not influenced Refer to Fig 5 13 right Hang the air in grill to the panel t...

Page 9: ...OPEN Drainage test Drainage test Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling The unit with pump Remove the test cover and stow about...

Page 10: ...f two duct connection The air volume in one duct is around 200 260m3 h for model TSV052 to TSV080 unit The air volume in one duct is around 300 500m3 h for model TSV110 to TSV130 unit The max length o...

Page 11: ...ht If necessary install a blind that does not interfere with the air flow During the heating mode the water drained off the outdoor unit The condensate should be well drained away by the drain hole to...

Page 12: ...ove could not achieve to 0 1MPa or below please check whether water mix or gas leak inside of the pipe 7 1 Vacuum with vacuum pump 1 2 3 MODEL A B C D E H F 38TSV 067P1 38TSV 052P1 38TSV 080P1 845 560...

Page 13: ...water Cover the joints of the connecting pipe with the soundproof insulating sheath fittings and bind it well with the tapes to prevent leakage Execute heat insulation work completely on both sides o...

Page 14: ...g torque N M Turn clockwise to close Stop Valve size Shaft valve body Cap Valve lid 6 4 5 4 6 6 Hexagonal wrench 4 mm 13 5 16 5 11 5 13 9 9 5 12 7 8 1 9 9 18 22 15 9 13 5 16 5 Hexagonal wrench 6 mm 23...

Page 15: ...ally the indoor part should be covered evenly with the out let pipe sheath fittings and be bound tightly with the constrictor to prevent condensation caused by entered air To prevent water from flowin...

Page 16: ...acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditioners or electrical ovens For power details of the air conditioner refer to the r...

Page 17: ...and indoor units The gas side and liquid side stop valves are both opened The air conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote c...

Page 18: ...Power supply Switch Fuse Available locally Power wiring indoor Power linking wiring Outdoor Weak elec signal link wiring Indoor Unit Outdoor Unit Power supply Ground the air conditioner properly in ca...

Page 19: ...d2 or d3 The DR information including DR malfunction can not be displayed when the unit is off or under abnormal condition self clean operation or LED display feature is activated 1 DR mode 1 DR mode...

Page 20: ...R board First remove handle cover Plug in connector Insert the connector all the way Model A Model C Model B For some models to connect the DR board just remove the top panel Government A C Controller...

Page 21: ...202000192390...

Reviews: