background image

6

• Confirm that the ceiling is able to support the weight of

the unit. See Table 1 for nominal weight.

• There should be enough room within the false ceiling for

installation and maintenance (see Fig. 4).

• The false ceiling should be horizontal and leveled.
• Install the unit in a location within the room that allows

uniform air flow in all directions.

Select the unit position with the following points in mind:
• The unit should be installed in a position that is suitable

to support the total weight of the unit, refrigerant piping

and condensate.

• Proper access should be provided for maintenance for

refrigerant piping, EXV (electronic expansion valve),

electrical box, and condensate pump. A 2-ft clearance is

recommended all around the unit. 

• The unit should not be positioned directly above any

obstruction.

• The unit must be installed square and level.
• The condensate drain should have sufficient downward

slope (1 in. per 100 in.) in any horizontal run between

unit and drain. Maximum condensate lift is 29 

1

/

2

 inches.

Step 3 — Mount the Unit

INSTALLING HANGER BOLTS — Install the hanger bolts

at the locations shown in Fig. 2, top view. Use 

3

/

8

-in. all-thread-

ed rod. For unit weight, see Table 1.
MOUNTING UNIT — The unit can now be lifted on to the

hanging rods for mounting.

1. Use rods and fasteners to suspend the unit at the factory-

provided mounting holes. 

2. Adjust the height of the unit until the bottom is level with

the false ceiling, with adequate space to provide enough

pitch for the drain.

3. Secure the unit in position with locknuts and washers on

both sides of the mounting bracket. Ensure that the

threaded rod does not protrude more than 2 in. below the

mounting brackets as shown in Fig. 5.

INSTALLING DUCT — Connect the return and supply

ducts to the duct collars provided on the unit. Adequate dis-

tance between the return and supply diffusers should be main-

tained to avoid short circulation of air within the space. The fil-

ter is located on the return side of the unit, on the rear or bottom

depending on the return air inlet arrangement.
RETURN AIR ARRANGEMENT — Based on the return air

arrangement requirement in the field, the unit can be modified

from rear return to bottom return. As shown in Fig. 6, remove

return air duct collar/filter rack and plenum bottom panel.

Swap the position to change the rear return to bottom return ar-

rangement.

Step 4 — Connect Piping

CONDENSATE PIPING  — The  unit  is  supplied  with  a

1

1

/

4

-in. OD drain connection to connect copper or PVC drain

piping. When installing condensate piping, follow these recom-

mendations:
• Maximum pump lift is 29 

1

/

2

 inches.

• The highest point in the condensate piping should be as

close to the unit as possible. See Fig. 7.

IMPORTANT: 

Be sure that the ceiling grid is supported

separately from the unit. The ceiling grid must not be

supported by an part of the unit or any associated wir-

ing or piping work.

MINIMUM DRAIN
TILT 1/100

a40-1849

Fig. 4 — False Ceiling Installation

 

a40-1722

Fig. 5 — Threaded Rod

PLENUM BOTTOM PANEL

SIDE RAIL

RETURN AIR DUCT COLLAR
FILTER RACK

A40-1852

Fig. 6 — Return Air Arrangement

DRAIN TILT 1/100

32 TO 40 in.

< 8 in.

24 in.

 MAX.

a40-1850

Fig. 7 — Condensate Piping

Summary of Contents for 40WAD007

Page 1: ...rds DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death...

Page 2: ...ze Figure 2 shows unit dimen sions See Fig 3 for fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regul...

Page 3: ...wg 0 04 to 0 20 INDOOR NOISE LEVEL dBA Low 31 31 33 33 34 Medium 34 34 36 37 38 High 35 36 37 38 40 UNIT Unit Dimensions W x H x D in 27 1 2 x 8 1 4 x 19 3 4 36 1 4 x 8 1 4 x 19 3 4 44 7 8 x 8 1 4 x...

Page 4: ...1847 1 3 8 Fig 2 40WAD007 024 Dimensions NOTE All dimensions shown in inches 40WAD UNIT SIZE DIMENSION in A B C D E F G H I J K L M 007 012 27 1 2 8 1 4 19 3 4 17 3 4 30 3 4 1 1 4 20 1 8 5 8 5 3 4 23...

Page 5: ...erial on the motor or blower wheels will not be covered by the manufacturer s war ranty Some units and or job conditions may require some form of temporary covering during construction PREPARING JOBSI...

Page 6: ...for the drain 3 Secure the unit in position with locknuts and washers on both sides of the mounting bracket Ensure that the threaded rod does not protrude more than 2 in below the mounting brackets as...

Page 7: ...ring must comply with CSA C22 1 Electrical Code This equipment in its standard form is designed for an elec trical supply of 208 230 1 60 Any damage to or failure of units caused by incorrect wiring o...

Page 8: ...r electrical devices WIRED REMOTE CONTROLLER PROGRAMMA BLE To connect a programmable wired remote controller thermostat to the indoor unit use 4 core shielded cable and 4 pin connector from electrical...

Page 9: ...nd liquid line service valves are in open posi tion Drain Pump and Drainage Test Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 12 2 Us...

Page 10: ...addition Be sure all electrical connections are secure Check condensate pump operation if applicable Check the heating and cooling action to confirm proper operation TROUBLESHOOTING Figure 14 shows t...

Page 11: ...are short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance th...

Page 12: ...2 a40 1932 Fig B SW2 Settings POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON O...

Reviews: